Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Makeup water to replace

A float valve is provided to control the supply of makeup water to replace the water vapor that has flashed off, Tne flash tank should be insulated. [Pg.1122]

Float valves are required on all cooling tower systems. Their purpose is to supply makeup water to replace that lost by evaporation, blowdown, drift and system leakage. They are usually installed in the cold water basin and function to maintain a preestablished water level. A typical flowsheet showing the recommended arrangements for instrumentation and valves is given in Figure 7.4. [Pg.169]

Carbon dioxide is often ignored in steam systems. However, when absorbed in water, it forms carbonic acid, which can be corrosive to all parts of the steam and condensate system. Its potential presence is frequently overlooked in the design of heat exchangers, steam traps, condensate systems, deaerators, and water-treating systems. Most steam systems require continual addition of makeup water to replace losses. Makeup water must be adequately treated, by demineralization or distillation, to remove carbonates and bicarbonates. If these are not removed, they can be thermally decomposed to carbon dioxide gas and carbonate and hydroxide ions. The ions will normally remain in the boiler water, but the caron dioxide will pass off with the steam as a gas. When the steam is condensed, the carbon dioxide will accumulate since is is noncondensable) be passed as a gas by the steam trap or if the condensate and carbon dioxide are not freely passed by the steam trap, become dissolved in the condensate and form carbonic acid. If carbonic acid is formed it can have a pH approaching 4 and be very corrosive to copper and steel. Even if both the gas and condensate are passed freely by the steam trap, the gas will become soluble in the condensate when subcooling occurs. If oxygen is present, the corrosion rate Is accelerated. [Pg.268]

Economizer A counter-flow heat exchanger for recovering additional energy from the combustion products increasing the temperature of feedwater heater and minimizing the temperature difference between saturation temperature and feedwater tem]>erature. Feednmter It constitutes the makeup water to replace the water lost by evaporation and the condensate returned. [Pg.607]

The sulfur slurry that accumulates in the bottom of the settler vessel is periodically withdrawn and pumped through a plate and frame filter press where the sulfur is removed and the filtrate is returned to the process. The filtercake is then water washed and air blown to minimize catalyst losses (not shown). The wash water is returned to the system where it serves as a primary source of make-up water to replace that lost by evaporation. The water wash and air blow cycle are the determining factors in the chemical makeup requirements of the process. A small amount of catalyst concentrate is added after each filtration cycle to replace filtercake losses. It is claimed that no catalyst degradation occurs under normal operating conditions. The only other chemical make-up requirement consists of a small amount of alkaline solution for pH control. [Pg.796]

Demineralizers are often used to treat raw makeup water or condensate where high purity is required, such as in large central station boHers that operate at high steam pressures. Demineralizers employ a combination of cation and anion exchange to remove additional material, including sodium and ammonium cations. VirtuaHy aH salt anions, such as bicarbonate, sulfate, and chloride, are removed and replaced by hydroxide ions in the demineralizer. [Pg.7]

Fume scrubber water recycle. The steel finishing industry uses fume scrubbers to capture acid gases from pickling tanks. Scrubber water, which may contain a dilute caustic solution, is neutralized and recirculated continuously to adsorb the acid. Makeup water is added to replace water lost through evaporation and water that is blown down to end-of-pipe metals treatment. [Pg.66]

Makeup-This term refers to the water required to replace the circulating water that is lost by evaporation, drift, blowdown and leakage. It is expressed as a percentage of the water circulated and normally is automatically controlled by a float valve. [Pg.8]

An example of such a product is ioBio , marketed by Baltimore Aircoil Co. (BAC). It is proposed for small cooling systems. This system is, in effect, an in-line dispenser of prilled elemental iodine (U), with replaceable iodine canisters available. The equipment is placed in the makeup waterline to the tower, and in-line options include filters, water meters, and back-flow prevention devices. Claims made are that the biocidal action of the elemental iodine is not affected by changes in temperature, system load, or water chemistry. Also, the system is compatible with virtually all scale and corrosion inhibitors and does not contribute to the corrosion of metal surfaces. [Pg.206]

MAKEUP WATER - Water fed to a system to replace that which is lost -for example, water fed to a boiler to replace that lost as steam or condensate water fed to a cooling tower to repiace that lost by evaporation, drift, or other causes. [Pg.101]

RAW MAKEUP WATER - Untreated water fed to a system to replace that lost. [Pg.124]

IE. Process Control. There are many different approaches to control of the cooling water treatment and blowdown process. Figure 12.5 is an example. The dissolved solids concentration is indicated by the conductivity of the water. This property is used to control the rate of blowdown. The blowdown, the evaporated water, and any system losses are replaced by makeup water, added under sump level control or through a float-operated valve. In a different approach, the rate of blowdown is made proportional to the rate of makeup water addition. [Pg.1187]

To ensure the water quality of the primary and secondary circuit water, a purification system is deployed. In the primary circuit the system consists of pumps and ion-exchange filters. The maximum temperature of the water intended for purification is up to 80°C. The secondary circuit does not have a permanently acting purification system. Once every half year, partial replacement of the secondary circuit water is performed. The water is replaced by makeup water from the fresh water storage tanks. Contaminated water from the secondary circuit is later forwarded through the evaporator to tanks as pure condensate. [Pg.491]

Makeup Water added to the circulating water system to replace water lost from the system by evaporation, drift, blowdown, and leakage. [Pg.93]

Makeup fresh water in recirculating water systems must be added to replace losses from entrainment (drift, or windage), evaporation losses, and blowdown. Windage losses can be estimated as 0.1 to 0,3 percent of the recirculation rate for induced-draft towers. If makeup water introduces dissolved salts (hardness) which will otherwise accumulate, a small amount of water is deliberately discarded (blowdown) to keep the salt concentration at some predetermined level. A calculation is demonstrated in Illustration 7.11. Chlorine treatment of the water to control algae and slime and addition of chromate-phosphate mixtures to inhibit corrosion have been common in the past, but restrictions on discharges to the environment by the blowdown have led to the use of nonchromate inhibitors. Many other practical details are available [14, 15]. [Pg.248]

Makeup water. Replacement water added to the steam. [Pg.587]

Absorption of SO3 in concentrated sulfuric acid and the formation of H2SO4 from SO3 and H2O produce heat in the absorber, as does acid dilution from makeup water addition. Process control requires that the acid be cooled before it is recirculated to the dryer or absorber towers or sent to storage. Earlier acid coolers of parallel banks of stacked, irrigated, cast iron sections have been largely replaced by stainless steel shell and tube or plate exchangers, with or without anodic protection. Hastelloy, Sandvik SX, and Saramet alloys and Teflon also are used in acid piping and coolers. ... [Pg.474]


See other pages where Makeup water to replace is mentioned: [Pg.752]    [Pg.752]    [Pg.3198]    [Pg.295]    [Pg.552]    [Pg.583]    [Pg.301]    [Pg.312]    [Pg.1739]    [Pg.307]    [Pg.63]    [Pg.5]    [Pg.1177]    [Pg.295]    [Pg.364]    [Pg.493]    [Pg.1186]    [Pg.1191]    [Pg.3]    [Pg.120]    [Pg.156]    [Pg.385]    [Pg.516]    [Pg.375]    [Pg.190]    [Pg.463]   
See also in sourсe #XX -- [ Pg.248 ]




SEARCH



Makeup

Makeup water

© 2026 chempedia.info