Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Set point ratio

The diagrams in Fig. 1 lb can be obtained by the so-called frequency-sweep method, where the lateral position and the distance Zc are fixed, while the frequency is varied around (O0. The Zc value corresponds to a given set-point ratio of the amplitude in contact to the free amplitude, rsp=Asp/Af. Depending on the tip-sample interaction, both the amplitude and the phase curve shifts in a certain direction. When the overall force is repulsive, the resonance frequency moves to higher values and results in a positive phase shift A(p=90 °-(p>0, where the phase shift of 90 ° corresponds to the free cantilever oscillations at ks=0 in Eq. 12. When the force is attractive the resonance frequency decreases compared to the free cantilever and Acp becomes negative. The situation in Fig. lib corre-... [Pg.78]

The one exception in which phase contrast is not due to the dissipation arises when the tip jumps between attraction phases (>90°) and repulsion phases (<90°). Since sine is a symmetric function about 90°, the phase changes symmetric even if there are no losses in the tip-sample interaction. The relative contribution of the repulsive and attractive forces can be estimated experimentally from the frequency-sweep curves in Fig. lib by measuring the effective quality factor as Qe=co0/Ao)1/2, where Ago1/2 is the half-width of the amplitude curve. The relative contribution of the attractive forces was shown to increase with increasing the set-point ratio rsp=As/Af. Eventually, this may lead to the inversion of the phase contrast when the overall force becomes attractive [110,112]. The effect of the attractive forces becomes especially prominent for dull tips due to the larger contact area [147]. [Pg.88]

Better control of the cantilever oscillation in liquid environment can be achieved when the cantilever is oscillated directly by an external force. This idea was implemented by the so-called Magnetic-Alternative-Current Mode (MAC Mode) [194]. A magnetic cantilever is driven by an external magnetic field which is generated by a solenoid placed beneath the sample. The direct excitation of the cantilever avoids unwanted resonance s from the cantilever holder, the fluid body, and the sample itself. Furthermore, the improved signal-to-noise ratio allows smaller oscillation amplitudes and set point ratios Asp/Af closer to 1. Both factors result in a significant reduction in the energy deposited into the sample,... [Pg.93]

According to this scheme, crystalHzation of PCL is initiated at the substrate interface. We can also estimate to a first approximation the height of the PMMA layer on the basis of the phase images at different set point ratios. A reduction of set point ratio from 0.96 to 0.83 corresponds to a reduction of probing ampH-tude of 3 nm (the free ampHtude is initially set to 24 nm). This result means that the thickness of the PMMA layer is 3 nm (Fig. 4.6b), since no changes are observed when working with tgp lower than 0.83, and it means that the PMMA... [Pg.55]

For imaging in IC-AFM (see Fig. 3.29), the amplitude of cantilever oscillation is used for feedback control, and the set point. Asp. is less than the free oscillation amplitude, A . This mode of operation is also referred to as amplitude modulation (AM) AFM. A convenient way to standardize the description of tapping conditions for both stiff and compliant materials is to use Ao, Asp, and Asp/Ao [108]. This ratio is called the set-point ratio r p. [Pg.110]

Figure 3.33. IC-AFM images of the free surface of a PMMA film containing 100 nm PBA latex particles. The height mode is on the left and the phase image is on the right. Free amplitude, A = 38 nm, A p = 30 nm, at a set-point ratio of 0.80. Figure 3.33. IC-AFM images of the free surface of a PMMA film containing 100 nm PBA latex particles. The height mode is on the left and the phase image is on the right. Free amplitude, A = 38 nm, A p = 30 nm, at a set-point ratio of 0.80.
Once the polished surfaces are prepared, they will need to be mounted in automated stages for analysis. This is facilitated by cryomicrotomy holders that are already designed to fit into AFM stages [188] (Leica Microsystems see Appendix VI). Automated image acquisition at prescribed locations is possible today with full and independent control over important imaging parameters used in IC-AFM, such as free amplitude, set-point ratio, scan size, scan speed, and signal gains. This allows automated acquisition of AFM data from combinatorial libraries. [Pg.450]

Foxboro developed a self-tuning PID controller that is based on a so-called expert system approach for adjustment of the controller parameters. The on-line tuning of K, Xi, and Xo is based on the closed-loop transient response to a step change in set point. By evaluating the salient characteristics of the response (e.g., the decay ratio, overshoot, and closed-loop period), the controller parameters can be updated without actually finding a new process model. The details of the algorithm, however, are proprietary... [Pg.735]

While process design and equipment specification are usually performed prior to the implementation of the process, optimization of operating conditions is carried out monthly, weekly, daily, hourly, or even eveiy minute. Optimization of plant operations determines the set points for each unit at the temperatures, pressures, and flow rates that are the best in some sense. For example, the selection of the percentage of excess air in a process heater is quite critical and involves a balance on the fuel-air ratio to assure complete combustion and at the same time make the maximum use of the Heating potential of the fuel. Typical day-to-day optimization in a plant minimizes steam consumption or cooling water consumption, optimizes the reflux ratio in a distillation column, or allocates raw materials on an economic basis [Latour, Hydro Proc., 58(6), 73, 1979, and Hydro. Proc., 58(7), 219, 1979]. [Pg.742]

Recommended nominal steam rates at 60 m/s exit velocity for a typical flare tip are shown in Figure 2. At lower velocities, higher steam ratios are required. Typical steam control consists of a flow ratio controller with adjustable ratio set point, related to flare gas flow. The ratio adjustment, located in the control house, provides for the higher steam ratios necessary at low flaring rates. [Pg.253]

Electronic air/fuel ratio characterization is becoming available. By driving gas and oil valves and the air damper separately via individual servo motors, electronic units can supervise the relative positions of the motors and provide characterization of air/fuel relationships utilizing an almost infinite number of set points to give close repeatable control. [Pg.378]

This is the equation of a straight line. One constructs a plot of the incremental concentration differences against the logarithm of their ratios. The line gives k = -slope and k = intercept/r. Figure 2-11 presents this plot for the same data set points to 90 percent completion were used, with 375 s chosen for t. [Pg.35]

The sulfonic acid flow passes through a second mass flow meter. If the mass flow of the sulfonic acid is different from the set point, it means that the S03/ organic ratio is incorrect (i.e., the resulting product may be under- or over-sulfonated) and an automatic controller resets the organic flow controller accordingly. [Pg.687]

In the above-described measurement, which we call the absolute method, all pumps have equal speeds (rpm) owing to interconnection to the same drive-shaft. In order to express, if required, a deviation registered for the analyte concentration, one must calibrate with a standard by varying its rpm (B) with respect to that of the titrant (A) a B/A rpm ratio greater than unity means a proportionally lower concentration and vice versa. In general, the absolute method serves to control a sample stream with nearly constant analyte concentration as a sensor one uses not only electroanalytical but often also optical detectors. However, with considerably varying analyte concentrations the differential method is more attractive its principle is that in the set-up in Fig. 5.15 and with the sensor adjusted to a fixed and most sensitive set-point, the rpm of the sample stream (C) is varied with respect to that of the titrant (A) by a feedback control (see Fig. 5.3a) from the sensor via a regulator towards the... [Pg.346]

By and large, a quarter decay ratio response is acceptable for disturbances but not desirable for set point changes. Theoretically, we can pick any decay ratio of our liking. Recall Section 2.7 (p. 2-17) that the position of the closed-loop pole lies on a line governed by 0 = cos C In the next chapter, we will locate the pole position on a root locus plot based on a given damping ratio. [Pg.104]

What we can do easily is to measure the fuel gas flow rate, multiply the value by R in the so-called ratio station, and send the signal as the set point to the air flow controller. The calculation can be based on actual flow rates rather than deviation variables. [Pg.198]

A more sophisticated implementation is full metering control (Fig. 10.6). In this case, we send the signals from the fuel gas controller (FC in the fuel gas loop) and the air flow transmitter (FT) to the ratio controller (RC), which takes the desired flow ratio (R) as the set point. This controller calculates the proper air flow rate, which in turn becomes the set point to the air flow controller (FC in the air flow loop). If we take away the secondary flow control loops on both the fuel gas and air flow rates, what we have is called parallel positioning control. In this simpler case, of course, the performance of the furnace is subject to fluctuations in fuel and air supply lines. [Pg.199]

Proportional gain, integral and derivative time constants to PI and PID controllers. Cohen-Coon was designed to handle disturbances by preventing a large initial deviation from the set point. The one-quarter decay ratio response is generally too underdamped for set point changes. [Pg.257]

Cascade control, along with ratio control, is used to control the temperature. The cold-water line is to have an air-to-close control valve. In case of failure in the air supply, the valve would open fully and a runaway reaction would be prevented. The hot-water line will have an air-to-open valve for similar reasons. After the two streams are mixed, the temperature will be measured. If it is above the desired temperature, the amount of air supplied to the valves will be reduced. This will increase the cold-water flow rate, and decrease the hot-water throughput. The result will be a reduction in the inlet water temperature. The desired temperature will be determined from a measurement of the reactor temperature. A deviation from the desired temperature will cause the set point of the second controller to be changed. This will result in a change of the inlet water temperature. [Pg.175]

In a comprehensive test program the characteristic functions of the ionization current and the primary air ratio as well as of the primary air ratio and the fan supply voltage have been gathered. A closed loop control has been designed on this basis, which also includes appliance start-up and calibration as well as a suitable, dynamic set point and actuator controls. [Pg.48]

Automatic control of distillate composition (xD) may also be affected by control of the reflux ratio, for example to maintain the distillate composition at constant set point (xDset). [Pg.161]

Hence, a theoretical reject pressure can be calculated from pressures measured in the field, together with a constant input from a ratio-cootrol unit. The theoretical pressure proportional to the reject flow rate is then used as the set point in the control loop. The measured variable pn, in the field can then be adjusted automatically by trimming a pressure-control valve in the reject line until the calculated pn) equals the measured pnj. [Pg.228]

A capsule summary of the merits of the three kinds of corrective action can be made. The proportional action is rapid but has a permanent offset that increases as the action speeds up. The addition of integral action reduces or entirely eliminates the offset but has a more sluggish response. The further addition of derivative action speeds up the correction. The action of a three-mode PID controller can be made rapid and without offset. These effects are illustrated in Figure 3.3 for a process subjected to a unit step upset, in this case a change in the pressure of the control air. The ordinate is the ratio of the displacements of the response and upset from the set point. [Pg.41]

Flow ratio control is essential in processes such as fuel-air mixing, blending, and reactor feed systems. In a two-stream process, for example, each stream will have its own controller, but the signal from the primary controller will go to a ratio control device which adjusts the set point of the other controller. Figure 3.17(a) is an example. Construction of the ratioing device may be an adjustable mechanical linkage or may be entirely pneumatic or electronic. In other two-stream operations, the flow rate of the secondary stream may be controlled by some property of the combined stream, temperature in the case of fuel-air systems or composition or some physical property indicative of the proportions of the two streams. [Pg.43]


See other pages where Set point ratio is mentioned: [Pg.63]    [Pg.80]    [Pg.87]    [Pg.912]    [Pg.912]    [Pg.55]    [Pg.202]    [Pg.110]    [Pg.118]    [Pg.105]    [Pg.111]    [Pg.590]    [Pg.63]    [Pg.80]    [Pg.87]    [Pg.912]    [Pg.912]    [Pg.55]    [Pg.202]    [Pg.110]    [Pg.118]    [Pg.105]    [Pg.111]    [Pg.590]    [Pg.747]    [Pg.225]    [Pg.75]    [Pg.150]    [Pg.613]    [Pg.974]    [Pg.422]    [Pg.106]    [Pg.207]    [Pg.502]    [Pg.492]    [Pg.442]    [Pg.554]    [Pg.36]    [Pg.301]   
See also in sourсe #XX -- [ Pg.110 , Pg.327 , Pg.450 ]




SEARCH



Set point

Setting point

© 2024 chempedia.info