Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Draft towers

The thermal design of cooling towers follows the same general procedures already presented. Integration of equation 35 is usually done numerically using the appropriate software, mass-transfer coefficients, saturation enthalpies, etc. In mechanical-draft towers the air and water dows are both suppHed by machines, and hence dow rates are fixed. Under these conditions the design procedure is straightforward. [Pg.104]

Natural-draft cooling towers are extremely sensitive to air-inlet conditions owing to the effects on draft. It can rapidly be estabUshed from these approximate equations that as the air-inlet temperature approaches the water-inlet temperature, the allowable heat load decreases rapidly. For this reason, natural-draft towers are unsuitable in many regions of the United States. Figure 10 shows the effect of air-inlet temperature on the allowable heat load of a natural-draft tower for some arbitrary numerical values and inlet rh of 50%. The trend is typical. [Pg.105]

Cooling-Tower Plumes. An important consideration in the acceptabiHty of either a mechanical-draft or a natural-draft tower cooling system is the effect on the environment. The plume emitted by a cooling tower is seen by the surrounding community and can lead to trouble if it is a source of severe ground fog under some atmospheric conditions. The natural-draft tower is much less likely to produce fogging than is the mechanical-draft tower. Nonetheless, it is desirable to devise techniques for predicting plume trajectory and attenuation. [Pg.105]

Two types of mechanical-draft towers are in use today the forced-draft and the induced-draft. In the forced-draft tower the fan is mounted at the base, and air is forced in at the bottom and discharged at low velocity through the top. This arrangement has the advantage of locating the ran and drive outside the tower, where it is convenient for inspection, maintenance, and repairs. Since the equipment is out of the hot, humid top area of the tower, the fan is not subjected to corrosive conditions. However, because of the low exit-air velocity, the forced-draft tower is subjected to excessive recirculation of the humid... [Pg.1163]

FIG. 12-14 Sizing chart for a coiinterflow induced-draft cooling tower, for induced-draft towers with (1) an iipspray distributing system with 24 ft of fill or (2) a flume-type distributing system and 32 ft of fill. The chart will give approximations for towers of any height. (Ecodyne Carp.)... [Pg.1164]

Data for determining the size of natural-draft towers have been presented by Chilton [Proc. Inst. Elec. Eng., 99,440 (1952)] and Rish and Steel (ASCE Swuposium on Thermal Power Plants, October 19.58). Chilton showed that the duty coefficient Df of a tower is approximately constant over its normal range of operation and is related to tower size by an efficiency factor or performance coefficient as follows ... [Pg.1169]

To determine how a natural-draft tower of any given duty coefficient will perform under varying conditions, Rish and Steel plotted the nomograph in Fig. 12-22. The straight hne shown on the nomograph illustrates the conditions of Example 14. [Pg.1169]

This type of tower uses fans at the base to force air through the tower fill or packing (Figure 9-102). Due to the relatively low oudet air velocity, there is a tendency for discharged hot air to recirculate into the fan intake and reduce tower performance. The fan handles only atmospheric air thereby reducing its corrosion problem when compared to the fan on an induced draft tower. The tower size for the forced as well as the induced draft unit is considerably less than for an atmospheric or natural draft unit due to the higher heat transfer rates. [Pg.380]

This tower uses fans at the top of the tower to draw air in the base of the tower through the fill and out the fan discharge (Figures 9-103-105). In this type of mechanical draft tower the hot moist air discharges vertically (usually) to the atmosphere with such a velocity as to eliminate the possibility of recirculation of this air in at the base of the tower. This moist air is corrosive to the fan parts and therefore requires protection of coated plastic or special metal blades and sealed motors and reduction gears. [Pg.380]

Figure 9-101. Component parts of modem natural draft tower. Used by permission of Hamon Cooling Towers, Inc. Figure 9-101. Component parts of modem natural draft tower. Used by permission of Hamon Cooling Towers, Inc.
Drift Loss or Windage Loss the amount of water lost from a tower as fine droplets entrained in the leaving air. For an atmospheric type tower this is usually 0.1-0.2% of the total water circulated. For mechanical draft towers it is usually less. [Pg.382]

Figure 9-102. Cross-section of iow-head forced-draft tower showing fan housing arrangement, fiiling, water distribution spray system and spray eliminators. Used by permission of Foster Wheeler Corp., Cooling Tower Dept. Figure 9-102. Cross-section of iow-head forced-draft tower showing fan housing arrangement, fiiling, water distribution spray system and spray eliminators. Used by permission of Foster Wheeler Corp., Cooling Tower Dept.
Recirculation the portion of exit or outlet air from the tower that recirculates back to the inlet of the fresh air to the tower. To keep this low it is important to space towers away from each other as well as from any structures which can deflect the exit moist air back to the inlet. Due to recirculation the wet bulb temperature at the tower inlet may be different from that at a point 100 yards away. The recirculation of induced draft towers is usually less than forced draft due to the upward velocity of discharge of the air. [Pg.383]

Normal recirculation in average installations for forced draft may run 3-10% of total inlet air, and 1-8% for induced draft towers, all depending upon the location and wind conditions during any day or season. Some towers can be arranged to have less than 1% recirculation. If conditions are suspected of being conductive to recirculation, it should definitely be allowed for in design of the tower. Recirculation increases the wet bulb temperature of entering air, increases the total air required (and hence size of... [Pg.383]

The economics of forced and induced draft cooling tower operation require a study of fan and water pump horsepower and usually dictate a fan static pressure requirement not to exceed 0.75-1.0 in. of water. For atmospheric and natural draft towers the economics of pumping water are still very important. This means that the ground area must be so selected as to keep the height dovm while not dropping the unit rates so low that performance becomes poor. This then, is a balance of ground area versus total deck height. Pritchard [16] presents an... [Pg.391]

Pressure loss through louvers for induced draft tower Assume louvers are along 24-ft dimension Total louver face area... [Pg.407]

Data is given in Figure 9-129 for tvater-air system. Performance of Atmospheric and Natural Draft Towers... [Pg.408]

The evaluation of atmospheric and natural draft towers has not been completely presented in the detail comparable to mechanical draft towers. Some data are available in estimating form, but the evaluation of transfer rates is only adequate for estimating purposes [4]. The design of such towers by the process engineer must be made only after due consideration of this, and ample factor of safety should be included. Figure 9-130 presents general information on water loss due to wind on the tower. [Pg.408]

Performance, 387 Ground Area vs. Height, 391 Pressure Losses, 393 Fan Horsepower for Mechanical Draft Tower, 392 Water Rates and Distribution, 393 Blow-Down and Continuation Build-Up, 394 Example 915 Determining Approximate Blow-Down for Cooling Tower, 395 Pre-... [Pg.498]

Having selected and purchased a cooling tower, it needs regular maintenance, as does any other part of the plant. This is true of every cooling tower, from the largest natural-draft tower to the smallest packaged unit. [Pg.530]

On larger multi-celled mechanical-draft towers of both counterflow and crossflow variety, the air inlets are confined to the two opposing faces and windage or drift loss is unlikely to occur, except under exceptionally high wind conditions. Here again, remedial work, depending upon the location, can be applied but at additional cost (see Figure 34.10). [Pg.533]

Mix products - placing a forced-draft tower beside an induced-draft one causes problems for both designs (Figure 34.12). [Pg.535]

Figure34.12 Mixing forced draft with induced. The overloaded forced-draft tower with excess plume results in elevated wet bulb at air inlets on new tower. Removing the forced draft and adding one more cell to the induced draft resolved the problem... Figure34.12 Mixing forced draft with induced. The overloaded forced-draft tower with excess plume results in elevated wet bulb at air inlets on new tower. Removing the forced draft and adding one more cell to the induced draft resolved the problem...
Figure 34.15 Ice on natural-draft tower (no de-icing ring fitted)... Figure 34.15 Ice on natural-draft tower (no de-icing ring fitted)...
Chimney-assisted natural draft towers are of hyperboloidal shapes because they have greater strength for a given thickness a tower 250 ft high has concrete walls 5-6 in. thick. The enlarged cross section at the top aids in dispersion of. exit humid air into the atmosphere. [Pg.4]

Countercurrent induced draft towers are the most common in process industries. They are able to cool water within 2 F of the wet bulb. [Pg.4]

Evaporation losses are 1 % of the circulation for every 100 F of cooling range. Windage or drift losses of mechanical draft towers are 0.1-0.3%. Blowdown of 2.5-3.0% of the circulation is necessary to prevent excessive salt buildup. [Pg.4]


See other pages where Draft towers is mentioned: [Pg.103]    [Pg.104]    [Pg.105]    [Pg.105]    [Pg.105]    [Pg.105]    [Pg.1149]    [Pg.1149]    [Pg.1163]    [Pg.1164]    [Pg.1165]    [Pg.1168]    [Pg.1169]    [Pg.1169]    [Pg.75]    [Pg.387]    [Pg.390]    [Pg.392]    [Pg.526]    [Pg.530]    [Pg.532]    [Pg.534]    [Pg.534]    [Pg.535]   
See also in sourсe #XX -- [ Pg.259 , Pg.260 , Pg.260 ]




SEARCH



Comparison Between Characteristics of Mechanical- and Natural-Draft Cooling Towers

Cooling tower draft

Cooling tower forced draft

Cooling tower induced draft

Cooling towers forced-draft tower

Cooling towers induced-draft tower

Cooling towers mechanical draft tower

Cooling towers natural draft tower

Crossflow mechanical draft towers

Hyperbolic natural-draft tower

Hyperbolic, natural draft cooling towers

Large mechanical-draft cooling towers

Mechanical draft cooling towers

Mechanical draft towers

Mechanical-draft cooling towers performance

Natural draft cooling towers

Natural draft towers

Towers forced-draft

Towers induced-draft

© 2024 chempedia.info