Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Pressure transmitters

For very low flow rates the orifice plate is often incorporated into a manifold, an integral part of the differential-pressure transmitter. This provides a convenient compact installation. [Pg.60]

Fig. 15. Differential pressure transmitter with remote seals. Fig. 15. Differential pressure transmitter with remote seals.
Differential Pressure. Differential pressure transmitters designed for Hquid level measurements use soHd-state electronics and have a two-wire 4—20 m A d-c output. [Pg.213]

The Series 1151 differential pressure transmitter manufactured by Rosemount (MinneapoHs, Minnesota) uses a capacitance sensor in which capacitor plates are located on both sides of a stretched metal-sensing diaphragm. This diaphragm is displaced by an amount proportional to the differential process pressure, and the differential capacitance between the sensing diaphragm and the capacitor plates is converted electronically to a 4—20 m A d-c output. [Pg.213]

The proper installation of both orifice plates and Venturi-type flow tubes requires a length of straight pipe upstream and downstream of the sensor, ie, a meter mn. The pressure taps and connections for the differential pressure transmitter should be located so as to prevent the accumulation of vapor when measuring a Hquid and the accumulation of Hquid when measuring a vapor. For example, for a Hquid flow measurement in a horizontal pipe, the taps are located in the horizontal plane so that the differential pressure transmitter is either close-coupled or connected through downward sloping connections to allow any trapped vapor to escape. For a vapor measurement in a horizontal pipe, the taps should be located on the top of the pipe and have upward sloping connections to allow trapped Hquid to drain. [Pg.65]

Cahbration of some measurement devices involves comparing the measured value with the value from the working standard. Pressure and differential pressure transmitters are calibrated in this manner. Calibration of analyzers normally involves using the measurement device to analyze a specially prepared sample whose composition is known. These and similar approaches can he applied to most measurement devices. [Pg.759]

Flow is an important measurement whose calibration presents some challenges. When a flow measurement device is used in applications such as custody transfer, provision is made to pass a known flow through the meter. However, such a provision is costly and is not available for most in-process flowmeters. Without such a provision, a true cahbration of the flow element itself is not possible. For orifice meters, calibration of the flowmeter normally involves cahbration of the differential pressure transmitter, and the orifice plate is usually only inspected for deformation, abrasion, and so on. Similarly, cahbration of a magnetic flowmeter normally involves cahbration of the voltage measurement circuitry, which is analogous to calibration of the differential pressure transmitter for an orifice meter. [Pg.759]

Compensation of the measured value for conditions within the instrument, such as compensating the output of a pressure transmitter for the temperature within the transmitter. Smart transmitters are much less affected by temperature and pressure variations than conventional transmitters. [Pg.768]

Transmission of more than one value from a transmitter. Information beyond the measured variable is available from the smart transmitter. For example, a smart pressure transmitter can also report the temperature within its housing. Knowing that this temperature is above normal values permits corrective action to be taken before the device fails. Such information is especially important during the initial commissioning of a plant. [Pg.768]

Vaeuum pressure Absolute pressure transmitters reeommended... [Pg.694]

Pressure Zero shift, air leaks in signal lines. Variable energy consumption under temperature control. Unpredictable transmitter output. Permanent zero shift. Excessive vibration from positive displacement equipment. Change in atmospheric pressure. Wet instrument air. Overpressure. Use independent transmitter mtg., flexible process connection lines. Use liquid filled gauge. Use absolute pressure transmitter. Mount local dryer. Use regulator with sump, slope air line away from transmitter. Install pressure snubber for spikes. [Pg.325]

The pressure transmitter (transducer block) senses the process pressure. It converts this signal to a signal proportional to the process pressure and sends it to the pressure controller. [Pg.359]

The pressure transmitter senses the process pressure and converts it to a signal that is proportional to it. [Pg.361]

The simulated FBAC consists of an acrylic main reactor (0.5m-H x 0.5m-W x l.Om-L), an air distributor system, particles feeding system including a feed hopper, a discharging sampler, a bag filter for capture of the elutriated fine particles and, pressure and flow rate measurement systems (Fig. 1). The air distributor system has ten air headers. An individual air header is connected with 5 air nozzles and can regulate the airflow rate. The opening ratio of the distributor is 2.1% and each nozzle has four holes for uniform air supply. To measure the pressure fluctuation at an individual air header, high frequency pressure transmitters were mounted at the approach and the exit headers of the FBAC. [Pg.510]

When the reactor temperature (Tl) becomes greater than Tmax (=240 F), PERIOD = 2, and the program turns the cooling water on with flow rate Fw. This flow is controlled with a proportional controller using control constant Kc, whose set point (Pset) is varied according to the time ramp function with setting kR and whose output to the valve is Pc. This ramp is horizontal until time period Tihold has passed. Then the setpoint is decreased linearly. The temperature is sensed using a pressure transmitter with output Ptt. [Pg.309]

Pressure loss coefficient, 13 261 Pressure measurement, 11 783 20 644-665. See also Vacuum measurement electronic sensors, 20 651-657 mechanical gauges, 20 646-651 smart pressure transmitters, 20 663-665 terms related to, 20 644-646 Pressure measurement devices. See also Pressure meters Pressure sensors location of, 20 682 types of, 20 681-682 Pressure meters, 20 651 Pressure microfiltration/ultrafiltration,... [Pg.758]

The dynamic response of most transmitters is usually much faster than the process and the control valves. Consequently we can normally consider the transmitter as a simple gain (a step change in the input to the transmitter gives an instantaneous step change in the output). The gain of the pressure transmitter considered above would be... [Pg.211]

Reactor temperature transmitter range SO-250 F Circulating jacket water temperature transmitter range 50-1 SO F Makeup cooling water flow transmitter range 0-250 gpm (orifice plate + diflerential pressure transmitter) >... [Pg.244]

If orifice plates are used as flow sensors, the signals from the differential-pressure transmitters are reaUy the squares of the flow rates. Some instrument engineers prefer to put in square-root extractors and convert everything to linear flow signals. [Pg.255]

The span of the pressure transmitter is SO psi. The control valve has linear installed... [Pg.411]

Assume the perfect gas law can be used 8.314 kPa m /kg mol K). Assume the pressure transmitter range is 1800-2000 kPa and that the valve has linear installed characteristics with a maximum flow rate of 2000 kg/h. [Pg.498]

Pneumatic differential pressure transmitter. Typical installation with orifice plate to sense flow rate. (Courtesy of Fischer and Porter Company.)... [Pg.711]

Electronic differential-pressure transmitter. (Courtesy of Honeywell.)... [Pg.712]

Acoustic chemometrics has its greatest benefits in cases where haditional sensors and measurement techniques, such as flow, temperature and pressure transmitters cannot be used. In many processes it is preferable to use noninvasive sensors because invasive sensors may cause disturbances, for example fouling and clogging inside the process equipment such as pipelines, reactors cyclones, etc. In this chapter we concentrate mainly on new industrial applications for acoustic chemomehics, and only discuss the necessary elements of the more technical aspects of the enabling technology below - details can be found in the extensive background literature [3-5],... [Pg.282]

For industrial fertilizer production reliable ammonia concentration data are essential. An experimental setup for acoustic chemometric prediction of ammonia concentration has been tested in a full-scale industrial plant. Figure 9.22 shows a bypass loop with the orifice plate. The acoustic sensor was again mounted onto the orifice plate [5]. To ensure constant differential pressure and temperature of the ammonia flow, two pressure transmitters and one temperature sensor were used. Reference samples were taken at the sample valve shown in Figure 9.22. [Pg.297]

Other supervisory signals may come from fire protection system components such as supervised control valves, system air and supervisory air pressure transmitters, water tank level and temperature transmitters, valve house and fire water pump building temperature transmitters, and fire water pumps. [Pg.184]

Sensor—Field measurement system (instrumentation) capable of detecting the condition of a process (for example, pressure transmitters level transmitters, and toxic gas detectors). [Pg.440]


See other pages where Pressure transmitters is mentioned: [Pg.896]    [Pg.59]    [Pg.212]    [Pg.213]    [Pg.23]    [Pg.28]    [Pg.28]    [Pg.263]    [Pg.695]    [Pg.68]    [Pg.155]    [Pg.240]    [Pg.50]    [Pg.852]    [Pg.255]    [Pg.211]    [Pg.238]    [Pg.241]    [Pg.246]    [Pg.288]    [Pg.48]   
See also in sourсe #XX -- [ Pg.129 , Pg.130 ]

See also in sourсe #XX -- [ Pg.329 , Pg.333 , Pg.334 ]




SEARCH



Transmittance

Transmittancy

Transmittivity

© 2024 chempedia.info