Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Circuit current

Power, P, defiaed as the rate at which work is performed, is expressed ia terms of energy divided by time and is most commonly given in units of horsepower, as for the power suppHed by mechanical devices such as diesel engines, or in the SI units of watts, especially when measuring electrical power. One horsepower is equivalent to the amount of power needed to lift 33,000 pounds (14,982 kg) one foot (30.5 cm) in one minute. One watt is equivalent to the power required to perform one joule of work per second. In a simple direct-current circuit where potential is represented by E ... [Pg.1]

High voliage alternating current circuit breakers 13118/1991 BS 5311/1996... [Pg.624]

More commonly known as earth leakage circuit breakers (ELCBs) or residual current circuit breakers (RCCBs). They operate on the principle of residual current. [Pg.679]

Both reactions indicate that the pH at the cathode is high and at the anode low as a result of the ion migration. In principle, the aeration cell is a concentration cell of H ions, so that the anode remains free of surface films and the cathode is covered with oxide. The J U curves in Fig. 2-6 for anode and cathode are kept apart. Further oxidation of the corrosion product formed according to Eq. (4-4) occurs at a distance from the metal surface and results in a rust pustule that covers the anodic area. Figure 4-2 shows the steps in the aeration cell. The current circuit is completed on the metal side by the electron current, and on the medium side by ion migration. [Pg.141]

Usually the annual variations in the specific resistance of the soil lead only to small changes in the current circuit resistance so that adjustment of the protection... [Pg.230]

Fig. 10-5 Protection measure by separation of electrical operational equipment that is connected to the cathodically protected object via the housing, with an FI protection circuit leakage current circuit breaker (see Ref. 14) Tj and isolating transformers (see Ref. 15). Fig. 10-5 Protection measure by separation of electrical operational equipment that is connected to the cathodically protected object via the housing, with an FI protection circuit leakage current circuit breaker (see Ref. 14) Tj and isolating transformers (see Ref. 15).
At the relatively low protection current density of 200 llA m and with the anode positioned on one side, it is to be expected that with this storage tank sufficient reduction in potential would be achieved on the other side of the tank from the anode. The off potential was measured using a measurement point at a depth of about 2 m as f/cu-cuso4 = -0.88 V at the tank. At the other side of the tank as well as above it, off potentials of-0.90 to -0.94 V were found. These potentials were measured with a protection current of 10 mA (anode 1 6 mA, anode 2 4 mA) with an additional resistance of 8 Q in the protection current circuit (see Fig. 11-2). With a direct connection between the tank and the group of magnesium anodes, the initial current was about 16 mA, which after 1 h of polarization decreased to about 14 mA. The reserve current, based on a long-term current of 10 mA, amounted to ca. 40% in the operation of the cathodic protection installation. [Pg.297]

As an example, a tank farm that is to be cathodically protected by this method is shown schematically in Fig. 11-4. As can be seen in the figure, injection of the protection current occurs with two current circuits of a total of about 9 A, via 16 vertically installed high-silicon iron anodes embedded in coke. These are distributed over several locations in the tank farm to achieve an approximately uniform potential drop. The details of the transformer-rectifier as well as the individual anode currents are included in Fig. 11-4. Anodes 4, 5 and 6 have been placed at areas where corrosion damage previously occurred. Since off potentials for 7/ -free potential measurements cannot be used, external measuring probes should be installed for accurate assessment (see Section 3.3.3.2 and Chapter 12). [Pg.300]

Figure 11 -7 shows the basic circuit diagram for a tank with two domes. The protection current flows via the two interconnected openers of the cover grounding switch to the cathode connection. If one of the covers is opened, the protection current circuit is broken and the tank grounded via the closing contact. The unconnected cable connection of the tank is without current and can be used for measuring potential. By this method, only one tank at a time is separated from the protection system while the other parts of the installations are still supplied with protection current. [Pg.306]

An electrical installation can only produce stray current if a conductor in the operating current circuit or part of the installation is grounded in more than one place. Such installations are ... [Pg.347]

After several years of operation, protection current densities between 50 and 450 /lA m were measured on several vessels. The filter tanks and pure water tanks were provided with protection current by separate current circuits. This was necessary because the nozzle bottom out of the filter tank made it impossible to supply the pure water tank with sufficient protection current. [Pg.461]

With long-term interference by several current circuits, the corresponding partial field strengths must be determined. The resultant longitudinal field strength can be assumed to be the square root of the sum of the squares of the partial field strengths. [Pg.520]

If, however, long-term interference results from current circuits that are connected in parallel (e.g., double conductors) or from current circuits that generally exhibit the same load flow direction (e.g., power station connection conductors), then the partial field strengths have to be added. [Pg.521]

In 1874 Heaviside established the ordinary symbolic method of analyzing alternating current circuits in common use today. It was a technique developed about fifteen years before AC came into commercial use. He emphasized the role of metallic circuits as guides, rather than conductors of AC currents. He discussed in detail causes of line distortion and suggested ways of alleviating it. [Pg.617]

BS 5311, High voltage alternating current circuit breaker BS 6867, Code of Practice for maintenance of electrical switchgear for voltages above 36 kV BS 158, Insulating oil for transformers and switchgear BS 5622, Insulation co-ordination... [Pg.212]

Power factor in an alternating current circuit is defined as the ratio of actual circuit power in watts (W) to the apparent power in voltage amperes (VA). The need for correction arises from fact that the majority of A.C. electrical loads take from the supply a lagging quadruple current (voltage amperes reactive, var) and thus operates at a lagging power factor due to the reactive (rather than capacitive) nature of their construction. [Pg.218]

In many cases it will suffice to include in the circuit a shunt of appropriately low resistance over which 7/ -drop potential measurements can be made for ready calculation of the magnitude of the current flow. This technique permits measurements to be made as required without opening the circuit even momentarily for the introduction of current-measuring devices. It is also possible to arrange instruments in a circuit so that no measuring resistance is introduced in the galvanic current circuit . [Pg.1019]

The parameter impedance in electrical alternating-current circuits is the equivalent of resistance in direct-current circuits. If a linear and time-invariant system, L, is considered, then it can be said that ... [Pg.50]

In addition to the electric controls that control the grid connection and the conversion between direct and alternating current circuits, a massive... [Pg.270]

In practice fliis process is run using an aulomaled continuous counter-current circuit in which the organic solvent flows in fhe opposite direction to the aqueous layer containing the lanthanides. An equilibrium is set up between the lanthanide ions in the aqueous phase and the organic layer, with there tending to be a relative enhancement of the concentration of the heavier lanthanides in the organic layer. Because the separation between adjacent... [Pg.5]


See other pages where Circuit current is mentioned: [Pg.1]    [Pg.889]    [Pg.227]    [Pg.227]    [Pg.230]    [Pg.231]    [Pg.231]    [Pg.237]    [Pg.243]    [Pg.271]    [Pg.296]    [Pg.297]    [Pg.348]    [Pg.349]    [Pg.459]    [Pg.254]    [Pg.195]    [Pg.297]    [Pg.960]    [Pg.2]    [Pg.331]    [Pg.240]    [Pg.23]    [Pg.466]    [Pg.40]    [Pg.50]    [Pg.614]   


SEARCH



A Direct-Current Circuits and Measurements

Alternating-current circuits

Circuit breakers current limiting

Circuit interrupters current chopping

Circuit parameters current waveform

Closed current loop circuit

Current Limits on Circuit Closure

Current Peak short-circuit

Current Short circuit withstand

Current closed circuit

Current measuring circuit

Current sensing circuit, designing

Current transformers circuit diagrams

DIRECT CURRENT CIRCUIT ANALYSIS

Direct current feeding circuit

Direct-current circuits

Electrical circuits alternating current

Electrical circuits direct current

Electrical circuits electric current

Equivalent circuit current flowing

External circuit current

Open circuit electrode corrosion current density

Open circuit voltage current density

Open circuit voltage exchange current density

Operational current-control circuit

Organic solar cells short-circuit current density

Polymer solar cells short circuit current

Prospective short circuit current

Residual current circuit breakers

Short circuit current Impedance

Short circuit current Instantaneous

Short circuit current mechanical force

Short circuit current thermal effects

Short circuit current, Isc

Short circuit currents

Short-circuit current-density

Short-circuit electric current

Short-circuit exciton current

Solar cells short circuit current

Solar cells, modeling short-circuit current

State short-circuit current density

Temperature short-circuit current

© 2024 chempedia.info