Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Control valves and actuator

Fig. 9. Control valve and actuator (a) nomenclature (b) fail-open (F/O) or air-to-close (A/C) action and (c) fail-closed (F/C) or air-to-open (A/O)... Fig. 9. Control valve and actuator (a) nomenclature (b) fail-open (F/O) or air-to-close (A/C) action and (c) fail-closed (F/C) or air-to-open (A/O)...
For engineers to use pneumatics, they must design a pneumatic system. As we noted in Chapter 2, a system is a group of related components that work together to achieve a process. A typical pneumatic system consists of a compressor, a reservoir, transmission lines, control valves, and actuators. These components are shown in Figure 11-13. [Pg.242]

The components of a hydraulic system are similar to those of the pneumatic system. Figure 11-14 shows the components of a hydraulic system. The pressure of the hydraulic fluid is provided by the system s pump. The hydraulic pump is a device that creates flow in the system. The reservoir stores the hydraulic fluid before it is pressurized by the pump. Transmission lines carry the pressurized hydraulic fluid to the control valve and actuators. The control valves regulate the flow and pressure of the hydraulic fluid. The actuators transfer the fluid power into mechanical power. [Pg.243]

Process technicians use hydraulic systems (see Figure 9-6) to open or close valves, lift heavy objects, run hydraulic motors, and stop the rotation of a rotary or reciprocating device. A hydraulic system is a collection of equipment designed to apply pressure on a confined liquid in order to perform work. A similar process is used in the brake systems of most cars and trucks. A hydraulic system is composed of a fluid reservoir, strainer, pump, piping, flow control valve, pressure control valve, four-way directional control valve, and actuator (cylinder, piston). [Pg.213]

Check operation and calibration of all dampers, lubricate as required Check all pilot positioners for accuracy Check all control valves and actuators Calibrate all controllers as required Calibrate all transmitters Set receiver gauges as required... [Pg.501]

Valve Application Technology Functional requirements and the properties of the controlled fluid determine which valve and actuator types are best for a specific apphcation. If demands are modest and no unique valve features are required, the valve-design style selection may be determined solely by cost. If so, general-purpose globe or angle valves provide exceptional value, especially in sizes less than 3-inch NFS and hence are very popular. Beyond type selection, there are many other valve specifications that must be determined properly in order to ultimately yield-improved process control. [Pg.787]

This symbol is used to represent all types of control valve, and both pneumatic and electric actuators. [Pg.195]

Red a. Stop buttons or electrical switches used for emergency stopping of machines. b. Emergency stop handles or bars on machines. c. Hazardous operation indicating lights on control, alarm panels, or in the installation. d. Fire protection equipment and systems (e g., fire hydrants, monitors, reels, alarms, etc.). e. Portable flammable liquid containers. f. Stop condition. g. Identification of ESD isolation valves and actuators. [Pg.244]

The catalyst preparation area is positioned between the two polyethylene production units with 60 feet separating each one. The aluminum alkyls storage canopy and isopentane horizontal storage tank are located at a remote area at an approximate distance of 250 feet away from the production and utility areas. The isopentane is transported to the catalyst preparation area through a 3-inch pipeline. A remote actuated isolation valve on this supply line that fails closed is located at the isopentane storage tank. This control valve and an associated isopentane feed pump are managed by the operator in the control room. [Pg.369]

The microprocessor-based systems should be programmed, challenged, and validated to eliminate the exposure of one product to another through control failure. Valves and actuation devices used to divert product flows should be programmed properly and validated for their adequate functionality. [Pg.36]

Feed tank with control valve and gravimetric flow the desired flow rate is ensured by the appropriate opening of the valve, that is, the actuator of a control loop using the weight of the reactor or of the feed tank, the level in the feed tank, or a flow meter as input. The maximal feed rate can be limited by the clearance of the valve or by a calibrated orifice. [Pg.246]

Functional requirements and the properties of the controlled fluid determine which valve and actuator types are best for a specific application. If demands are modest and no unique valve features are required, the valve design style selection may be determined solely by... [Pg.79]

FIG. 8-80 Valve and actuator with valve positioner attached. (Courtesy Fisher Controls International LLC.)... [Pg.84]

Sample introduction is a major hardware problem for SFC. The sample solvent composition and the injection pressure and temperature can all affect sample introduction. The high solute diffusion and lower viscosity which favor supercritical fluids over liquid mobile phases can cause problems in injection. Back-diffusion can occur, causing broad solvent peaks and poor solute peak shape. There can also be a complex phase behavior as well as a solubility phenomenon taking place due to the fact that one may have combinations of supercritical fluid (neat or mixed with sample solvent), a subcritical liquified gas, sample solvents, and solute present simultaneously in the injector and column head [2]. All of these can contribute individually to reproducibility problems in SFC. Both dynamic and timed split modes are used for sample introduction in capillary SFC. Dynamic split injectors have a microvalve and splitter assembly. The amount of injection is based on the size of a fused silica restrictor. In the timed split mode, the SFC column is directly connected to the injection valve. Highspeed pneumatics and electronics are used along with a standard injection valve and actuator. Rapid actuation of the valve from the load to the inject position and back occurs in milliseconds. In this mode, one can program the time of injection on a computer and thus control the amount of injection. In packed-column SFC, an injector similar to HPLC is used and whole loop is injected on the column. The valve is switched either manually or automatically through a remote injector port. The injection is done under pressure. [Pg.381]

The rapid development of new methods of fabrication and microfluidic components enables the desired control and manipulation of small amounts of fluids. The microvalves in microelec-tromechanical systems (MEMS) are essential elements of a micro total analysis system. Typically, there are two types of microvalve one is the passive valve, the operation of which is dependent upon its surrounding pressure conditions, and the other is the active valve, which can be controlled actively. Active valves are categorized in three major ways initial working state, control pattern, and actuation principle. Each microvalve has advantages and disadvantages from the... [Pg.3309]

A combiuatiou of water discharge devices (sprinklers), distribution piping to supply water to the discharge devices or more sources of water under pressure, water flow controlling devices (valves), and actuating devices (temperature, rate of rise, smoke, or other type device). The system automatically delivers and discharges water in the fire area. [Pg.279]

In processes, by control actuators we mean any mechanism that transforms an electrical signal into a hydraulic or pneumatic change over the process variables, typically material flow. The most common actuators are control valves and servomotors, which execute commands like open, close, or similar operations as indicated by the controller. [Pg.40]

Pneumatic System Components. The major components are a compressor, an air storage tank (receiver), an air-cleaning apparatus composed of a main line filter, an air dryer, and a mist separator, all connected by a series of hoses. These sections are followed by an air-conditioning section composed of a filter, regulator, and lubricator, then a controlling section made up of a directional control valve and a speed controller, and, finally, the actuator or operating system for which the pneumatic system was designed to power. [Pg.1503]

Due consideration is also required on the potential role of SIF devices in mitigating damages when incidents do occur. External fires can often damage control valves or actuators, which are not designed to be fire-safe, and therefore cannot play a role in mitigating a fire after it has occurred. Separate fire-safe SIF isolation valves can be vital in mitigating such events. [Pg.124]


See other pages where Control valves and actuator is mentioned: [Pg.67]    [Pg.67]    [Pg.775]    [Pg.71]    [Pg.72]    [Pg.88]    [Pg.391]    [Pg.71]    [Pg.72]    [Pg.88]    [Pg.599]    [Pg.946]    [Pg.947]    [Pg.963]    [Pg.318]    [Pg.111]    [Pg.264]    [Pg.1187]    [Pg.1191]    [Pg.951]    [Pg.952]    [Pg.968]    [Pg.779]    [Pg.239]   
See also in sourсe #XX -- [ Pg.397 , Pg.398 , Pg.399 , Pg.399 ]




SEARCH



Actuator, control valve

Control Actuator

Control valve

Valve actuators

Valves actuated

© 2024 chempedia.info