Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Differential temperature control

Differential temperature as well as differential pressure can be used as a primary control variable. In one instance, it was hard to meet purity on a product in a column having close boiling components. The differential temperature across several bottom section trays was found to be the key to maintaining purity control. So a column side draw flow higher in the column was put on control by the critical temperature differential. This controlled the liquid reflux running down to the critical zone by varying the liquid drawn off at the side draw. This novel scheme solved the control problem. [Pg.69]

The first thing to note is that the furnace surrounds the sample-holder containing the differential thermocouples. A separate control thermocouple controls the furnace temperature and should be placed as close as possible to the position of the sample holder. Some commercial manufacturers use the Reference leg of the differential thermocouple to control the temperature. However, if you were to build a DTA using the components as shown in 7.1.14,... [Pg.364]

Experimental Methods Measurements of specific heat and enthalpies of transition are now usually carried out on quite small samples in a Differential scanning calorimeter (DSC). DSC is applied to two different moles of analysis, of these the one is more closely related to traditional calorimetry and is described here. In DSC an average-temperature circuit measures and controls the temperature of sample and reference holders to conform to a Organisation and Qualities... [Pg.86]

In (b) typical trends of temperature vs. time are presented T0 is the controlled furnace temperature trend, 7 R is the T trend of the inert reference specimen, Ts is the trend observed for a sample undergoing some transformation. The corresponding differential curve (AT vs. time (or vs. temperature)) is shown in (c). [Pg.60]

QAI will monitor the results of pressure differentials, temperature, and humidity obtained from the control room daily before starting the manufacturing process in the area for comparison of results with the standard provided for each area. They should be within limits. Whenever any operation such as manufacturing or filling starts, QAI will fill an inspection start-up checklist and give release for manufacturing or packaging. See attachment no. 1700.30(A), 1700.30(B), and 1700.30(C). [Pg.703]

In all these cases the reflux rate is simply set at a safe value, enough to nullify the effects of any possible perturbations in operation. There rarely is any harm in obtaining greater purity than actually is necessary. The cases that are not on direct control of reflux flow rate are (g) is on cascade temperature (or composition) and flow control, (h) is on differential temperature control, and (i) is on temperature control of the HTM flow rate. [Pg.50]

If the flowrate of the makeup cooling water were made very large, the jacket temperature could be reduced to almost 294 K, which would give a differential temperature of 333 — 294 = 39 K. But we are using only 2.9 K of the potential driving force. Thus there is plenty of cooling muscle available to achieve very tight temperature control. [Pg.30]

In this large reactor the temperature differential driving force under design conditions is 333 - 304 = 29 K. The largest it can ever be is 333 - 294 = 39 K. Since we are using a large fraction of this maximum differential temperature, there is less muscle available. We demonstrate quantitatively in Chapter 3 the deterioration in temperature control as a larger fraction of the maximum differential is used. [Pg.30]

The ethane is much lighter than the methyl chloride, so it accumulates in the condenser and acts essentially like an inert substance that blankets the condenser. The effect of the inert substance can be considered to reduce either (1) the bubblepoint temperature, thus reducing the differential temperature driving force and reducing heat transfer, or (2) the effective heat transfer area. Either effect is a reduction in heat transfer. So if the ethane is not vented off during the batch, the pressure cannot be controlled even with the chilled water valve wide open. [Pg.232]

Differential temperature controls flow through each row of collectors. [Pg.312]

Some of the compressor energy that was introduced by CP-1 is recovered in the expander turbine generator (ETG-1) as the working fluid pressure is reduced from that of the condenser (CO-2) to that of the evaporator (EV-1). The compressor station operation is optimized under differential temperature control (ATC-7) by the control system described in detail in Section 2.5.3 (see Figures 2.20 and 2.22). The electricity generated by ETG-1 is used to lower the total power consumption of the plant. [Pg.531]

As a metathesis reaction proceeds, the concentration of the products increase until nucleation and, eventually, crystallization can occur. The rate of the reaction, and hence nucleation and growth, can be controlled through temperature and concentration. Working with differential solubilities is the simplest method for the synthesis of materials. For example, the semiconductor CdS can be synthesized by the reaction ... [Pg.151]

This nonmonotonic behavior can lead to feedback control instability. On one side of the hump the controller should be direct acting. On the other it should be reverse acting. So we must be careful when applying differential temperature control structures. [Pg.213]

Obviously, the heat transfer is the conjugating process here with respect to establishing the conjugate convection process. The controlling parame ter is obviously the differential temperature AT, while point AT r behaves as the bifurcation point of the potential stationary states of the system. [Pg.167]

The bypassed vapor heats up the liquid there, thereby causing the pressure to rise. WTien the bypass is closed, the pressure falls. Sufficient heat transfer surface is provided to subcool the condensate, (f) Vapor bypass between the condenser and the accumulator, with the condenser near ground level for the ease of maintenance When the pressure in the tower falls, the bypass valve opens, and the subcooled liquid in the drum heats up and is forced by its vapor pressure back into the condenser. Because of the smaller surface now exposed to the vapor, the rate of condensation is decreased and consequently the tower pressure increases to the preset value. With normal subcooling, obtained with some excess surface, a difference of 10-15 ft in levels of drum and condenser is sufficient for good control, (g) Cascade control The same system as case (a), but with addition of a TC (or composition controller) that resets the reflux flow rate, (h) Reflux rate on a differential temperature controller. Ensures constant internal reflux rate even when the performance of the condenser fluctuates, (i) Reflux is provided by a separate partial condenser on TC. It may be mounted on top of the column as shown or inside the column or installed with its own accumulator and reflux pump in the usual way. The overhead product is handled by an alter condenser which can be operated with refrigerant if required to handle low boiling components. [Pg.51]


See other pages where Differential temperature control is mentioned: [Pg.747]    [Pg.69]    [Pg.1061]    [Pg.173]    [Pg.403]    [Pg.81]    [Pg.173]    [Pg.239]    [Pg.279]    [Pg.33]    [Pg.33]    [Pg.51]    [Pg.56]    [Pg.517]    [Pg.175]    [Pg.94]    [Pg.640]    [Pg.18]    [Pg.953]    [Pg.308]    [Pg.66]    [Pg.180]    [Pg.127]    [Pg.571]    [Pg.1686]    [Pg.930]    [Pg.566]    [Pg.2879]    [Pg.2881]    [Pg.51]    [Pg.56]    [Pg.287]   
See also in sourсe #XX -- [ Pg.547 , Pg.562 , Pg.563 , Pg.676 , Pg.677 , Pg.678 ]




SEARCH



Control double differential temperature

Differential control

Temperature control

Temperature control controllers

Temperature controller

Temperature differential

Temperature-controlled

© 2024 chempedia.info