Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Cascade temperature controller

Fig. 10. Block diagrams a) Single loop concentration controi and b) Cascade temperature control... Fig. 10. Block diagrams a) Single loop concentration controi and b) Cascade temperature control...
A reliable control of the reaction course can be obtained by isothermal operation. Nevertheless, to maintain a constant reaction medium temperature, the heat exchange system must be able to remove even the maximum heat release rate of the reaction. Strictly isothermal behavior is difficult to achieve due to the thermal inertia of the reactor. However, in actual practice, the reaction temperature (Tr) can be controlled within 2°C, by using a cascade temperature controller (see Section 9.2.3). Isothermal conditions may also be achieved by using reflux cooling (see Section 9.2.3.3), provided the boiling point of the reaction mass does not change with composition. [Pg.159]

Therefore, the chapter is mainly focused on the design of model-based control approaches. Namely, a controller-observer control strategy is considered, where an observer is designed to estimate the heat released by the reaction, together with a cascade temperature control scheme. The performance of this control strategy are further improved by introducing an adaptive estimation of the heat transfer coefficient. Finally, the application of the proposed methods to the phenol-formaldehyde reaction studied in the previous chapters is presented. [Pg.6]

In the following, the model-based controller-observer adaptive scheme in [15] is presented. Namely, an observer is designed to estimate the effect of the heat released by the reaction on the reactor temperature dynamics then, this estimate is used by a cascade temperature control scheme, based on the closure of two temperature feedback loops, where the output of the reactor temperature controller becomes the setpoint of the cooling jacket temperature controller. Model-free variants of this control scheme are developed as well. The convergence of the overall controller-observer scheme, in terms of observer estimation errors and controller tracking errors, is proven via a Lyapunov-like argument. Noticeably, the scheme is developed for the general class of irreversible nonchain reactions presented in Sect. 2.5. [Pg.97]

Another approach for removing heat is a circulation loop through an external heat exchanger, as shown in Figure 3.24. The circulation rate is maximized for good heat transfer on the process side, while the heat transfer medium is throttled by the reactor temperature controller. If the reactor is small and well mixed, the cascade temperature control arrangement as shown may not be necessary, and the reactor temperature controller may be connected directly to the valve. [Pg.55]

Table 23.4 shows the three possible loop configurations. Number 3 corresponds to cascade temperature control and, as we have seen in Section 20.1 and Example 20.1, it provides fast compensation. Thus configuration 3 is selected for the reactor. [Pg.604]

Fig. 6.9. Direct-charged aluminum melting furnace with cascaded temperature control and regenerative burners. On the next 20-sec cycle, two air valves, two exhaust valves, and two fuel shutoff valves will reverse positions. Ma = milliamps. Se = suction exhaust. SP = setpoint. T/s = temperature sensor. Courtesy of North American Mfg. Co. [Pg.263]

Tendency Model-based Improvement of the Slave Loop in Cascade Temperature Control of Batch Process Units... [Pg.467]

The batch evolution presented in Figure 1 has a similar shape that the ones drawn from optimization [4]. The results show that temperature and free monomer concentration can be reliably tracked with a nearly linear multivariable calorimetric controller that manipulates the monomer addition and heat exchange rates, and with a control scheme that can be seen as the adequate coordination of two controllers that are well-known and accepted in industrial practice a cascade temperature controller that manipulates the heat exchange rate Qj for a given monomer feed rate w, and a ratio-type free-monomer controller that sets w proportionally to the heat generation rate Q. [Pg.631]

The figure below shows cascade temperature control of a polymerization reactor, which uses feed heat exchange to adjust the reactor temperature. Using the instrumentation diagram, explain how this cascade control system (both master and slave components) handles the following disturbances. (describe what happens to the reactor temperature.) Assume normal temperatures of coolant (70°F), polymerization feed (200°F), exchanger effluent (100°F), and reactor outlet (800°F). [Pg.314]

Schemes to control the outlet temperature of a process furnace by adjusting the fuel gas flow are shown in Figure 13. In the scheme without cascade control (Fig. 13a), if a disturbance has occurred in the fuel gas supply pressure, a disturbance occurs in the fuel gas flow rate, hence, in the energy transferred to the process fluid and eventually to the process fluid furnace outlet temperature. At that point, the outlet temperature controller senses the deviation from setpoint and adjusts the valve in the fuel gas line. In the meantime, other disturbances may have occurred in the fuel gas pressure, etc. In the cascade control strategy (Fig. 13b), when the fuel gas pressure is disturbed, it causes the fuel gas flow rate to be disturbed. The secondary controller, ie, the fuel gas flow controller, immediately senses the deviation and adjusts the valve in the fuel gas line to maintain the set fuel gas rate. If the fuel gas flow controller is well tuned, the furnace outlet temperature experiences only a small disturbance owing to a fuel gas supply pressure disturbance. Schemes to control the outlet temperature of a process furnace by adjusting the fuel gas flow are shown in Figure 13. In the scheme without cascade control (Fig. 13a), if a disturbance has occurred in the fuel gas supply pressure, a disturbance occurs in the fuel gas flow rate, hence, in the energy transferred to the process fluid and eventually to the process fluid furnace outlet temperature. At that point, the outlet temperature controller senses the deviation from setpoint and adjusts the valve in the fuel gas line. In the meantime, other disturbances may have occurred in the fuel gas pressure, etc. In the cascade control strategy (Fig. 13b), when the fuel gas pressure is disturbed, it causes the fuel gas flow rate to be disturbed. The secondary controller, ie, the fuel gas flow controller, immediately senses the deviation and adjusts the valve in the fuel gas line to maintain the set fuel gas rate. If the fuel gas flow controller is well tuned, the furnace outlet temperature experiences only a small disturbance owing to a fuel gas supply pressure disturbance.
Fig. 13. Cascade control schemes, where TC = temperature controller FC = fuel gas flow controller and LC = liquid level controller, (a) Simple circuit having no cascade control (b) the same circuit employing cascade control and (c) and (d) Hquid level control circuits with and without cascade control,... Fig. 13. Cascade control schemes, where TC = temperature controller FC = fuel gas flow controller and LC = liquid level controller, (a) Simple circuit having no cascade control (b) the same circuit employing cascade control and (c) and (d) Hquid level control circuits with and without cascade control,...
States or Australia. In some cases, pot stills, arranged in cascade, are still used. The more sophisticated plants employ one or more carbon steel or cast-iron vessels heated electrically and equipped with temperature controls for both the bulk Hquid and the vessel walls. Contact time is usually 6—10 h. However, modem pitches are vacuum-distilled, producing no secondary quinoline insolubles, to improve the rheological properties. [Pg.348]

Feedforward control can also be applied by multiplying the liquid flow measurement—after dynamic compensation—by the output of the temperature controller, the result used to set steam flow in cascade. Feedforward is capable of a reduction in integrated error as much as a hundredfold but requires the use of a steam-flow loop and dynamic compensator to approach this. [Pg.746]

FIG. 8-53 The reactor temperature controller sets coolant outlet temperature in cascade, with primary integral feedback taken from the secondary temperature measurement. [Pg.749]

Column Bottom Temperature. The bottom temperature is often controlled on the reboiler outlet line with a control valve in the heating medium line. The control point can also be on a bottom section tray. Care must be exercised in location of the temperature control point. It is recommended, especially for large columns, that a cascade arrangement be used. The recommended scheme has a complete flow recorder/controller (FRC) in the heating medium line including orifice and control valve. The set point of this FRC is manipulated by the temperature recorder/controller (TRC). This eliminates the TRC from manipulating the control valve directly (recall that temperature is the most difficult parameter to control). This makes for smoother control for normal operations. Also, it is handy for startup to be able to uncouple the TRC and run the reboiler on FRC for a period. [Pg.68]

Figure 3. Example of Graphical Output from Analysis Mode. Reaction progress for water-jacketted reactor, with Cascade coupled temperature controllers, both in self-tuning mode. Figure 3. Example of Graphical Output from Analysis Mode. Reaction progress for water-jacketted reactor, with Cascade coupled temperature controllers, both in self-tuning mode.
A cascade control system can be designed to handle fuel gas disturbance more effectively (Fig. 10.1). In this case, a secondary loop (also called the slave loop) is used to adjust the regulating valve and thus manipulate the fuel gas flow rate. The temperature controller (the master or primary controller) sends its signal, in terms of the desired flow rate, to the secondary flow control loop—in essence, the signal is the set point of the secondary flow controller (FC). [Pg.189]

Figure 10.1. Cascade control of the temperature of a furnace, which is taken to be the same as that of the outlet process stream. The temperature controller does not actuate the regulating valve directly it sends its signal to a secondary flow rate control loop which in turn ensures that the desired fuel gas... Figure 10.1. Cascade control of the temperature of a furnace, which is taken to be the same as that of the outlet process stream. The temperature controller does not actuate the regulating valve directly it sends its signal to a secondary flow rate control loop which in turn ensures that the desired fuel gas...
Example 10.2 Consider the temperature control of a gas furnace used in heating a process stream. The probable disturbances are in the process stream temperature and flow rate, and the fuel gas flow rate. Draw the schematic diagram of the furnace temperature control system, and show how feedforward, feedback and cascade controls can all be implemented together to handle load changes. [Pg.197]

A reactor is cooled by a circulating jacket water system. A double cascade reacidr temperature control to jacket temperature control to makeup cooling water flow control is employed. [Pg.244]

Figure S.2b shows another common system where cascade control is used. The reactor temperature controller is the primary controller the jacket temperature controller is the secondary controller. The reactor temperature control is isolated by the cascade system from disturbances in cooling-water inlet temperature and supply pressure. Figure S.2b shows another common system where cascade control is used. The reactor temperature controller is the primary controller the jacket temperature controller is the secondary controller. The reactor temperature control is isolated by the cascade system from disturbances in cooling-water inlet temperature and supply pressure.
Conventional venus cascade control, (a) DisUllRlion oIuinn-rebotler temperature oonlro) (t>) C5TR temperature control. [Pg.256]

Reactor temperature is controlled through a cascade system. Circulating water temperature is controlled by makeup cooling water. The setpoint of this temperature controller is set by the reactor temperature controller. The circulation rate of process liquid through the cooler is flow-controlled. [Pg.296]

The reactor temperature controller (loop 2) is the primary controller, whereas the jacket temperature controller (loop 3) is the secondary controller. The advantage of the cascade control is that the reactor temperature control quickly reacts by the cascade system to disturbances in cooling fluid inlet conditions. The d3mamics of the transfer function G32 is faster than that of G 22-In the CSTR cascade control there are two control loops using two different measurements temperatures T and Tj, but only one manipulated variable Fj. The transfer function of the primary controller is the following ... [Pg.21]

Figure 3.9. Steam heaters, (a) Flow of steam is controlled off the PF outlet temperature, and condensate is removed with a steam trap or under liquid level control. Subject to difficulties when condensation pressure is below atmospheric, (b) Temperature control on the condensate removal has the effect of varying the amount of flooding of the heat transfer surface and hence the rate of condensation. Because the flow of condensate through the valve is relatively slow, this mode of control is sluggish compared with (a). However, the liquid valve is cheaper than the vapor one. (c) Bypass of process fluid around the exchanger. The condensing pressure is maintained above atmospheric so that the trap can discharge freely, (d) Cascade control. The steam pressure responds quickly to upsets in steam supply conditions. The more sluggish PF temperature is used to adjust the pressure so as to maintain the proper rate of heat transfer. Figure 3.9. Steam heaters, (a) Flow of steam is controlled off the PF outlet temperature, and condensate is removed with a steam trap or under liquid level control. Subject to difficulties when condensation pressure is below atmospheric, (b) Temperature control on the condensate removal has the effect of varying the amount of flooding of the heat transfer surface and hence the rate of condensation. Because the flow of condensate through the valve is relatively slow, this mode of control is sluggish compared with (a). However, the liquid valve is cheaper than the vapor one. (c) Bypass of process fluid around the exchanger. The condensing pressure is maintained above atmospheric so that the trap can discharge freely, (d) Cascade control. The steam pressure responds quickly to upsets in steam supply conditions. The more sluggish PF temperature is used to adjust the pressure so as to maintain the proper rate of heat transfer.
In all these cases the reflux rate is simply set at a safe value, enough to nullify the effects of any possible perturbations in operation. There rarely is any harm in obtaining greater purity than actually is necessary. The cases that are not on direct control of reflux flow rate are (g) is on cascade temperature (or composition) and flow control, (h) is on differential temperature control, and (i) is on temperature control of the HTM flow rate. [Pg.50]


See other pages where Cascade temperature controller is mentioned: [Pg.3]    [Pg.135]    [Pg.171]    [Pg.264]    [Pg.607]    [Pg.627]    [Pg.3]    [Pg.135]    [Pg.171]    [Pg.264]    [Pg.607]    [Pg.627]    [Pg.733]    [Pg.746]    [Pg.747]    [Pg.749]    [Pg.85]    [Pg.696]    [Pg.870]    [Pg.115]    [Pg.37]    [Pg.355]    [Pg.42]    [Pg.51]    [Pg.54]    [Pg.56]   
See also in sourсe #XX -- [ Pg.135 , Pg.159 ]




SEARCH



Cascade control

Cascade controller

Cascade temperature

Control cascading

Temperature control

Temperature control cascade loop

Temperature control controllers

Temperature controller

Temperature-controlled

© 2024 chempedia.info