Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Conductors minimum size

To contain the temperature of the electrical circuits within safe limits for a particular temperature class of the surroundings, the maximum current rating for a minimum size of a conductor is also stipulated in ICC 60079-1 I. The constructional requirements also stipulate the minimum clearances and creepage distances in air between the conducting parts of all the intrinsically safe L lectrical eirctiits. [Pg.183]

To determine the minimum size of ground conductor, consider a station grid made of Z coated steel, having the following parameters ... [Pg.713]

Consider GI for grounding, and the same parameters of Section 22.14.1, leading to a minimum size of grounding conductor as 80 A/mm, based on IS 3043. Fault level for a 400 kV power station as in Table 13.10 is 40 kA (envisaging no further rise in the fault level, /q = /g)... [Pg.715]

To delermine ihe minimum size of current-carrying conductors and decide on the mounting arrangement). [Pg.864]

To determine the mininumi size of conductor for i required faith lev el. to account for the thermal effects only one can use the following formula to detertiiine the minimum size ol conductor for tiny fault level ... [Pg.865]

Figure 28.5 Determining the minimum size of conductor for a required fault level... Figure 28.5 Determining the minimum size of conductor for a required fault level...
Ten 1. Omm PVC insulated cables are to be drawn into a plastic conduit which is 6 m long between boxes and contains one bend. A 4.0mm PVC insulated CPC is also included. Determine the minimum size of conduit to contain these conductors. [Pg.221]

Double socket outlets must have two terminals for protective conductors. One terminal to be used for each protective conductor, of a minimum size of 1.5 mm ... [Pg.341]

For TT systems, the minimum sizes of buried earthing conductors are given in Table 54A where a buried electrode is used. For other electrodes, such as a building metal frame and for TN-S systems, the size may be selected from Table 54G or calculated from the formula in section 543-01-03. For TT systems, however, it may not be possible to calculate because the earth fault loop impedance is not likely to be known until it can be measured. [Pg.151]

The minimum size of main equipotential bonding conductor for PME systems is given in Table 54H and is related to the size of the supply neutral. For new PME installations, the designer should ascertain the intended size of the supply conductors from the supply company and then select the size of the bonding conductor from Table 54H. [Pg.152]

Determine the minimum conductor size for a fault level of 50 kA for one second for an aluminium conductor. [Pg.865]

This minimum conductor size will take account of the healing effects only during the fault, irrespective of the current rating of the conductor. The required conductor size may be more than this, depending upon the continuous eurrent it has to carry, as discussed later. [Pg.865]

Nomograms Figure 28.6(a)-(d) have also been drawn based on equation (28.1). From these nomograms the minimum conductor size can be extrapolated that would be necessary to sustain a given fault level. [Pg.866]

The uncertainty principle is negligible for macroscopic objects. Electronic devices, however, are being manufactured on a smaller and smaller scale, and the properties of nanoparticles, particles with sizes that range from a few to several hundred nanometers, may be different from those of larger particles as a result of quantum mechanical phenomena, (a) Calculate the minimum uncertainty in the speed of an electron confined in a nanoparticle of diameter 200. nm and compare that uncertainty with the uncertainty in speed of an electron confined to a wire of length 1.00 mm. (b) Calculate the minimum uncertainty in the speed of a I.i+ ion confined in a nanoparticle that has a diameter of 200. nm and is composed of a lithium compound through which the lithium ions can move at elevated temperatures (ionic conductor), (c) Which could be measured more accurately in a nanoparticle, the speed of an electron or the speed of a Li+ ion ... [Pg.179]

The resist materials that were developed for the printing industry are also useful for the manufacture of semi-conductor devices. In retrospect, this is fortuitous since the demands of the two technologies are quite different. Consider, for example, the resolution required to print a newspaper where the goal is to generate legible print. Here the resolution need only be a fraction of a millimeter, whereas typical semi-conductor devices that are in production today have minimum features of two or three microns. These features are smaller than a typical bacterium and are comparable in size to the organelles of cells. [Pg.90]

Feature Sizes. Although minimum feature sizes in TFML interconnections are large relative to IC feature sizes (i.e., 25- xm versus l- xm line widths), the conductor and dielectric layers are substantially thicker in TFML structures, a fact that results in high aspect ratios. Conductor layers must be several micrometers thick to keep resistive losses low, and dielectric layers must be 10 to 30 xm thick to maintain low interconnection capacitance. Thus a thickness width aspect ratio as large as 1 1 is frequently required. This aspect ratio demands anisotropic-etching processes. [Pg.488]

The limitation to the size of the reactor with light conductors is the UV transparency of fhe maferial and the light distribution to the catalyst particle. The critical and probably the most intricate factor is the distribution of fhe available lighf in fhe conductors to the catalyst particles and to ensure that each particle receives at least the minimum amoimt of light necessary... [Pg.164]

His mathematical analysis deals with the problem of determining how much of one powder A, must be added to another powder B, to obtain continuity of powder A in a random mixture of the two. When more than the minimum is added, more continuity will result. Continuity is expressed as the probability that pairs of particles of powder A have radii, the sum of which just equals the distance between their centers. Forscher s mathematical analysis leads him to conclude that for an aggregate of equal-size spheres A is probably discontinuous if the ratio of A to B is below Both A and B are continuous when A/B exceeds this ratio and eventually B becomes discontinuous if B/A falls below In the discussion given, powder A is a good conductor of electricity, and powder B, a poor conductor. The degree of continuity of powder A was assumed proportional to the over-all conductivity of the compound powder mixture. [Pg.271]

When high voltage motors are being considered, it is usually found that the minimum conductor size of the cable is determined by the let-through fault withstand capability rather than the full-load or starting current. Cable manufacturers provide graphical data for fault withstand capabilities of their cables, which are based on practical tests. These aspects are also associated with the protection system used for the motor, e.g. a contactor-fuse combination, a circuit breaker, the protective relay characteristics (thermal, inverse time with or without instantaneous or earth fault elements). [Pg.124]

A1.5mm2 CPC is acceptable since this is the nearest standard-size conductor above the minimum cross-sectional area of 1.10mm found by calculation. [Pg.197]

A house extension has a total load of 6 kW installed some 18m away from the mains consumer unit for lighting. A PVC insulated and sheathed twin and earth cable will provide a sub-main to this load and be clipped to the side of the ceiling joists over much of its length in a roof space which is anticipated to reach 35°C in the summer and where insulation is installed up to the top of the joists. Calculate the minimum cable size if the circuit is to be protected by a type B MCB to BS EN 60898. Assume a TN-S supply, that is, a supply having a separate neutral and protective conductor throughout. [Pg.205]


See other pages where Conductors minimum size is mentioned: [Pg.547]    [Pg.695]    [Pg.702]    [Pg.712]    [Pg.721]    [Pg.462]    [Pg.1230]    [Pg.151]    [Pg.343]    [Pg.344]    [Pg.120]    [Pg.489]    [Pg.54]    [Pg.470]    [Pg.470]    [Pg.470]    [Pg.291]    [Pg.525]    [Pg.318]    [Pg.6]    [Pg.8]    [Pg.160]    [Pg.294]    [Pg.144]    [Pg.226]   
See also in sourсe #XX -- [ Pg.866 ]




SEARCH



© 2024 chempedia.info