Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Process control proportional response

Cyclic voltammetry was carried out in the presence of penta- and hexacyano-ferrate complexes in order to probe the homogeneity and conductivity of the TRPyPz/CuTSPc films (125), (Fig. 36). When the potentials are scanned from 0.40 to 1.2 V in the presence of [Fe (CN)6] and [Fe CN)5(NH3)] complexes, no electrochemical response was observed at their normal redox potentials (i.e., 0.42 and 0.33 V), respectively. However, a rather sharp and intense anodic peak appears at the onset of the broad oxidation wave, 0.70 V. The current intensity of this electrochemical process is proportional to the square root of the scan rate, as expected for a diffusion-controlled oxidation reaction at the modified electrode surface. The results are consistent with an electrochemical process mediated by the porphyrazine film, which act as a physical barrier for the approach of the cyanoferrate complexes from the glassy carbon electrode surface. [Pg.423]

Chapter 22 provides equations for typical process controllers and control valve dynamics. The controllers considered are the proportional controller, the proportional plus integral (PI) controller and the proportional plus integral plus derivative (PID) controller. Integral desaturation is an important feature of PI controllers, and mathematical mc els are produced for three different types in industrial use. The control valve is almost always the final actuator in process plan. A simple model for the transient response of the control valve is given, which makes allowance for limitations on the maximum velocity of movement. In addition, backlash and velocity deadband methods are presented to model the nonlinear effect of static friction on the valve. [Pg.4]

Example 29.4 Closed-Loop Response of a First-Order Process under Proportional Digital Control... [Pg.322]

To illustrate the influence of each control mode, consider the control system responses shown in Figure 9.4. These curves illustrate the typical response of a controlled process for different types of feedback control after the process experiences a sustained disturbance. Without control the process slowly reaches a new steady state that differs from the desired steady state. The effect of proportional control is to speed up the process response and reduce the offset. The addition of integral control eliminates offset but tends to make the response more oscillatory. Adding derivative action reduces the degree of oscillation and the response time, ... [Pg.205]

Proportional-plus-integral control is the most generally useful control mode and therefore the one usually applied to automated process-control. Its major limitation is in processes with large dead-time and capacitance if reset time is faster than process dead-time, the controller-response changes are faster than the process, and cycling results. In these cases, derivative control is beneficial. [Pg.778]

With the exception of simple, manually controlled shutoff valves, process-control valves are generally used to control the volume and pressure of gases or liquids within a process system. In most applications, valves are controlled from a remote location through the use of pneumatic, hydraulic, or electronic actuators. Actuators are used to position the gate, ball, or disk that starts, stops, directs, or proportions the flow of gas or liquid through the valve. Therefore, the response characteristics of a valve are determined, in part, by the actuator. Three factors critical to proper valve operation are response time, length of travel, and repeatability. [Pg.186]

The kind of response more likely to occur is a load change, requiring a different value of controller output. What could happen to a dead time process under proportional control in the event of a gradual load change is plotted in Fig. 1.7. [Pg.12]

Reset, then, is necessary if offset is to be eliminated altogether. Whether proportional and derivative are useful modes depends on the nature of the process. If rapid load changes outside the forward loop may be encountered, proportional and derivative action could be advantageous. If the process Is fundamentally non-self-regulating, as in level control, proportional action Is essential. Finally, if the process is fairly easy to control because of the absence of dead time, derivative may be useful in Improving the dynamic load response-but this is unusual. [Pg.220]

Control algorithms We have discussed that in closed-loop control systems a corrective action is taken by the controller in response to feedback from a transducer. The exact corrective action depends on the algorithm which has been developed. The simplest control approach is a two position control which turns the control element on and off based on the monitored value of the output. With an on/off strategy, the process value will typically oscillate above and below the set point. The most common controller is the PID (proportional, integral, and derivative) loop controller which is able to detect an early trend, adjust quickly, and prevent an over-correction. A PID controller can maintain temperatures within 1°F. The controller provides the means to define the control algorithm by assigning a constant for each of the three control modes. Typically, most of the adjustment is accomplished with the proportional control element, with the control action, u be-... [Pg.381]

Integral action can be slow, since it relies on the integral of the error being large, where the error is the difference between the set point and the process variable. Proportional action usually provides the muscle for the controller. However, too much proportional action creates instability. In some circumstances, PI controllers are not sufficiently fast, making a third controller action necessary. This term is called derivative time and can someffines be introduced to speed up the response time of the controller. The control equation for a proportional-integral-derivative (PID) controller is... [Pg.288]

Open-Loop versus Closed-Loop Dynamics It is common in industry to manipulate coolant in a jacketed reacdor in order to control conditions in the reacdor itself. A simplified schematic diagram of such a reactor control system is shown in Fig. 8-2. Assume that the reacdor temperature is adjusted by a controller that increases the coolant flow in proportion to the difference between the desired reactor temperature and the temperature that is measured. The proportionality constant is K. If a small change in the temperature of the inlet stream occurs, then depending on the value or K, one might observe the reactor temperature responses shown in Fig. 8-3. The top plot shows the case for no control (K = 0), which is called the open loop, or the normal dynamic response of the process by itself. As increases, several effects can be noted. First, the reactor temperature responds faster and faster. Second, for the initial increases in K, the maximum deviation in the reactor temperature becomes smaller. Both of these effects are desirable so that disturbances from normal operation have... [Pg.718]

We expect that a proportional controller will improve or accelerate the response of a process. The larger Kc is, the faster and more sensitive is the change in the compensation with respect to a given error. However, if Kc is too large, we expect the control compensation to overreact, leading to oscillatory response. In the worst case scenario, the system may become unstable. [Pg.84]

In terms of the situation, if we use a PI controller on a slow multi-capacity process, the resulting system response will be even more sluggish. We should use PID control to increase the speed of the closed-loop response (being able to use a higher proportional gain) while maintaining stability and robustness. This comment applies to other cases such as temperature control as well. [Pg.102]

Figure 31 demonstrates the combined controller response to a demand disturbance. The proportional action of the controller stabilizes the process. The reset action combined with the proportional action causes the measured variable to return to the setpoint. The rate action combined with the proportional action reduces the initial overshoot and cyclic period. [Pg.153]

J6. The frequency response data given below were obtained by pulse-testing a closed-loop system that contained a proportional-only controller with a proportional band of 25. Controller setpoint was pulsed and the process measurement signal was recorded as the output signal. [Pg.497]


See other pages where Process control proportional response is mentioned: [Pg.69]    [Pg.637]    [Pg.551]    [Pg.305]    [Pg.126]    [Pg.124]    [Pg.1230]    [Pg.241]    [Pg.173]    [Pg.174]    [Pg.273]    [Pg.81]    [Pg.96]    [Pg.16]    [Pg.51]    [Pg.202]    [Pg.152]    [Pg.69]    [Pg.777]    [Pg.777]    [Pg.373]    [Pg.131]    [Pg.192]    [Pg.89]    [Pg.134]    [Pg.94]    [Pg.13]    [Pg.496]    [Pg.533]    [Pg.177]    [Pg.283]    [Pg.113]    [Pg.228]   
See also in sourсe #XX -- [ Pg.40 ]




SEARCH



Control response

Controlled response

Process response

Proportional control

Proportional controller

Response controller

© 2024 chempedia.info