Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Front wall loading

Rear wall loading is normally used only to determine the net overall frame loading. Because the rear wall load is opposite in direction to the front wall load, its inclusion tends to reduce the overall lateral blast force. Rear wall effects are many... [Pg.19]

The loads from external near-surface burst explosions are based on hemispherical surface burst relationships. Peak pressure (P psi) and scaled. impulse Ci/W psi/lb ) are plotted vs. scaled distance (R/W ft/lb ). Roof and sidewall elements, side-on to the shock wave, see side-on loads (P and i ). The front wall, perpendicular to the shock wave, sees the much higher reflected shock wave loads (P and i ). An approximate triangular pressure-time relationship is shown in Figure 5a. The duration, T, is determined from the peak pressure and impulse by assuming a triangular load. Complete load calculations include dynamic loads on side-on elements, the effect of clearing times on reflected pressure durations, and load variations on structural elements due to their size and varying distance from the explosive source. [Pg.101]

The side walls are defined relative to the explosion source as shown in Figure 3.6. These walls will experience less blast loading than the front wall, due to lack of overpressure reflection and to attenuation of the blast wave with distance from the explosion source. In certain cases, the actual side wall loading is combined with other blast induced forces (such as in-plane forces for exterior shear walls). The general form of side wall blast loading is shown in-Figure 3.8,... [Pg.18]

The shape of (he rear wall loading is similar to that for side and roof loads, however the rise time ami duration arc influenced by a not well understood pattern of spillover from the roof and side walls and from ground reflection effects. The rear wall blast load lags that for the front wall by L/U, the lime for the blast wave to travel the length, L, of the building. The effective peak overpressure is similar to that for side walls and is calculated using Equation 3.11 (Ph is normally used to designate the rear wall peak overpressure instead of P,). Available references indicate two distinct values for the rise lime and positive phase duration. [Pg.19]

The rear wall is proportioned the same as the front and side walls, spanning vertically from foundation to roof. Because the highest loads are on the front wall, a rear wall analysis would only be. necessary to determine a net loading on the overall building. The analysis will be for a wall segment 1 foot wide. [Pg.21]

This chapter provides an example of the evaluation and retrofit of the masonry walls of an existing reinforced concrete framed building using the principles outlined in Chapter 10. The evaluation of the roof, structural framing and foundation are not covered in this example. The explosion magnitude and front wall blast load are determined by others. The analysis of the exterior walls, and upgrade options, arc presented in this example. [Pg.253]

The overall load on a structure is also a function of the size of the structure. The effect of the lateral distribution of load local to an obstruction (front wall of a structure facing the blast) should be carefully analysed. For structures with depths less than about 50 m parallel to the direction of travel of the blast wave, the blast load would have largely passed the structure before the structure had time to respond to the blast wave since the wave is always travelling at or above the speed of sound. For a 50 m deep structure, the peak blast wave front would only engage the structure for about 0.02 s, which is typically well below the global fundamental natural period of the structure but not necessarily the local element response period. [Pg.95]

New England Power s Salem Harbor Station Coal At high load 50-60% At low loads 60-75% (Refer to note 2) l5/kW 900/ton NO, Being converted for longterm testing. Front wall-fired dry bottom boiler. N2O emissions were consistent with previously reported results. [Pg.893]

The concrete block walls of the cell housing the generator tube and associated components are 1.7 meters thick. The facility also includes a Kaman Nuclear dual-axis rotator assembly for simultaneous transfer and irradiation of reference and unknown sample, and a dual Na iodide (Nal) scintillation detector system designed for simultaneous counting of activated samples. Automatic transfer of samples between load station to the rotator assembly in front of the target, and back to the count station, is accomplished pneumatically by means of two 1.2cm (i.d.) polyethylene tubes which loop down at both ends of the system and pass underneath the concrete shielding thru a pipe duct. Total one-way traverse distance for the samples is approx 9 meters. In performing quantitative analysis for a particular element by neutron activation, the usual approach is to compare the count rates of an unknown sample with that of a reference standard of known compn irradiated under identical conditions... [Pg.358]

The response of the overall structure may be determined by the same techniques described above. The difference between directly loaded elements and supporting elements is the force amplitude and pulse shape of the applied loading. The loading on the overall stmctural system is determined from the reaction force time histories from directly loaded elements. Note that the loads on supporting members, frames, or shear walls, in some cases, may comprise reaction forces from pressures acting on the front and back faces of the structure simultaneously, taking into account the different arrival times of the blast wave. [Pg.136]

Fig. 2.49.2. Schema of a freeze drying production plant with approx. 20 m2 shelf area. The chamber and condenser are in the same vacuum chamber, separated by a wall in which the valve is built, providing the shortest possible path for the water vapor. The condenser and the brine heat exchanger are cooled by LN2. The condenser surface is made from plates (Fig. 2.49.3), its temperature can be controlled between -110 °C and -60 °C. The shelves can be controlled by the circulated brine between -70 °C and +50 °C. The trays with product can be automatically loaded and unloaded from a trolley. The shelves can be pressed together in one block and the trays are loaded to the shelves by pushing one shelf after another in front of the trolley. Fig. 2.49.2. Schema of a freeze drying production plant with approx. 20 m2 shelf area. The chamber and condenser are in the same vacuum chamber, separated by a wall in which the valve is built, providing the shortest possible path for the water vapor. The condenser and the brine heat exchanger are cooled by LN2. The condenser surface is made from plates (Fig. 2.49.3), its temperature can be controlled between -110 °C and -60 °C. The shelves can be controlled by the circulated brine between -70 °C and +50 °C. The trays with product can be automatically loaded and unloaded from a trolley. The shelves can be pressed together in one block and the trays are loaded to the shelves by pushing one shelf after another in front of the trolley.
Normal Reflection. An upper limit to blast loads is obtained if one interposes an infinite, rigid wall in front of the wave, and reflects the wave normally. [Pg.8]

The above lateral forces were determined from the combination of front and rear wall peak reactions neglecting any difference in time phasing. A more numerically complex approach would have been to determine lateral and vertical loads at each time step, and use the maximum value for foundation design. Such an approach would have resulted in lower toads. [Pg.96]

On an analytical damped balance (see Fig. 22), tenths and hundredths of a gramme are loaded with the aid of a special mechanism manipulated by means of disks at the right-hand side of the front balance wall. Thousandths and ten thousandths of a gramme are indicated by the position of the pointer on an illuminated scale in the lower part of the balance between its pans. [Pg.38]

Fig. 2.73.2. Sterile wall with two freeze-drying plants (10 m2 shelf area each), one loading storage (front) with 10 divided shelves and one unloading storage (behind transfer cart). Fig. 2.73.2. Sterile wall with two freeze-drying plants (10 m2 shelf area each), one loading storage (front) with 10 divided shelves and one unloading storage (behind transfer cart).
In practical combustion systems, the predominant mode of heat transfer is usually not molecular conduction, but turbulent diffusion, except at the boundaries and the flame front. Conduction is the only mode of heat transfer through refractory walls, and it determines ignition and extinction behaviors of the flame. Turbulent diffusion, an apparent or pseudo conduction mechanism arising from turbulent eddy motions, will be discussed in Section 4.4. The relations from the theory of conduction heat transfer15-17 can be used to evaluate heat losses through furnace walls and load zones, and through the pipe walls inside boilers and heat exchangers, etc. [Pg.151]


See other pages where Front wall loading is mentioned: [Pg.20]    [Pg.114]    [Pg.155]    [Pg.20]    [Pg.114]    [Pg.155]    [Pg.69]    [Pg.39]    [Pg.76]    [Pg.77]    [Pg.215]    [Pg.233]    [Pg.69]    [Pg.139]    [Pg.436]    [Pg.661]    [Pg.397]    [Pg.557]    [Pg.181]    [Pg.66]    [Pg.49]    [Pg.39]    [Pg.52]    [Pg.93]    [Pg.70]    [Pg.65]    [Pg.287]    [Pg.323]    [Pg.315]    [Pg.102]    [Pg.41]    [Pg.399]   
See also in sourсe #XX -- [ Pg.2 , Pg.3 , Pg.3 , Pg.4 , Pg.4 , Pg.5 , Pg.5 , Pg.6 , Pg.6 , Pg.7 , Pg.7 , Pg.8 , Pg.8 , Pg.9 , Pg.9 , Pg.10 , Pg.10 , Pg.11 , Pg.11 , Pg.12 , Pg.12 , Pg.13 , Pg.13 , Pg.14 , Pg.20 ]




SEARCH



Wall loading

© 2024 chempedia.info