Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Proportional band, controllers

Samples were heated on a Zeiss hot stage, modified by replacing the platinum sample temperature thermocouple by a more sensitive copper-constantan couple, located as close as possible beneath the sample cover slip. A second temperature program thermocouple was placed in contact with the ceramic heater frame of the hot stage. The stage was programmed at 2°C. per minute with a slope-proportional band controller. Temperature was controlled to 0.05°C. Ice reference junctions were used on both samples and program thermocouples. The output of the sample-ice junction thermocouple was recorded on the 0.5 mv. per inch z-axis of the Moseley x-y recorder. [Pg.10]

The reactor was heated using staged resistance heaters which received their power via proportional band controllers activated by thermocouple sensors... [Pg.178]

The Ziegler and Nichols closed-loop method requires forcing the loop to cycle uniformly under proportional control. The natural period of the cycle—the proportional controller contributes no phase shift to alter it—is used to set the optimum integral and derivative time constants. The optimum proportional band is set relative to the undamped proportional band P , which produced the uniform oscillation. Table 8-4 lists the tuning rules for a lag-dominant process. A uniform cycle can also be forced using on/off control to cycle the manipulated variable between two limits. The period of the cycle will be close to if the cycle is symmetrical the peak-to-peak amphtude of the controlled variable divided by the difference between the output limits A, is a measure of process gain at that period and is therefore related to for the proportional cycle ... [Pg.729]

The speed of the controller is adjusted by the proportional band and reset rate (proportional and integral gains). These parameters also influence the stability of the control loop. All control loops are limited to a gain of less than one at their critical frequency. Higher closed-loop gain will make the loop unstable. [Pg.394]

Proportional band In a proportional controller, the control point range through which the controlled variable must pass in order to move the final control element through its full operating range. [Pg.1469]

Stable control of reduced pressures is readily achieved by the use of two (or more) pressure-reducing valves in parallel (Figure 22.10). At full load and loads not too much below this level both valves are in use. As the load diminishes, the controlled pressure begins to increase and the valve which is set at the lower pressure begins to close. When the load can be supplied completely by the valve set at the higher pressure, the other valve closes. Any further load reduction causes the remaining valve to modulate through its proportional band. [Pg.323]

Dry bulb sensors may be bi-metal strips, thermistors or refrigerant-filled phials or bellows responding to pressure differences caused by temperature change. These, in turn, provide an electrical or mechanical signal. The mechanical items are used to alter the value of potentiometers or make-or-break contacts. The signals are transmitted to amplifiers, which respond to the degree of error. An important feature is the proportional band of temperature over which the controls call for up to full plant capacity. [Pg.440]

Generally, the proportional gain is dimensionless (i.e.. p(t) and e(t) have the same units). Many controller manufacturers use the percent proportional band, which is defined as... [Pg.84]

PI controllers are most common. They eliminate offsets and have acceptable speeds of response in most industrial settings. We usually pick a low to intermediate gain (wide proportional band, PB 150) to reduce the effect of noisy signals (from flow turbulence also why we do not use D control). We also use a low reset time ( 0.1 min/repeat i.e. relatively large I action) to get fast set-point tracking. [Pg.101]

Three terms commonly used to describe the proportional mode of control are proportional band, gain, and offset. [Pg.129]

Proportional band, (also called throttling range), is the change in value of the controlled variable that causes full travel of the final control element. Figure 14 shows the relationship between valve position and temperature band for two different proportional bands. [Pg.129]

The proportional band of a particular instrument is expressed as a percent of full range. For example, if full range of an instrument is 200°F and it takes a 50°F change in temperature to cause full valve travel, the percent proportional band is 50°F in 200°F, or 25%. Proportional bands may range from less than 1% to well over 200%. However, proportional bands over 100% cannot cause full valve travel even for full range change of the controlled variable. [Pg.129]

Gain, also called sensitivity, compares the ratio of amount of change in the final control element to amount of change in the controlled variable. Mathematically, gain and sensitivity are reciprocal to proportional band. [Pg.129]

With proportional control, the final control element has a definite position for each value of the measured variable. In other words, the output has a linear relationship with the input. Proportional band is the change in input required to produce a full range of change in the output due to the proportional control action. Or simply, it is the percent change of the input signal required to change the output signal from 0% to 100%. [Pg.130]

The proportional band determines the range of output values from the controller that operate the final control element. The final control element acts on the manipulated variable to determine the value of the controlled variable. The controlled variable is maintained within a specified band of control points around a setpoint. [Pg.130]

The proportional band is the input band over which the controller provides a proportional output and is defined as follows ... [Pg.131]

The controller has a proportional band of 100%, which means the input must change 100% to cause a 100% change in the output of the controller. [Pg.131]

If the fulcrum setting was changed so that a level change of 2 in, or 50% of the input, causes the full 3-in stroke, or 100% of the output, the proportional band would become 50%. The proportional band of a proportional controller is important because it determines the range of outputs for given inputs. [Pg.131]

The controller has been set for a proportional band of 50%. Therefore, a 50% change in the 200°F span, or a change of 100°F, causes a 100% controller output change. [Pg.133]

At time tb the measured variable increases by 100°F, or 50%, of the measured variable span. This 50% controller input change causes a 100% controller output change due to the controller s proportional band of 50%. The direction of the controller output change is decreasing because the controller is reverse-acting. The 100% decrease corresponds to a decrease in output for 15 psi to 3 psi, which causes the control valve to go from fully open to fully shut. [Pg.133]

If the measured variable drops below the setpoint, a positive error is developed, and the control valve opens further. If the measured variable goes above the setpoint, a negative error is developed, and the control valve throttles down (opening is reduced). The 50% proportional band causes full stroke of the valve between a +50°F error and a -50°F error. [Pg.134]

When the error equals zero, the controller provides a 50%, or 9 psi, signal to the control valve. As the error goes above and below this point, the controller produces an output that is proportional to the magnitude of the error, determined by the value of the proportional band. The control valve is then capable of being positioned to compensate for the demand disturbances that can cause the process to deviate from the setpoint in either direction. [Pg.134]

The proportional band is the change in input required to produce a full range of change in the output due to the proportional control action. [Pg.135]

A proportional plus integral controller is used to control the level in the reflux accumulator of a distillation column by regulating the top product flowrate. At time t = 0, the desired value of the flow controller which is controlling the reflux is increased by 3 x 10-4 m3/s. If the integral action time of the level controller is half the value which would give a critically damped response and the proportional band is 50 per cent, obtain an expression for the resulting change in level. [Pg.329]

The common types of control loops are level, flow, temperature, and pressure. The type of controller and the settings used for any one type are sometimes pretty much the same from one application to another. For example, most flow control loops use PI controllers with wide proportional band and fast integral action. [Pg.231]

A- FLOW LOOPS. PI controllers are used in most flow loops. A wide proportional band setting (PB — ISO) or low gain is used to reduce the effect of the noisy flow signal due to flow turbulence. A low value of integral or reset time (t, - 0.1 minute per repeat) is used to get fast, snappy setpoint tracking. [Pg.231]

The tuning of proportional level controllers is a trivial job. For example, we could set the bias value at 50 percent of full scale, the setpoint at 50 percent of full scale, and the proportional band at 50. This means that the control valve will be half open when the tank is half full, wide open when the tank is 75 percent full, and completely shut when the tank is 25 percent full. Changing the proportional band to 100 would mean that the tank would be completely full to have the valve wide open and completely empty to have the valve shut. [Pg.233]

Tray 4 temperature on the Lehigh distillation column i controlled by a pneumatic Pf controller with a 2-mipute reset time and a 50 percent proportional band. Temperature controller output (COr) adjusts the Ktpoint of a steam flow controller (reset time 0.1 min and proportional band 100 percent). Column base level is controlled by a pneumatic proportional-only controller setting bottoms product withdrawal rate. [Pg.243]

Proportional band settings of the reactor temperature controller, circulating jacket water temperature controller, and cooling water flow controller arc 20, 67, and 200, respectively. [Pg.244]

J6. The frequency response data given below were obtained by pulse-testing a closed-loop system that contained a proportional-only controller with a proportional band of 25. Controller setpoint was pulsed and the process measurement signal was recorded as the output signal. [Pg.497]

A setting knob is provided on the more traditional stand-alone controllers for the adjustment of Kc as well as a pointer to set the desired value. The setting knob for Kc is sometimes graduated in terms of proportional band. This quantity is defined as the error required to move the final control element over its whole range and is expressed as a percentage of the total range of the measured variable (see Example 7.1). In the newer MBC installations, the control action is simulated in the form of software and values of Kc and of the desired value are entered via an appropriate keyboard with the relevant values displayed on a VDU (Visual Display Unit)—see Section 7.19. [Pg.567]

The level of liquid in a tank is controlled using a pneumatic proportional controller as shown in Fig. 7.6. The level sensor is able to measure over the range 1.85 to 2.2S m. It is found that, after adjustment, the controller output pressure changes by 4 kN/m2 for a 0.01 m variation in level with the desired value held constant. If a variation in output pressure of 80 kN/m2 moves the control valve from fully open to fully closed, determine the gain and the proportional band. [Pg.567]


See other pages where Proportional band, controllers is mentioned: [Pg.439]    [Pg.439]    [Pg.726]    [Pg.726]    [Pg.746]    [Pg.777]    [Pg.199]    [Pg.131]    [Pg.59]    [Pg.223]    [Pg.234]    [Pg.238]    [Pg.288]    [Pg.671]    [Pg.672]    [Pg.748]    [Pg.234]   
See also in sourсe #XX -- [ Pg.194 , Pg.201 ]




SEARCH



Control banding

Proportional band

Proportional control

Proportional controller

© 2024 chempedia.info