A SELV system is an extra-low voltage system (50 Vac or 120 Vdc free of ripple when measured between any two conductors), which is electrically separated from the earth (or ground) and other systems (such as the primary winding of an isolating transformer) in such a way that a single fault cannot give rise to the risk of electric shock. A PELV system is also an extra-low voltage system, but is one that is not electrically separated from earth. In all other respects it must satisfy the requirements of a SELV system. [Pg.364]

PELV An extra-low voltage system similar to SELV but connected to earth at... [Pg.513]

Some people assume that the term low voltage means safe voltages, but as you have seen the LVD applies to products that operate at typical line (mains) voltages (e.g., 230/400 volts in Europe and 120/208 volts in the U.S.) that present shock and fire hazards. Safe voltages are those less than 50 Vac/60 Vdc, depending on the standard or term applied and are referred to as Extra-Low Voltage or Safety Extra-Low Voltage (ELV/SELV). [Pg.85]

ISO 8818 1988 Leisure accommodation vehicles — Caravans — 12 V direct current extra low voltage electrical installations... [Pg.96]

Extra low-voltage (less than 50Va.e.) e.g. telephone equipment, low-voltage desk lights No No No... [Pg.42]

Very small transformers are used in electronic applications. Small transformers are used as isolating transformers in shaver sockets and can also be used to supply separated extra-low-voltage (SELV) sources. Equipment supplied from a SELV source may be installed in a bathroom or shower room, provided that it is suitably enclosed and protected from the ingress of moisture. This includes equipment such as water heaters, pumps for showers and whirlpool baths. [Pg.96]

Isolating transformers - such as separated extra-low voltage (SELV) transformers. If the primary winding and the secondary winding of a double wound transformer have a separate connection to earth, then the output of the transformer is effectively isolated from the input since the only connection between the primary and secondary windings is the magnetic flux in the core. [Pg.120]

Tbere are occasions when even a 110 V supply from a centre-tapped transformer is too high for example, supplies to inspection lamps for use inside damp or confined places. In these circumstances a safety extra-low voltage (SELV) supply would be required. [Pg.250]

The wiring of the extra-low-voltage battery supply must be run in such a way that it does not come into contact with the 230V wiring system (lET Regulation 721.528.1). [Pg.252]

Electrical supplies at voltages above extra low voltages (ELV) - that is, above 50V a.c. - can kill human beings and livestock and should therefore be treated with the greatest respect. As an electrician working on electrical installations and equipment, you should always make sure that the supply... [Pg.38]

Any voltage above PELV (Protective extra low voltage), i.e. 25V ac or 60V ripple-free dc... [Pg.259]

For both normal and abnormal environments it is essential to preserve the integrity of the extra-low voltage circuit and prevent it from becoming live at a higher voltage from another system. Therefore, in a SELV system, any exposed conductive parts should not be connected to, or be in contact with. [Pg.36]

Where it is not possible to meet all the requirements in subsection 411-02 for SELV, but the voltage does not exceed extra-low voltage, the protection is called protective extra low voltage (PELV). The difference between a SELV and PELV system is that the latter is connected to earth but in other respects meets the SELV requirements. Other extra-low voltage systems are called functional extra-low voltage (FELV). The relevant precautions are detailed in section 471-14. The socket outlets in SELV, PELV and FELV systems... [Pg.134]

It may be impracticable to supply the more powerful hand tools, such as large angle grinders, at extra-low voltage, so section 606-04-04 allows the use of higher voltage tools protected by electrical separation. As already observed, pneumatic or hydraulically powered tools are an alternative. [Pg.160]

Regulation 608-03-04 requires extraneous conductive parts to be connected to the protective conductor to establish an equipotential zone. The special requirements include the provisions of section 601 if there is a bath or shower, so any socket outlets must be not less than 2.5 m from them. The extra-low voltage (usually 12 V) circuit cables to the rear and brake lights have to be separated from the low voltage wiring see Regulation 608-06-04. [Pg.161]

Section 4 deals with yet another method - the use of extra-low voltage, i.e. [Pg.169]

Fig. 16.2 Welding under a walkway in a ship s engine room. The safety precautions are (1) The power source is fitted with a low voltage device. (2) The handlamp and heated quiver are fred from step-down transformers and operate at safety extra-low voltage. (3) There is an insulated box for the electrode holder when not in use. (4) The fumes are extracted by the centrifugal fan. (5) The operator is wearing insulated clothing and rubber boots and is separated from the steel floor by l5nng on dry wooden planks. (6) There is a second person present. Fig. 16.2 Welding under a walkway in a ship s engine room. The safety precautions are (1) The power source is fitted with a low voltage device. (2) The handlamp and heated quiver are fred from step-down transformers and operate at safety extra-low voltage. (3) There is an insulated box for the electrode holder when not in use. (4) The fumes are extracted by the centrifugal fan. (5) The operator is wearing insulated clothing and rubber boots and is separated from the steel floor by l5nng on dry wooden planks. (6) There is a second person present.
Where cables pass through fire barriers, check that the opening is sealed. Ensure that segregation of the telecommunication, fire alarm, emergency lighting and extra-low voltage circuits from the rest of the installation circuits has been effected. [Pg.343]

Ceiling recessed downlighters have caused fires. Samples should be removed to check whether there is adequate ventilation space in the ceiling void to dissipate the lamp heat, particularly where there is thermal insulation. Check also that the cables are of adequate size where the luminaire does not have an integral transformer and the extra-low voltage lamps are fed from a separate transformer. [Pg.345]

Requirement of synchrony on driving of bimanual controls, light indication during operation, selector switch with lock, operator interface with extra low voltage with maximum 25 V, contactors with mechanically guided contacts (BRASIL, 2010). These aspects are hard to fit in machines, because require changes of electrical parts ... [Pg.87]


See other pages where Voltage extra low is mentioned: [Pg.364]    [Pg.508]    [Pg.514]    [Pg.86]    [Pg.161]    [Pg.372]    [Pg.146]    [Pg.226]    [Pg.257]    [Pg.4]    [Pg.33]    [Pg.36]    [Pg.37]    [Pg.37]    [Pg.37]    [Pg.134]    [Pg.134]    [Pg.147]    [Pg.374]    [Pg.374]    [Pg.374]    [Pg.192]   