Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Air Supply Device

The devices sending air to the stack can be fans, blowers, or compressors. They must meet two requirements (1) being able to send enough air to the stack for reaction (typically 2.5 to 3.0 times stoichiometric ratio), (2) being able to overcome the pressure drop caused by the stack. Fans can only be used for air-cooled stacks because their pressure boost is lower than several kPa. The advantages of fans are that they have the lowest power consumption and noise levels. Blowers and compressors are used for liquid-cooled stacks. Compressors have the highest power consumption and noise levels. Whenever possible, blowers should be used over compressors. A blower can achieve a pressure boost up to about 25 kPa. When the pressure need is more than a blower can provide, a compressor must be used. [Pg.186]

It is often worth the effort to build a stack with a lower air pressure drop so that a blower can be used. A lower pressure drop can be achieved by making the flow channels straighter, shorter, wider, and deeper. The stack may offer a slightly lower performance due to the lower air partial pressure. [Pg.186]

Relationship between power consumption versus air flow rate and pressure boost. [Pg.187]


The air distribution method and dimensioning of the air supply devices are important factors in determining the accumuiation of hear and contaminants. Examples of this are presented in Section 8.4. After the behavior of the air distribution method and devices are known, the characteristic effects ot the other airflow elements can be calculated. [Pg.654]

Respiratory protective equipment can be divided into two broad categories air purifying and air supplying devices. Air purifying devices are items such as dust masks, chemical cartridge respirators, and gas masks. The air supplying devices are hose masks, air line respirators, and self-contained apparatus. [Pg.142]

Respiratory Protection—Consists of air cleaning or air supplying devices that protect your breathing system from contaminants or supply fresh air in toxic/oxygen deficient atmospheres. [Pg.310]

The air pressure drop using 80% RH air was significantly higher (about 1 time more) than that using dry air. With 80% RH at °C, the total air volume entering the stack will be about 15% more than that of dry air, and this accounts for a smaller portion of the total air pressure drop. The larger portion is believed to be related to the partial blockage of the flow field channels by liquid water. Since the stack was intended to operate at a current density of less than 0.5 A cm , the air supply device had to be able to overcome around a 10 kPa pressure drop. [Pg.218]

Nickel carbonyl should be used in totally enclosed systems or under good local exhaust. Plants and laboratories where nickel carbonyl is used should make use of air-monitoring devices, alarms should be present in case of accidental leakage, and appropriate personal respiratory protective devices should be readily available for emergency uses. Monitoring of urinary nickel levels is useful to help determine the severity of exposure and identify appropriate treatment measures. Some large-scale users of nickel carbonyl maintain a supply of sodium diethyldithiocarbamate, or Antabuse, a therapeutic agent, on hand for use in case of overexposure. [Pg.14]

Health Hazards Information - Recommended Personal Protective Equipment Individual breathing devices with air supply neoprene gloves protective clothing eye protection Symptoms Following Exposure Inhalation of concentrated gas will cause suffocation. Contact will liquid can damage eyes because of low temperature. Frostbite may result from contact with liquid General Treatment for Exposure INHALATION remove to fresh air use artificial respiration if necessary. EYES get medical attention promptly if liquid has entered eyes. SKIN soak in lukewarm water (for frostbite) Toxicity by Inhalation (Threshold Limit Value) Data not available Short-Term Exposure Limits Data not available Toxicity by Ingestion Not pertinent (boils at -24.7°C) Late Toxicity Data not available Vtqtor (Gas) Irritant Characteristics Data not available Liquid or Solid Irritant Characteristics Data not available Odor Threshold Data not available. [Pg.130]

Ventilation noise originates primarily from fans and the air turbulence generated inside ducts and around supply air and exhaust air terminal devices. The appearance of the noise is, of course, affected by factors such as the speed of rotation and the power of the fan, and by how the fan is stabilized or in other ways acoustically insulated. The noise level and the frequency characteristics are also largely derermined by the velocity of the air inside ducts and around terminal devices, where factors such as the dimensions and appearance of the ducts and terminal devices may play a decisive role in the appearance of the noise. [Pg.346]

During summer. Fig. S. 6a, there is a need for cooling in the occupied zone (area up to 2 m from the floor level) rhus it is desirable to apply the stratification strategy with vertical temperature and contaminant stratification in the hall in order ro save cooling energy costs. This can be done, for example, by using a low-impulse air supply with the devices at the floor level. [Pg.638]

An exhaust hood requires an adequate supply airflow rate (direct supply or indirect from another room and transported through a transfer opening) inside the room where the exhaust is situated. This means that the supply airflow rate should be approximately equal to the exhaust rate and that the supply devices should be placed in such a way that the incoming air does not... [Pg.814]

Mostly the use of a supply inlet as a local ventilation system presumes that the supply device (with air from outside the room) is located inside a large room, which also has an adequate exhaust airflow rate or has convenient ex-haust/transfer openings for the airflow. It is also necessary that the exhaust flow rate is maintained (or pressure difference kept). Otherwise the air supply could change in rate or direction. Instead of using air from a ventilation system, the supply air could be taken from the room (volume) it is situated in. In this case, the room must also have a supply and an exhaust flow rate. It is often necessary to clean the air before it is used in the supply inlet. [Pg.917]

Impact of air supply or exhaust devices to room airflow... [Pg.1030]

Often the inlet device (air supply) in a ventilated room is geometrically complicated. To resolve the flow around such a device would require a very fine grid. Instead of trying to resolve the complex flow near the inlet device, one can choose to use the box method or the prescribed velocity method.Both methods are based on the observation that downstream of the inlet, the flow behaves like a wall jet. Thus it is important that the bound-... [Pg.1042]

In industrial ventilation the majority of air velocity measurements are related to different means of controlling indoor conditions, like prediction of thermal comfort contaminant dispersion analysis adjustment of supply airflow patterns, and testing of local exhausts, air curtains, and other devices. In all these applications the nature of the flow is highly turbulent and the velocity has a wide range, from O.l m in the occupied zone to 5-15 m s" in supply jets and up to 30-40 m s in air curtain devices. Furthermore, the flow velocity and direction as well as air temperature often have significant variations in time, which make measurement difficult. [Pg.1152]

Dampers Devices fitted in ductwork to provide a flow resistance to control the air supply. Dampers may be... [Pg.1427]

Displacement air diffusion Air diffusion where the mixing of supply air and room air external to the air terminal device is at a minimum. See also Air diffusion and Air terminal devices. [Pg.1430]

Induction supply ATD An air terminal device in which the primary air from the duct induces secondary airflow from the treated space in such a way that a high rate of mixing between the air from these two sources takes place within the device. [Pg.1451]

Primary airflow rate The mass or volume of air entering a supply air terminal device in unit time from an upstream duct or a plenum box. Or the air leaving through an opening and entering a space. [Pg.1469]

The total pressure of the air at any point in a closed system will he the sum of the static and velocity pressures. Tosses of pressure due to friction will occur throughout the system and will show as a loss of total pressure, and this energy must he supplied hy the air-moving device, usually a fan. [Pg.274]

Procuring equipment protective ensembles, air monitoring devices, sampling equipment, decontamination apparatus, and supplies (disposables, tape, notebook, and so on)... [Pg.600]

Brattice driers, incorporating a device for removing the dried material (Fig. 44) have been used in Germany. The moist material, spread in a thin layer over cloth stretched on wooden frames (1), is dried in warm air supplied via the ducting (2) at a rate of about 0.5 m/sec. Next to the frame on which the material is dried there is a tin funnel (3) with a built-in sieve in its base. This funnel is connected with the ventilating duct by a flexible tube. Each frame (7) contains about 1.2 kg of fulminate (dry substance). To dry a batch of fulminate at 65-70°C takes... [Pg.155]

If operated on clean, dry plant air, pneumatic controllers offer good performance and are extremely reliable. In many cases, however, plant air is neither clean nor dry. A poor-quality air supply will cause unreliable performance of pneumatic controllers, pneumatic field measurement devices, and final control elements. The main shortcoming of the pneumatic controller is its lack of flexibility when compared to modem electronic controller designs. Increased range of adjustability, choice of alternative control algorithms, the communication link to the control system, and other features and services provided by the electronic controller make it a superior choice in most of todays applications. Controller performance is also affected by the time delay induced by pneumatic tubing mns. For example, a 100-m run of 6.35-mm ( -in) tubing will typically cause 5 s of apparent process dead time, which will limit the control performance of fast processes such as flows and pressures. [Pg.72]

To decrease the start-up time and the electrical power demand requested for the air supply system, Whyatt et al. [10] redesigned the [ISV 3] system completely. The aim was to meet the U S Department of Energy ambient temperature start-up time demand targets, which are < 1 min by 2005 and < 30 s by 2010. Figure 2.84a shows the flow schematics of the device and the prototype is shown in Figure 2.84b. [Pg.377]

In a hydroelectric plant it is necessary to decrease the flow of water to a turbine very rapidly in the event of a sudden drop in the load. In such a case a relief valve may be opened so as to bypass water around the machine, and then this relief valve may be slowly closed. Alternatively, an air chamber may be used to absorb the shock. Some excess water may flow into this device and compress the air to a higher pressure. One disadvantage is that water under pressure absorbs air, so it is necessary to renew the air supply periodically by the operation of a small air compressor. Also, an air chamber has distinct size limitations. [Pg.506]

This is a very moving film about a 17-year-old boy in isolation. He can only receive guests while wearing a helmet with an air purification system. Ever since childhood he has had to wear an air purification device on his back. At home, he makes use of various air purification devices and always carries around a hose which supplies purified air. He has not been outside in more than eight years. He has DNA deficiencies and his father worked with chemical substances, which according to the movie accounts for this boy s disorders. [Pg.180]


See other pages where Air Supply Device is mentioned: [Pg.629]    [Pg.630]    [Pg.144]    [Pg.144]    [Pg.204]    [Pg.97]    [Pg.186]    [Pg.287]    [Pg.293]    [Pg.629]    [Pg.630]    [Pg.144]    [Pg.144]    [Pg.204]    [Pg.97]    [Pg.186]    [Pg.287]    [Pg.293]    [Pg.114]    [Pg.1609]    [Pg.347]    [Pg.352]    [Pg.880]    [Pg.890]    [Pg.918]    [Pg.347]    [Pg.58]    [Pg.165]    [Pg.54]    [Pg.143]    [Pg.56]    [Pg.377]    [Pg.99]    [Pg.127]   


SEARCH



Air supplying

© 2024 chempedia.info