Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Cooling water loops

Evaluate the integrity of the old cooling water loop piping, and i.Jemily ways to protect against its failure... [Pg.442]

The cooling-water circuit provides cooling water for the steam condenser and for the compressor intercooler. Since these units are constructed from mild steel, the cooling water used can be either sea water, river water or scheme water. Probably the second option is best because there are no further equipment materials requirements and this water is free. The total circulation through this cooling-water loop is approximately 120 000 kg (120 cubic metres). [Pg.280]

On the cooling water side, a loop system is normally used. Fresh cold cooling water (10-20 C) is supplied to a recirculating stream of cooling water (about 30 °C) in which the amount supplied is regulated by a temperature indicator/ controller in the cooling water loop. To avoid skin formation of paste on the inside tube surfaces, which would seriously hamper heat transfer, the differential between the cooling water temperature and the neutralisation temperature is kept close to 20 0. [Pg.163]

Figure 8.2 Schematic Diagram of Cooling Water Loop... Figure 8.2 Schematic Diagram of Cooling Water Loop...
Pressure drop around the cooling water loop is estimated as follows Pioop = 15 psi (pipe losses) + 5... [Pg.233]

Given a network structure, it is possible to identify loops and paths for it, as discussed in Chap. 7. Within the context of optimization, it is only necessary to consider those paths which connect two different utilities. This could be a path from steam to cooling water or a path from high-pressure steam used as a hot utility to low-pressure steam also used as a hot utility. These paths between two different utilities will be designated utility paths. Loops and utility paths both provide degrees of freedom in the optimization. ... [Pg.390]

A modification of the direct process has recentiy been reported usiag a ckculating reactor of the Buss Loop design (11). In addition to employing lower temperatures, this process is claimed to have lower steam and electricity utihty requirements than a more traditional reactor (12) for the direct carbonylation, although cooling water requirements are higher. The reaction can also be performed ia the presence of an amidine catalyst (13). Related processes have been reported that utilize a mixture of methylamines as the feed, but require transition-metal catalysts (14). [Pg.513]

Water. Water mains should be connected to plant fire mains at two or more poiats, so that a sufficient water supply can be deHvered ia case of emergency. The plant loop and its branches should be adequately valved so that a break can be isolated without affecting a principal part of the system. If there is any question of maintaining adequate pressure, suitable booster pumps should be iastaHed. Any connection made to potable water for process water or cooling water must be made ia such a manner that there can be no backflow of possibly contaminated water check valves alone are not sufficient. The municipal supply should faH freely iato a tank from which the water is pumped for process purposes, or commercially available and approved backflow preventers should be used. [Pg.98]

In order to avoid the need to measure velocity head, the loop piping must be sized to have a velocity pressure less than 5% of the static pressure. Flow conditions at the required overload capacity should be checked for critical pressure drop to ensure that valves are adequately sized. For ease of control, the loop gas cooler is usually placed downstream of the discharge throttle valve. Care should be taken to check that choke flow will not occur in the cooler tubes. Another cause of concern is cooler heat capacity and/or cooling water approach temperature. A check of these items, especially with regard to expected ambient condi-... [Pg.422]

Manifold barriers confine the radioactivity to the 1) ceramic fuel pellet 2) clad 3) cooling water, as demonstrated by the TMI-2 accident 4) primary cooling loop 5) containment and 6) separation from the public by siting. Further protection is provided by engineered safety systems pressurizers, depressurization, low pressure injection, high pressure injection and residmil heat removal systems. [Pg.208]

This cooling water is usually arranged in a closed loop with the water being pumped through secondary coolers or over cooling towers and then returned to the jackets for reuse. Water quality must be good, with steam condensate being preferred, properly treated to prevent corrosion, etc. [Pg.380]

NOTE Strongly alkaline, closed loop LPHW system formulations, such as nitrite/borates, typically include an azole product at about 4 to 5% (50% solution). Lower alkalinity products (often the molybdates) have significantly less, perhaps only 0.5%. For comparison, open cooling water and chilled water system formulations typically contain about 2 to 3 % (50% solution) azole. [Pg.401]

The components of the basic feedback control loop, combining the process and the controller can be best understood using a generalised block diagram (Fig. 2.29). The information on the measured variable, temperature, taken from the system is used to manipulate the flow rate of the cooling water in order to keep the temperature at the desired constant value, or setpoint. This is illustrated by the simulation example TEMPCONT, Sec. 5.7.1. [Pg.96]

This is a conventional water loop heat pump system using a boiler and cooling tower to maintain the water loop temperature (see Measures S15-S17 in Section 6.2). Since outside air handling unit and other terminal devices like unit heaters, wall fin convectors, etc which are often used with this water loop heat pump system need a different operating water temperature than that of the water loop, a plate heat exchanger is used between the primary heating circuit... [Pg.111]

Figure 19 depicts a water-loop heat pump system where the cooling tower and boiler have been replaced with a ground heat exchanger. This is the most common configuration of ground source heat pump used in commercial buildings. [Pg.117]

The exhaust air of the building is collected in three exhaust air handling units. Indirect evaporative coolers exploit the remaining cooling capacity of the exhaust air and cool the supply air in the dehumidifier via a water loop. This cold recovery makes the system more efficient. Depending on ambient... [Pg.439]

The lube oil must be maintained within a specific operating band to ensure optimum equipment performance. This is accomplished by controlling the flow rate of the cooling water with a temperature control loop. [Pg.120]

The actuating signal passes through the two control elements the temperature controller and the temperature control valve. The temperature control valve responds by adjusting the manipulated variable (the cooling water flow rate). The lube oil temperature changes in response to the different water flow rate, and the control loop is complete. [Pg.121]

Systems are designed to function normally even when a single instrument or control function fails. This is achieved with redundant controls, including two or more measurements, processing paths, and actuators that ensure that the system operates safely and reliably. The degree of redundancy depends on the hazards of the process and on the potential for economic losses. An example of a redundant temperature measurement is an additional temperature probe. An example of a redundant temperature control loop is an additional temperature probe, controller, and actuator (for example, cooling water control valve). [Pg.486]

Most disturbances in chemical engineering systems are load disturbances, such as changes in throughput, feed composition, supply steam pressure, cooling water temperature, etc. The feedback controller s Auction when a load disturbance occurs is to return the controlled variable to its set-point by suitable changes in the manipulated variable. The dosedloop response to a load disturbance is called the regulator response or the closed-loop load response. [Pg.171]

About 70 percent of the hydrogen is converted to electricity in the fuel cell stack, and the tail gas is then burned to generate heat which is transferred via a glycol/water loop to the steam generator. The same loop passes through the cooling plates or the fuel cell to remove heat. [Pg.49]

Utility functions such as the supply of steam and cooling water generally are set up to service several processes. Boiler feed water is prepared and steam is generated in a single boiler house. Noncontact steam used for surface heating is circulated through a closed loop, whereby various quantities are made available for the specific requirements of the different processes. The condensate is nearly always recycled to the boiler house, where a certain portion is discharged as blowdown. [Pg.253]


See other pages where Cooling water loops is mentioned: [Pg.106]    [Pg.158]    [Pg.219]    [Pg.603]    [Pg.213]    [Pg.220]    [Pg.241]    [Pg.232]    [Pg.106]    [Pg.158]    [Pg.219]    [Pg.603]    [Pg.213]    [Pg.220]    [Pg.241]    [Pg.232]    [Pg.457]    [Pg.27]    [Pg.388]    [Pg.350]    [Pg.7]    [Pg.328]    [Pg.2]    [Pg.96]    [Pg.206]    [Pg.416]    [Pg.224]    [Pg.108]    [Pg.112]    [Pg.115]    [Pg.116]    [Pg.129]    [Pg.56]    [Pg.327]   
See also in sourсe #XX -- [ Pg.213 ]




SEARCH



Cooling water

WATER-COOLED

Water loops

© 2024 chempedia.info