Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Flammable atmospheres

Static charge generation causes an ignition hazard only if the accumulated charges create an electric field sufficient to produce an electrical discharge in a flammable atmosphere. In most processes, this means that the electric field intensity at some location must reach the breakdown strength of air (nominally 3 X lO " V/m). The objective of static-control measures is to ensure that electric field intensities cannot reach this value. [Pg.2333]

Provide vacuum relief device/system (can be a source of oxygen in vapor space resulting in flammable atmosphere)... [Pg.48]

Inadequate ventilation in ducts due to partial obstructions or closed dampers leading to creation of flammable atmosphere. Possibility of fire/explosion. [Pg.50]

Design to contain overpressure where practical Maintain ignition source control Maintain use of inert atmosphere Provide automatic isolation via quick closing valves of manifold duct system on detection of fire/flammable atmosphere or overpressure in duct system... [Pg.51]

Provide automatic sprinkler system/inerting gas Provide deflagration vents Provide deflagration suppression system Monitor flammable atmosphere/fire Provide nitrogen blocks (nitrogen injection to stop flame propagation) or other explosion isolation measures... [Pg.51]

Ignition of flammable atmosphere in vessel vapor space. [Pg.55]

Provide emergency purge and/or isolation activated by detection of flammable atmosphere or high oxygen concentrations... [Pg.55]

Inert gas not present leading to creation of flammable atmosphere. [Pg.86]

Vacuum transfer into reactor, drum or feed tank runs dry, resulting in air being pulled into vessel, creating flammable atmosphere. Potential for fire/explosion. [Pg.87]

Ignition of flammable atmosphere for open filters or solvent may be above flash point with air present when cleaning or unplugging closed filters. This may necessitate tight control of ignition sources to prevent a fire/explosion. [Pg.102]

Protect cables from steam, water, oil leaks, corrosive or flammable atmosphere, heat sources etc. [Pg.118]

Intrinsic Safety. Static electrical concepts such as minimum ignition energy do not directly apply when assessing the safety of electrical circuits such as radios, flashlights and instmmentation. Intrinsically safe electrical equipment is usually available which has been subjected to fault analysis and testing. The equipment must be certified for the flammable atmosphere in which it will be used (NFPA 497). Refer to texts on Intrinsic Safety such as [63]. [Pg.5]

A static discharge must coincide in time and space with a flammable atmosphere. [Pg.17]

A locally ignited flame must propagate into a surrounding flammable atmosphere. [Pg.17]

It is recommended that flammability always be assessed first, since it is inherently safer to avoid flammable atmospheres than to avoid sources of ignition such as static electricity. If a flammable atmosphere cannot be avoided at all times, the system should be designed to minimize both the probability and consequences of ignition. In this chapter it is assumed that static electricity is the only source of ignition however, in practical situations all sources of ignition such as those described in [ 157] should be evaluated. [Pg.47]

The potential to form a flammable atmosphere is addressed using methods discussed in Chapters 5 and 6. [Pg.47]

Of the instmments described only some are suitable for use outside the laboratory. Where any instrument is carried into a flammable environment it should either be certified as intrinsically safe for exposure to the flammable atmosphere or isolated from the atmosphere such as by keeping it within a purged enclosure. Any probe connected to the instmment must be separately considered as a possible ignition source. Electrometers are described in [ 1531. A more general review of electrostatic instruments is given in [ 136]. [Pg.50]

General measures for controlling flammable atmospheres inside equipment are described in NFPA 69 Explosion Prevention Systems. These measures do not necessarily prevent flammable atmospheres in some practical cases, such as when powders are added to an inerted vessel via an open manway. Where possible such cases are identified in the relevant sections of Chapters 5 and 6. [Pg.81]

Small concentrations of volatile components in a liquid mixture may accumulate in the vapor space of a container over time and appreciably reduce the flash point relative to the reported closed-cup value. This may be the result of degassing, chemical reaction or other mechanism. An example is bitumen [162]. Similarly, if a tank truck is not cleaned between deliveries of gasoline and a high flash point liquid such as kerosene or diesel oil, the mixture might generate a flammable atmosphere both in the tmck tank and the receiving tank. Contamination at the thousand ppm level may create hazards (5-1.4.3 and 5-2.5.4). Solids containing upward of about 0.2 wt% flammable solvent need to be evaluated for flammable vapor formation in containers (6-1.3.2). [Pg.85]

In view of the above adverse effects a safety factor should be applied where flammability is assessed using flash point. For pure liquids in containers the vapor should be considered potentially flammable if the liquid temperature is upward of at least 5°C below the reported flash point. For mixtures whose composition is less certain, such as petroleum mixtures, the safety factor should be about 15°C relative to the flash point [55]. Where combinations of adverse effects are identified the safety factors should be increased accordingly. A simple but very conservative approach is to assume that all liquids having a flash point <141°F may produce a flammable atmosphere under some ambient conditions, even where no mist or froth production is involved. A more practical approach is to assume that liquids handled in air at least 5-15°C below their closed cup flash points will not present ignition risks unless... [Pg.85]

Prevention of a flammable atmosphere may be accomplished using any of the alternatives presented in NEPA 69. in cases where fuel concentration cannot be limited, the most common technique (inerting) is to add a suitable inert gas such as nitrogen, so that the residual oxygen concentration is insufficient to support a flame. A safety factor is then applied. Eor most flammable gases and vapors this typically involves reducing the oxygen concentration to less than 5-8 vol% (see Chapter 2-7 of NEPA 69). [Pg.95]

Sample containers are discussed in 5-8.4.2. Eor tanks containing a flammable atmosphere this is most safely accomplished using a sampling well, also known as a gauge well. This is a metal pipe, sometimes perforated, through which a sample container or gauging device is lowered into the liquid. The metal pipe is permanently fixed and electrically bonded to the top and... [Pg.142]


See other pages where Flammable atmospheres is mentioned: [Pg.253]    [Pg.11]    [Pg.47]    [Pg.48]    [Pg.65]    [Pg.76]    [Pg.79]    [Pg.81]    [Pg.84]    [Pg.93]    [Pg.93]    [Pg.94]    [Pg.101]    [Pg.115]    [Pg.116]    [Pg.118]    [Pg.127]    [Pg.128]    [Pg.131]    [Pg.131]    [Pg.131]    [Pg.133]    [Pg.138]    [Pg.142]    [Pg.144]    [Pg.145]   
See also in sourсe #XX -- [ Pg.1442 ]




SEARCH



© 2024 chempedia.info