Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Testing current

It is permissible to lest just one panel of a multi panel-assembly so long as the construction of other panels is similar and busbar arrangement and supports are the same. The value of the prospective short-circuit current may be determined from a calibrated oscillogram. The test current in any phase should not vary by more than 10% of the average in the three phases and must be applied for a predetermined time of I or. 1 seconds. Unless specified otherwise, this should be considered as to be I second. [Pg.429]

To isolate the circuit after the lest is over and to also interrupt the test in between, in case the test piece fails. The breaker must possess an instantaneous capacity of more than the test current and the short-circuit MVA of the feeding generator. To achieve the desired voltage it must be suitable to perform the duties of repeated short-circuit tests. [Pg.429]

Source side reactance L (to control the magnitude of the test current)... [Pg.429]

The maximum peak current also appears in phase Y and measures at 110.6 kAat the first loop of the current wave. This loop is 110.6/50, i.e. 2.21 times the test current and satisfies the requirement of Table 13.11. [Pg.433]

Before creating a fault condition, to obtain the required /sc the impedance of the test circuit is adjusted so that the required fault current is obtained in all the phases on creating a short-circuit. To provide the required thermal effect (/sc /). the duration of test, /, is then adjusted accor-dingly. The relevant standards therefore stipulate that the test current may be higher or lower than required and can be compensated by adjusting its duration, i. [Pg.433]

This is measured between phase to phase or phase to neutral, depending upon the availability of the neutral. The test current is kept at the rated value for the equipment or the system under test. For the system shown in Figure 20.9(a). [Pg.663]

The protection current produced by the usual full-wave rectifier has a 100-Hz alternating component of 48%. There are receivers with selective transmission filters for 100 Hz, which corresponds to the first harmonic of the cathodic protection currents [45]. With such a low-frequency test current, an inductive coupling with neighboring pipelines and cables is avoided, which leads to more exact defect location. [Pg.123]

Output fuse failure Test current limitation, remove overloading or short circuit, set control device... [Pg.239]

Balls, M. and Worth, A.P (Eds.) (2002). Alternative Methods for Chemicals Testing Current Status and Future Prospects. ATLA 30, Supplement 1, 71-80. [Pg.338]

Rapid tests (currently Detects HIV antibodies within minutes of sample application... [Pg.1257]

NS (children, environmental exposure) Neurological Impaired motor and cognitive function 40-50,20 years before testing current mean, 2.9 Stokes et al. 1998... [Pg.43]

Worth AP, Balls M (eds) (2002) Alternative (non-animal) methods for chemicals testing current status and future prospects. A report prepared by ECVAM and the ECVAM working group on chemicals. ATLA 30(Suppl 1), pp 125... [Pg.89]

Abstract. We have performed the chemical analysis of extragalactic carbon stars from VLT/UVES spectra. The derived individual abundances of metals and s-elements as well as the well known distance of the selected stars in the Small Magellanic Cloud and the Sagittarius dwarf galaxies permit us to test current models of stellar evolution and nucleosynthesis during the Asymptotic Giant Branch phase in low metallicity environments. [Pg.262]

The USA monitoring and surveillance programs for detecting antibiotic residues in the domestic and imported meat supply are described. An overview of the field/laboratory tests currently in use is also provided ... [Pg.137]

Add a test current source as shown. The test current source is added between nodes 1 and 0 because we are interested in the impedance between those two nodes. Either an AC current or an AC voltage source can be used. Wire the circuit shown. Note that ground now serves as node 0. [Pg.321]

A systematic, generalized approach for the scale-up of granular mixing devices is still far from attainable. Clearly, more research is required both to test current hypotheses and to generate new approaches to the problem. [Pg.178]

The Microsemi data sheet of the 1N4733A shows a nominal zener voltage of 5.1 V at a test current of 49 mA. The IsSpice model shows 5.101 V at 49 mA, while the Micro-Cap model shows 5.819 V at a current of 42 mA. With results such as these, the logical question is, are the models correct ... [Pg.171]

The zener diode used for this simulation is used in its soft region, which means that it is used below its recommended test current. This region is often not defined in data books, and may not be correctly... [Pg.183]

PSpice did not have a similar zener diode in its library, so a 1N4728 zener diode model was downloaded from an unnamed Web site. You could also use a voltage source set at 3.3 V in place of the zener. This would assume that the zener is used at its test current, IZT, which biases the PSpice results however, if asked to build this circuit by using only the models that were contained in PSpice, this would be a natural assumption to make. [Pg.184]

These results show that all three of the SPICE simulators were not equipped to handle simulations of this particular zener diode in its soft region. However, zener diodes are not well defined or tested in this region of operation, so it may just be that the circuit tested had a worse than average zener diode in it. To further explore this problem, the experiment was modified to put more current than the specified test current in the zener diode. The circuit with these modifications made is shown in Fig. 6.64. The measurements across the zener diode are shown in Table 6.6, and the the resistance-to-voltage response is contained in Fig. 6.65. [Pg.185]

The 1N4728 has a test current of 78 mA for the "hard case, 98 mA was used to drive it. For the soft case, the zener current was only about 3 mA. Using such a wide operating range for a zener diode invites the flaws of the models to show up. If we only looked at the operating point... [Pg.185]


See other pages where Testing current is mentioned: [Pg.20]    [Pg.432]    [Pg.433]    [Pg.434]    [Pg.594]    [Pg.617]    [Pg.663]    [Pg.355]    [Pg.215]    [Pg.616]    [Pg.88]    [Pg.83]    [Pg.15]    [Pg.84]    [Pg.525]    [Pg.868]    [Pg.232]    [Pg.917]    [Pg.49]    [Pg.249]    [Pg.41]    [Pg.53]    [Pg.168]    [Pg.176]    [Pg.698]   
See also in sourсe #XX -- [ Pg.16 ]




SEARCH



Carcinogenicity test, current

Current Requirement Tests

Current Spike Test

Current Test Organisms

Current interrupt test

Current transformers type tests

Currents testing for

Direct current polarization test

Direct current polarization test methods

Dynamic currents testing

Eddy current nondestructive testing

Eddy current testing

Eddy-current tests

Electrical tests current-carrying capacity

Field testing, current status

Inspections eddy current testing

Recommended test current

Speed-current tests

Work package 1 Evaluation of current test procedures and experimental facilities for cyclic oxidation testing

© 2024 chempedia.info