Cooling towers location

Cooling Towers. The cooling tower location relative to the prevailing wind direction should be such that the wind hits the short side or the side perpendicular to the inlet louvers. This helps balance the air flow to the two inlet sides. [Pg.79]

The cooling tower location with regard to its proximity to a susceptible population. [Pg.323]

Heat picked up by the water on the shell side of the heat exchanger loop is dumped to the secondary system sump tank. The cooling tower loop then draws its suction from the sump tank and pumps the heated water through a cooling tower located on the roof of the console area. Finally, the cooled water is returned to the sump tank to restart the cooling cycle. [Pg.205]

Plant layout and noise suppression material are two general noise abatement methods. Plant layout does not affect noise levels at any given point however, noise can be abated by screening off a section of the plant. An example of this is to orient cooling towers with their closed faces toward the critical location. This method must also consider wind direction to balance air draft. Tankage can be located to act as a noise screen. [Pg.83]

The fibrous strands that composed the mounds adhering to the tube wall were examined and identified as seed hairs from grass. Subsequently, fibrous material was collected from the cooling tower basin and seed pods from grass growing in a bog located adjacent to and upwind of the cooling towers. This material was also examined and found to be identical to the seed hairs that composed the mounds adhering to the tube wall. [Pg.257]

Specimen Location Suction side component of cooling tower pump... [Pg.285]

In addition, the small motor fan attempts to blow air down over the motor and is no match for the much bigger cooling tower fan drawing air up and around the motor. The small fan in this case is useless- even counterproductive. This application needs a TEAO motor. Cooling tower manufacturers sometimes purchase special motors tailored for their application... special grease, seals, slingers, weep hole locations, epoxy coatings, etc.. Such features make an OEM replacement more desirable than an off the shelf replacement. [Pg.81]

Cooling towers and evaporative condensers release into the atmosphere fine droplets of water, which may carry sources of contamination such as algae and bacteria. Many of these thrive at the temperatures to be expected in water cooling systems and one of them, Legionella pneumophila, has been identified as a particular hazard to health. Cooling apparatus should be cleaned and disinfected frequently to reduce these risks of contamination and should not be located where water droplets can be drawn into ventilation air intakes. [Pg.77]

At some sites, the cooling water required can be taken from a river or lake, or from the sea at other locations cooling towers will be needed. [Pg.893]

Fire prevention may include providing degassing boots/vent stacks to the top of risers where flammable combustible vapors can be entrained in the water system, i.e. water pressure lower than process pressure. Combustible gas detection at the top ofthe vent stacks can be used to detect flammable material presence in cooling tower. However, the hostile environment and difficult to access location makes the detection challenging to maintain. [Pg.320]

Location of cooling tower with respect to exposure to or from nearby processing, storage, or utility operations or facilities... [Pg.320]

Cooling towers spacing and layout should follow the criteria found in CCPS book Guidelines for Facility Siting and Layout (CCPS, 2003b). If the cooling tower s combustible exterior is protected for exposure with a sprinkler system, it may (on a case-by-case basis) be located less than 100 ft (30 m) from the hazard. [Pg.321]

The sulfuric acid plant has boiler blowdown and cooling tower blowdown waste streams, which are uncontaminated. However, accidental spills of acid can and do occur, and when they do, the spills contaminate the blowdown streams. Therefore, neutralization facilities should be supplied for the blowdown waste streams (Table 15), which involves the installation of a reliable pH or conductivity continuous-monitoring unit on the plant effluent stream. The second part of the system is a retaining area through which non-contaminated effluent normally flows. The detection and alarm system, when activated, causes a plant shutdown that allows location of the failure and initiation of necessary repairs. Such a system, therefore, provides the continuous protection of natural drainage waters, as well as the means to correct a process disruption. [Pg.431]

Gas ejectors (an ejector is a vent for removing non-condensable gases from the condensing unit located downstream from the turbine. Condensate from the cooling towers is pumped to the condenser unit to condense the steam leaving the turbine. In this way, low pressure is created downstream from the turbine, which leads to improved efficiency to generate electric... [Pg.301]

Fig. 6. Simplified schematic layout of a classic geothermal power plant. The main escape routes for steam are from the cooling tower and gas ejectors, which are located just downstream from the turbine. Fig. 6. Simplified schematic layout of a classic geothermal power plant. The main escape routes for steam are from the cooling tower and gas ejectors, which are located just downstream from the turbine.
The electron gun is located at the outer wall of the accelerating cavity, and the electrons are injected into the cavity at a voltage of abouf 35-40 kV. The cavify is cooled by a water jacket on the inner coaxial conductor and at the end flanges and by discrefe water channels along the outer diameter. The system is designed to operate with a 2 MW cooling tower up to an outside temperature of 35°C (95°F). Therefore, no water chiller is required. The RF amplifier defects and follows changes in fhe resonant frequency of the cavity so that accurate control of the cavity temperature is not required. [Pg.47]


See other pages where Cooling towers location is mentioned: [Pg.90]    [Pg.87]    [Pg.111]    [Pg.111]    [Pg.90]    [Pg.87]    [Pg.66]    [Pg.228]    [Pg.154]    [Pg.547]    [Pg.237]    [Pg.90]    [Pg.87]    [Pg.111]    [Pg.111]    [Pg.90]    [Pg.87]    [Pg.66]    [Pg.228]    [Pg.154]    [Pg.547]    [Pg.237]    [Pg.70]    [Pg.79]    [Pg.79]    [Pg.355]    [Pg.103]    [Pg.478]    [Pg.1166]    [Pg.1166]    [Pg.140]    [Pg.239]    [Pg.77]    [Pg.84]    [Pg.532]    [Pg.341]    [Pg.184]    [Pg.86]    [Pg.299]    [Pg.42]    [Pg.303]    [Pg.478]    [Pg.70]    [Pg.79]   
See also in sourсe #XX -- [ Pg.95 , Pg.96 ]




SEARCH



Cooling tower

Tower Location

© 2024 chempedia.info