Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Total heat control

If the substitute fuel is of the same general type, eg, propane for methane, the problem reduces to control of the primary equivalence ratio. For nonaspiring burners, ie, those in which the air and fuel suppHes are essentially independent, it is further reduced to control of the fuel dow, since the air dow usually constitutes most of the mass dow and this is fixed. For a given fuel supply pressure and fixed dow resistance of the feed system, the volume dow rate of the fuel is inversely proportional to. ypJ. The same total heat input rate or enthalpy dow to the dame simply requires satisfactory reproduction of the product of the lower heating value of the fuel and its dow rate, so that WI = l- / remains the same. WI is the Wobbe Index of the fuel gas, and... [Pg.524]

The total intercooler duty is the difference between the total heat in of the rich gas and lean oil and the total heat out of the off gas and rich oil all at the terminal calculated or design conditions. The total duty is often divided between several coolers placed to re-cool the oil as it passes down the column. If intercoolers are not used, then the absorption cannot meet the design terminal outlet conditions and the quantity of material absorbed will be reduced. If the intercooling is too great so as to sub-cool, then greater absorption may be achieved, but this can be controlled by the intercooler operation. [Pg.116]

R.L. Bohon, AnalChem 35 (12), 1845-52 (1963) CA 60,1527 (1964) Approx heats of expin, Qv were detd on mg amounts of propints and expls by differential thermal analysis (DTA). Small-screw-cap metal cupsi sealed with a Cu washer served as constant vol sample containers the initial cup pressure could be controlled from 0 to approximately lOOOpsia. The calibration constant was calcd for each run from the total heat capacity of the cup and the relaxation curve, thereby compensating for equipment variations. [Pg.945]

Inherent hazard (e.g., toxicity, stability, reactivity) Cost Renewability Recyclability Size (volume) Scalability Controllability Energy (i.e., total, heating, cooling, recovery, treatment, etc.) Ease of cleaning and maintenance Safety/process safety ... [Pg.229]

The second device comprised a set of three circumferentially located pintle-type injectors Keihin, 10450-PG7-0031) to inject fuel radially into the main duct of the first flow arrangement as near-rectangular pulses. The frequency and duration of fuel injection were software controlled, and the fuel flow from each injector was delivered close to the outer edge of the annular ring flame holder by a cross-jet of air (1.2 x 5 mm), directed along the duct axis with exit velocity up to 100 m/s. The amplitude of the oscillated input was limited by the volume injection rate of the injectors. Propane, rather than methane, provided up to 3.5 kW of the total heat release of around 100 kW. With fluid dynamic damping, the RMS of the oscillated fuel flow corresponded to a heat release of around 1.8 kW. [Pg.300]

To a solution of 148 g. (0.845 mole) of methyl 7-methyl-7-nitrovalerate (p. 86) in 500 ml. of commercial absolute ethanol (total volume about 632 ml.) in a 2.5-1. rocking high-pressure bomb is added 12.5-25.0 g. (Note 1) of W-5 2 Raney nickel catalyst (Note 2), previously rinsed with absolute ethanol. The bomb head and fittings are placed in position, including a thermocouple attached to a semi-automatic heating control (Micromax). Hydrogen is introduced into the bomb until the pressure reaches 1000 lb. per sq. in. (Note 3). [Pg.59]

In order to write the heat balance, it is assumed that all reactions are exothermic, that the temperature control is achieved by means of a heat exchange jacket surrounding the reactor, and that heat losses to the environment can be neglected. Energy balances can be written both for the fluid in the reactor and for the fluid in the jacket. In the first case, by including in (2.25) the proper expression for the total heat of reaction, this equation reads... [Pg.30]

In a liquid-liquid exchanger, the total heat transferred (Q) from the hot process fluid to the cooling water is dependent on the overall heat transfer coefficient (U), the heat transfer area (A), and the log mean temperature difference (ATm). Therefore, any of these can be manipulated to control Q. [Pg.278]

Diagram 3 shows the reactor system under non-reactive conditions using ethanol as a test substance with a feed rate of 20 g/min, pressure 80 bar, temperature 50 °C. In the first 6 minutes the reactor was filled by the feed pump to the desired degree of filling. After that the heating control was switched on, reaching the desired temperature after another 12 min, then the feed flow and pressure control were activated. Under these conditions the reactor reached a steady state after a total time of 20 min. [Pg.40]

The control performance of the heat-integrated reactor-column system shown in Fig.. 5.9 deteriorates as the auxiliary rehoiler provides less and less heat to the column. The reason is that uncontrolled variations in the steam pressure of the waste heat boiler affect the heat supplied to the column. When these variations are of the same order of magnitude as the total heat supplied by the auxiliary reboiler, the latter cannot compensate properly for the variations. Part of the prob-... [Pg.154]

This subject is discussed in detail in Chap. 5, along with the use of auxiliary reboilers and condensers as well as the idea of using total heat input controllers. [Pg.233]

The total pyrolysis time (or total heating time THT) is another parameter used to control the pyrolytic process. This parameter should be chosen long enough for the total amount of sample to be pyrolysed during THT. Because longer THTs than those exactly needed for the pyrolysis of the sample are commonly used, this parameter is not critical as long as the whole sample is pyrolysed within THT. [Pg.73]

Professional-type MWO with temp, control Group 1 Group 2 1,000 ml 98°C (set) 15-20 min 20-25 min Total heating time (from room temp.)... [Pg.111]


See other pages where Total heat control is mentioned: [Pg.155]    [Pg.155]    [Pg.22]    [Pg.400]    [Pg.254]    [Pg.496]    [Pg.879]    [Pg.367]    [Pg.196]    [Pg.435]    [Pg.217]    [Pg.498]    [Pg.300]    [Pg.423]    [Pg.101]    [Pg.344]    [Pg.238]    [Pg.327]    [Pg.154]    [Pg.201]    [Pg.3037]    [Pg.2499]    [Pg.331]    [Pg.110]    [Pg.408]    [Pg.72]    [Pg.15]    [Pg.70]    [Pg.259]    [Pg.35]    [Pg.606]    [Pg.175]   
See also in sourсe #XX -- [ Pg.155 ]




SEARCH



Heat controlled

Heating control

Total heat

© 2024 chempedia.info