Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Circuit breakers current limiting

Vacuum and SF6 devices were developed at about the same time as competitors. There is little to choose between them since they are both simple mechanisms. Some engineers in the past considered the possibility that the vacnnm conld be lost while the circuit breaker was in its on state was a serions disadvantage. However, the technology has greatly improved and thousands of vacnnm circnit breakers are in service. Vacuum circuit breakers are limited to about 13.8 kV due to insulation difficulties across the open contacts. Current ratings at 13.8 kV are limited to about 3000 A, with corresponding fault making duties up to 100 kA peak. SF6 equipment tends to be preferred to vacuum equipment. [Pg.147]

Service entrance equipment should be installed in an indoor electrical room whenever possible. The equipment should include one to six main service entrance power circuit breakers or load break disconnect switches and feeder circuit breakers for loads within the plant. Circuit breakers and disconnect switches for 480/277 V systems that are rated at 1000 A or more must include groimd fault protection. Feeder circuit breakers will typically be molded case. Integrally fused circuit breakers are available with very high short circuit lAC ratings for both power and molded case circuit breakers. Fuses and current limiters for integrally fused circuit breakers must be stored within the electrical room. [Pg.1484]

Fuses should not be used to protect secondary voltage feeders. The time current characteristics of fuses above 100 A will not coordinate with the groimd fault pickup currents and time delays of the main overcurrent protection (circuit breaker or fused disconnect switch) ground fault protection. A main load break disconnect switch can be equipped with current-limiting fuses to reduce the available short-circuit current from the utility and should have a three-phase voltage relay for single-phase protection. [Pg.1484]

Circuit breakers are invariably used for the incomer, busbar section and switchboard interconnector switching devices, because the currents that they need to switch are too high for contactors to handle properly. Outgoing circuits can be static loads or motor loads, and these are usually limited... [Pg.162]

Moulded case circuit breakers are available in two basic modes of operation, current limiting and non-current limiting. It is difficult to design a moulded case circuit breaker to have a cut-off characteristic that is less than 0.01 second when a fully asymmetrical short-circuit current flows. However, there are such circuit breakers available, and care is needed when selecting these devices for a circuit that has a high prospective fault current. Some manufacturers are able to provide a cut-off in the order of 0.006 second. [Pg.163]

Where moulded case circuit breakers are chosen for a plant in favour of fuses the coordination of cascaded units becomes a little more difficult than with fuses. This difficulty arises from the fact that these circuit breakers have a definite or near definite minimum time limit to their time-current characteristic. This causes the lower part of the circuit breaker protection curve to be almost horizontal at a low value of time, typically in the range of 0.003 and 0.01 second. [Pg.165]

Note Some oil companies specify a lower disconnection time tdis than 5.0 seconds, e.g., 1.0 second. This significantly increases the disconnection current by a factor of about 3.0 times. This ensures a much lower permissible limit to Zioopf, and thereby making it more necessary to use an earth leakage circuit breaker. Indirectly this reduction in time should be accompanied by ensuring that the earth return impedance Z r (and Zer) is kept very low i.e. as far below... [Pg.242]

The maximnm rating of any one of the loads mnst be limited by the rapid tripping or fnsing time of the device that protects the circnit. Fnses fnnction better than moulded case circuit breakers in these sitnations becanse they are not limited by a definite minimum time constraint. To ensnre that the protective device fnnctions rapidly the rated cnrrent of this device must be limited to about 30% of the rated current of the inverter npstream. Hence the ratio of load kVA to inverter kVA of each load snb-circnit will be a maximnm of abont 25%. [Pg.450]

A circuit breaker is an electrical device designed to open when a current flow exceeds a limit. [Pg.289]

Circuit protective devices, such as fuses, circuit breakers, and GFCIs, automatically limit or shut off current flow in the event of a ground-fault, overload, or short circuit in a wiring system. [Pg.189]

Overcurrent devices limit the current that can flow through a circuit or electrical device. If the current exceeds a given limit, the device shuts off power. Fuses and circuit breakers are two common overcurrent devices. [Pg.146]

Circuit Breakers Circuit breakers are a form of switch that opens when current passing through them exceeds some designed limit. There are two kinds of breakers, each with a different principle of operation. One type opens when the temperature of the breaker reaches a predetermined level. The temperamre of the environment around the breaker can affect its response. The second type is magnetic. They open when reaching a predetermined current level. Environmental temperature has less effect on this type of breaker. There are many different breaker designs. Codes specify what types to use in certain applications. [Pg.146]

To increase the safety, commercial Li-ion cells are usually equipped with safety devices that catch an abnormal behavior and shutdown or limit the ciurrent. The current interrupt device (CID) and the positive temperature coefficient (PTC) are representative of such safety devices. The CID functions as a circuit breaker for the overcharge mainly, disconnecting the positive lead from the circuit by using a concave and movable aluminum disk, when the internal pressure of a cell suddenly increases [36,37]. The PTC is a fuse-like device based on materials whose resistance increases dramatically with an increase in temperature. When a large current flow in the circuit and a violent temperature rise due to the Joule heat occms as a result of external shorting, the resistance of the PTC element can rapidly increase by several orders and limit the current to a relatively low and safe... [Pg.479]

CRITICAL CIRCUITS. In situations where series-rated equipment is used, caution should be taken that critical power circuits are not interrupted. In the case of a series-rated circuit breaker system and a high-fault-current situation, two circuit breakers would trip simultaneously and limit the amount of fault current passing to the lower-rated breaker in the system. Thus two circuit breakers trip simultaneously this terminates the power in the circuit in which the fault occurred as well as the feeder circuit feeding the branch. [Pg.706]

For special applications, compliance may be achieved by other means. For example, the insertion of a 1 1 safety transformer in a mains voltage system would isolate the system on the secondary side from the earthed neutral system on the primary. Earthing one pole of the secondary side through an impedance so as to limit the potential earth fault current to no more than about 5 mA would create a system that would prevent eleetric shock injuries for a phase-to-earth fault. It is usual to employ a circuit that detects the flow of fault current and trips a circuit breaker controlling the supply. This type of system is often used in test areas. [Pg.74]

Similar systems are used where continuity of supply is important and it is undesirable for earth faults to lead to the interruption of the supply. In these systems, the limited fault current flowing causes an audible or visual alarm rather than tripping a circuit breaker. [Pg.74]

High currents (short circuit) Limitation of short circuit current by fuses or circuit breakers Short circuit safe installation of leads... [Pg.219]

Fuses and nonadjustable circuit breakers are capable of carrying their full rated current capacity for an indefinite period. The use of fuses in the laboratory is limited to the electrical service for certain highly specialized laboratory equipment or to the equipment itself. Circuit breakers are typically found in electrical panels and on certain items of laboratory equipment. Most devices can tolerate a small overload for a significantly prolonged period however, the larger the overload, the more rapidly the device will open. Circuit breakers are designed for specific applications, so their characteristics will vary. Also, the devices are subject to wear, catastrophic failure, and abuse. For example, in some cases when a circuit breaker is subjected to a massive current... [Pg.231]

The magnetic circuit breaker is designed to respond to an induced electrical field and will be actuated if the field strength exceeds the preset current limit. This type of device is generally unaffected by temperature, but is more sensitive to current fluctuations than the thermal device. Some devices are available which combine the characteristics of both types, but all of these devices require a large, transient surge of current to operate, such as occurs when two conductors or current sources come into contact. [Pg.231]


See other pages where Circuit breakers current limiting is mentioned: [Pg.518]    [Pg.518]    [Pg.137]    [Pg.706]    [Pg.464]    [Pg.318]    [Pg.318]    [Pg.464]    [Pg.247]    [Pg.2245]    [Pg.2494]    [Pg.128]    [Pg.151]    [Pg.163]    [Pg.163]    [Pg.634]    [Pg.413]    [Pg.342]    [Pg.108]    [Pg.106]    [Pg.129]    [Pg.391]    [Pg.391]    [Pg.706]    [Pg.41]    [Pg.77]    [Pg.314]    [Pg.420]    [Pg.469]    [Pg.65]    [Pg.448]    [Pg.449]   
See also in sourсe #XX -- [ Pg.77 ]




SEARCH



Breakers

Circuit breakers

Current breakers

Current limit

Currents circuits)

Limitation current

Limited currents

Limiting currents

© 2024 chempedia.info