To maintain aerobic conditions and to avoid the formation of deposits, the flow conditions (flow rate and gradient) are particularly important in waste water pipelines. Therefore, for the different types of pipes used for estate drainage, minimum gradients which depend on the individual nominal diameter are specified in [3]. [Pg.290]

Nowadays, high-pressure flushing is used almost exclusively for the cleaning of waste water pipelines. This cleaning process serves to remove any deposits and blockages, and is also a preparatory measure for pipeline inspections and, if necessary, for repairs. [Pg.291]

To check the suitability of the sewer pipes for their use as a one-pipe system for waste water pipelines in drinking-water protected areas, an expert s report was commissioned [23]. Table 3 summarises the results of this report. Ductile sewer pipes are particularly suitable for the repetitive tests specified in the guidelines [24] with water or air or vacuum tests [25],... [Pg.296]

DIN EN 1124-3 [38] Pipes and fittings of longitudinally welded stainless steel pipes with spigot and socket joints for waste water pipelines - Part 3 System X Dimensions... [Pg.325]

Many cities of the world do not levy a separate fee on water distributed, and even in those places where water is in shortest supply, a minimal ration may be free to everyone. The problem of wasted water and unmetered water a dding to the overall water demand is not new. In ancient Rome, fountains were coimected to the pubHc water by privately installed and owned lead pipelines, many of which were unrecorded, illegal, and hence untaxed. Frontius, the water commissioner of Emperor Nerva of Rome in AD 96, developed cmde meters to increase revenue and cut demand. [Pg.236]

Semiat, R., Hasson, D., Zelmanov, G. and Hemo, I. (2004) Threshold scaling limits of RO concentrates flowing in a long waste disposal pipeline. Water... [Pg.241]

Oxygen utilization plans will be prepared. This will include applications to potable water treatment, waste water treatment, lake and river injection and the use for oxygen fired incineration. The oxygen use sites will be selected and the volumetric requirements for oxygen at each site will be estimated. The estimates will be used to establish the location of oxygen pipelines and distribution terminal points. New pipelines must be installed for the transport of oxygen. [Pg.182]

Soil and water contamination can occur not only by damage of pipelines. A majority of crude oil treatment processes need water either as cooling medium or heating agent in heat exchangers, or simply as a reagent. These avenues lead to oil-water contacts, which are responsible for formation of waste water that must be cleaned before it is released back to the environment. There are many different methods used for cleaning waste water. These can be classified as follows ... [Pg.306]

The leakages cause damage to other property, the capacity demand of the waste water system increases, costly repair is needed, and such work may conflict with other activities and traffic. To prevent this, one of the external coating systems that has been recommended for water pipelines in soil is 25 pm zinc -I- asphalt or bitumen [8.18]. [Pg.210]

In contrast to power stations with small and large pipes, in refineries there are many small pipelines for fire-fighting water, waste water, products, etc. Furthermore, refineries have a large area. Conventional cathodic protection can possibly be used for the small pipelines, but it is actually susceptible to trouble because of possible electrical bridging of the numerous insulating joints required. [Pg.315]

The main part of the WWTP is usually the aerobic biological activated sludge process. Around this central facility a complex of preparatory and subsequent separation operations is grouped. The facility may be a dedicated plant on the site of the polymer installation, a central facility in the site containing the polymer installation, or an external urban WWTP connected by dedicated pipeline or a sewer with little risk of storm overflow prior to the WWTP. The central waste water plant is normally equipped with ... [Pg.208]

Construction components of estate drainage systems within buildings, such as pipes, fittings, and pipe couplings for the connection, transporting, and collection pipelines must be suitable for a maximum waste water temperature of 368 K (95 C) at an ambient temperature of 283 K (10 C). The corresponding usability is checked in a system test under cyclic and continuous loading conditions [2]. [Pg.290]

For underground waste water sewers and pipelines, the pipes, fittings, and pipe connections must be suitable for diameters... [Pg.290]

During transport of mixtures of water and solids, as is usual in waste water sewers and pipelines, abrasion occurs in the region of the bottom of the pipe as a result of the action of the solids in the waste water. This abrasion depends on the... [Pg.291]

Table 3 Ductile cast-iron pipeline system for the transportation of waste water in drinking-water protection zones II [23]... Table 3 Ductile cast-iron pipeline system for the transportation of waste water in drinking-water protection zones II [23]...
In waste water sewers and pipelines in water-protection zone II, leakproof testing must be carried out at certain intervals during operation, at least every five years. Shorter intervals may be necessary, depending on the type and loading of the sewers and pipelines [24]. [Pg.299]

For waste water with a normal level of aggressiveness, a service life of e.g. 20 years is calculated for a hot-dip galvanised pipeline with a coating thickness of 100 pm and a 1 mm thick wall of the steel pipe. This is based on a corrosion rate of the hot-dip coating of approx. 5 to 10 pm/a (without excessive abrasion) and of the steel of 100 pm/a (without the normal erosion or cavitation loading) [37]. [Pg.305]

Corrosion damage to several components made of low-alloy steels and cast iron in the waste water treatment plant of a petroleum refinery were also caused by the action of sulphate-reducing bacteria. To prevent further damage, the pipelines were either replaced by those made of glass-fiber-reinforced polyester resin or they were lined with sulphate-resistant concrete [12]. [Pg.316]

The materials listed in Table 21 were investigated by simulating laboratory tests under operating conditions and exposure tests in waste water evaporator units of flue gas desulphurisation plants and waste incineration plants [64]. It was confirmed that only an approximate resistance can be estimated for the metallic materials in these plant sections. Precise material resistance data can only be determined for actual plants. The mass losses determined for alloy C-276 and alloy 59 after an exposure time of 9 months was only 0.053 mm/a (2.09 mpy) and 0.045 mm/a (1.77 mpy), respectively, with respect to the term of exposure. Therefore, they do not have technical significance. This results in the following proposal for materials for pipelines and tanks of waste water evaporator units of flue gas desulphurisation plants... [Pg.337]

UP/PHA resin suitability for glass fiber-reinforced molded parts that are exposed to corrosive media and environmental influences has contributed greatly to their wider application. On the basis of economic and technical factors, laminates based on unsaturated polyester resins and vinyl ester resins have become an indispensable, alternative material in industries with high corrosive loads, such as cellulose and paper [876], chlorine electrolysis [877], flue gas desulphurization in power plants and waste incineration plants, [878] and as pipelines for communal and industrial waste water [879]. [Pg.824]


See other pages where Waste water pipelines is mentioned: [Pg.312]    [Pg.312]    [Pg.1543]    [Pg.309]    [Pg.52]    [Pg.1346]    [Pg.202]    [Pg.194]    [Pg.1346]    [Pg.64]    [Pg.363]    [Pg.366]    [Pg.1365]    [Pg.447]    [Pg.105]    [Pg.1547]    [Pg.650]    [Pg.385]    [Pg.647]    [Pg.357]    [Pg.44]    [Pg.309]    [Pg.333]    [Pg.334]    [Pg.332]    [Pg.334]    [Pg.184]    [Pg.288]    [Pg.291]   