Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Preset

Within the preset time limit, the operator can at any time press the reject button, which will close the on/off shutter, open the exit panel and move the block on to an output conveyor At the same time the entrance panel will open to admit the next block awaiting inspection. [Pg.592]

Another difference is related to the mathematical formulation. Equation (1) is deterministic and does not include explicit stochasticity. In contrast, the equations of motion for a Brownian particle include noise. Nevertheless, similar algorithms are adopted to solve the two differential equations as outlined below. The most common approach is to numerically integrate the above differential equations using small time steps and preset initial values. [Pg.266]

After an initial starting geometry has been generated and optimized (e.g., in a force field), the new conformation is compared with all the previously generated conformations, which are usually stored as a list of unique conformations. If a substantially different geometry is detected it is added to the list otherwise, it is rejected. Then a new initial structure is generated for the next iteration. Finally, a preset stop criterion, e.g., that a given number of loops has been performed or that no new conformations can be found, terminates the procedure. [Pg.105]

Scale of Operation Coulometric methods of analysis can be used to analyze small absolute amounts of analyte. In controlled-current coulometry, for example, the moles of analyte consumed during an exhaustive electrolysis is given by equation 11.32. An electrolysis carried out with a constant current of 100 pA for 100 s, therefore, consumes only 1 X 10 mol of analyte if = 1. For an analyte with a molecular weight of 100 g/mol, 1 X 10 mol corresponds to only 10 pg. The concentration of analyte in the electrochemical cell, however, must be sufficient to allow an accurate determination of the end point. When using visual end points, coulometric titrations require solution concentrations greater than 10 M and, as with conventional titrations, are limited to major and minor analytes. A coulometric titration to a preset potentiometric end point is feasible even with solution concentrations of 10 M, making possible the analysis of trace analytes. [Pg.507]

In both of these pieces of apparatus, isothermal operation and optimum membrane area are obtained. Good temperature control is essential not only to provide a value for T in the equations, but also because the capillary attached to a larger reservoir behaves like a thermometer, with the column height varying with temperature fluctuations. The contact area must be maximized to speed up an otherwise slow equilibration process. Various practical strategies for presetting the osmometer to an approximate n value have been developed, and these also accelerate the equilibration process. [Pg.550]

Filters for use in sterile gas filtration must conform to standards similar to those mandated for sterile hquid filtration. Nondestmctive integrity tests may be apphed. The tests are performed by wetting the filter with an appropriate solvent, commonly 60/40 isopropyl alcohol/water for hydrophobic membranes, and applying air or nitrogen gas at a preset pressure. [Pg.142]

The Bucher-Guyer horizontal rotary press is a highly automated batch process machine that requires no press aid. The press consists of a horizontal hydrauhc ram inside a rotating cylinder containing many flexible rods covered with a knitted synthetic fabric. The rods have serrated surfaces to allow juice which passes through the fabric to flow to the discharge ends. Hydrauhc pressure is apphed for a preset time, the ram is retracted, and the cylinder is rotated to break up the press cake. This cycle is repeated several times before the press cake is removed from the cylinder and the press is cleaned (16). Juice yield for this horizontal rotary press is 84% with secondary water addition it is increased to 92% (15). [Pg.572]

Hydrauhc pressure is apphed to the mash first at 2750—3440 kPa (400—500 psi) and then at 17,200—20,600 kPa (2500—3000 psi) for preset times the pomace is removed after each cycle. One person can operate several presses at once, each with a 4—5 t/h throughput. [Pg.572]

Process variables that must be controlled include the power level, pressure, and flow of the arc gases, and the rate of flow of powder and carrier gas. The spray gun position and gun to substrate distance are usually preset. Substrate temperature can be controlled by preheating and by limiting temperature increase during spraying by periodic intermptions of the spray. [Pg.135]

Trip Valves The trip valve is part of a system that is used where a specific valve action (i.e., fail up, Fail down, or lock in last position) is required when pneumatic supply pressure to the control valve falls befow a preset level. Trip systems are used primarily on springless piston ac tuators requiring fail-open or fail-closed acrion. An air storage or Volume tank and a check v ve are used with the trip valve to provide power to stroke the valve when supply pressure is lost. Trip valves are designed with hysteresis around the trip point to avoid instabihty when the trip pressure and the reset pressure settings are too close to the same value. [Pg.786]

Operating Pressure Raising the pressure may increase the separation efficiency considerably. Calculations involving the absorption of methanol from water-saturated air showed that doubling the pressure doubled the concentration of methanol which could be tolerated in the feed gas while stiU achieving a preset concentration specification in the off gas. [Pg.1359]

The Asahi process (Fig. 16-63) is used principally for high-volume water treatment. The hquid to be treated is passed upward through a resin bed in the adsorption tank. The upward flow at 30-40 m/h [12-16 gal/(min ft")] keeps the bed packed against the top. After a preset time, 10 to 60 min, the flow is interrupted for about 30 s, allowing the entire bed to drop. A small portion (10 percent or less) of the ion-exchange resin is removed from the bottom of the adsorption tank and transferred hydraulically to the hopper feeding the regeneration tank. [Pg.1557]


See other pages where Preset is mentioned: [Pg.506]    [Pg.507]    [Pg.1604]    [Pg.1917]    [Pg.100]    [Pg.387]    [Pg.256]    [Pg.265]    [Pg.322]    [Pg.120]    [Pg.525]    [Pg.170]    [Pg.172]    [Pg.145]    [Pg.148]    [Pg.359]    [Pg.484]    [Pg.255]    [Pg.31]    [Pg.303]    [Pg.578]    [Pg.23]    [Pg.517]    [Pg.423]    [Pg.362]    [Pg.214]    [Pg.764]    [Pg.1688]    [Pg.1769]    [Pg.1864]    [Pg.1942]    [Pg.2328]    [Pg.77]    [Pg.78]    [Pg.79]    [Pg.109]    [Pg.139]    [Pg.143]    [Pg.143]   


SEARCH



Asynchronous preset

Modifying presets

Phase presetting

Preset counts

Preset value

Presets

Presets

Pressure preset ventilators

Saving presets

Synchronous preset

Up-down presetable counter

Volume preset ventilators

With Asynchronous Preset and Clear

With Synchronous Preset and Clear

© 2024 chempedia.info