Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Valve, control flow characteristics

Figure 10-13 Control valve flow characteristics. (From Fisher Controls, 1987.)... Figure 10-13 Control valve flow characteristics. (From Fisher Controls, 1987.)...
The control valve flow characteristics and the functionality between the flow through the control valve and the valve signal voltage were determined experimentally. The voltage is applied across a resistor to the... [Pg.195]

Control valves. Valve vendors publish much information about flow-control valves. Much of their information covers what is known as control valve flow coefficients Cv. It is convenient to express the valve capacity and the valve flow characteristics in terms of the flow coefficient Cv. This value is defined as the flow of water at 60°F, in gallons per minute (gpm), at a pressure drop of 1.0 psi across the valve. In a flow valve, therefore, controlling the flow of water at 60°F as the valve opens, keeping a 1.0-psi pressure drop across the valve, the C value is the rate of water flow, gpm. [Pg.225]

Table 2.61 lists the inherent valve characteristics of the various types of control valves. The characteristics that are recommended are a function of the intended application, and are listed in the tabulation at the lower part of Figure 2.62. It should be noted that the listed valve characteristics assume that the valve pressure drop is constant. Unfortunately, in most applications (Figure 2.60), the available valve pressure differential is not constant but drops as the load (flow) increases. This is the reason why the recommended valve characteristics in Figure 2.62 are different if the ratio of the maximum to minimum pressure differential is above or below 2 1. [Pg.214]

Modifications of the fuel injectors of an advanced combustor were made to permit spatial control of individual fuel-injection sites. Miniature fuel delivery valves were developed and flow bench was tested to characterize the valve flow characteristics. Optical sensors and a translating gas sampling rake are being integrated in an experimental rig to evaluate the level of pattern factor control at the combustor exit. The CFD simulations were run, and the results will be validated with data that will be acquired from the forthcoming APFC experiments. The numerical solutions will then be used to develop control algorithms that will be used for future closed-loop APFC experiments. [Pg.189]

IV.l Consider the flow control loop shown in Figure 13.2a. The following information is also available (1) An orifice plate is used to measure the flow (2) a variable capacitance differential pressure transducer is employed (see Appendix 11 A) to sense and transmit the pressure difference developed around the orifice plate (3) the controller is PI and (4) the control valve is of equal percentage, with the valve flow characteristic curve given by... [Pg.548]

Another factor that affects the linearity of the response is the characteristic of the valve selected. Three of the most common valve characteristics include quick opening, linear, and equal percentage. If the majority of the system pressure drop is taken across the valve, then a linear valve should be used since its installed characteristic will also be linear, giving the linear response desired. However, if the pressure drop across the valve is a small part of the total line drop and is not constant, then an equal percentage valve can be used since its installed characteristic will be close to linear. Quick-opening valves are most commonly used with on-off controllers where a large flow is needed as soon as the valve begins to open. More information on these valve flow characteristics can be found in Chapter 2. [Pg.148]

FIG. 8-82 Installed flow characteristic as a function of percent of total system head allocated to the control valve (assuming constant head pump, no elevation head loss, and an R equal 30 equal-percentage inherent characteristic). [Pg.791]

Determine the operating point on the pump characteristic curve when the flow is such that the pressure drop across the control valve is 35 kN/m2. [Pg.241]

FLOW MEASUREMENT SIGNAL TO CONTROLLER LOCATION OF CONTROL VALVE IN RELATION TO MEASURING ELEMENT BEST INHERENT CHARACTERISTIC ... [Pg.315]

Table 10-3 Example Flow Coefficient Values for a Control Valve with Various Trim Characteristics... [Pg.318]

You want to control the flow rate of a liquid in a transfer line at 350 gpm. The pump in the line has the characteristics shown in Fig. 8-2, with an 5 in. impeller. The line contains 150 ft of 3 in. sch 40 pipe, 10 flanged elbows, four gate valves, and a 3 x 3 control valve. The pressure and elevation at the entrance and exit of the line are the same. The valve has an equal percentage trim with the characteristics given in Table 10-3. What should the valve opening be to achieve the desired flow rate (in terms of percent of total stem travel) The fluid has a viscosity of 5cP and a SG of 0.85. [Pg.337]

A piping system takes water at 60°F from a tank at atmospheric pressure to a plant vessel at 25 psig that is 30 ft higher than the upstream tank. The transfer line contains 300 ft of 3 in. sch 40 pipe, 10 90° els, an orifice meter, a 2 x 3 pump with a 7 in. impeller (with the characteristic as given in Fig. 8-2) and a 3 x 2 equal percentage control valve with a trim characteristic as given in Table 10-3. A constant flow rate of 200 gpm is required in the system. [Pg.338]

The inherent characteristics are those that relate flow to valve position in the situation where the pressure drop over the control valve is constant. These are the (APn/AP ) = 0 curves in Fig. 7.8. Instcdled characteristics are those that result from the variation in the pressure drop over the valve. [Pg.221]

The liquid flow rate from a vertical cylindrical tank, 10 feet in diameter, is flow-controlled. The liquid flow into the tank is manipulated to control liquid level in the tank. The control valve on the inQow stream has linear installed characteristics and can pass 1000 gpm when wide open. The level transmitter has a span of 6 feet of liquid. A proportional controller is uaed with a gain of 2. Liquid density is constant. [Pg.373]

When processes are subject only to slow and small perturbations, conventional feedback PID controllers usually are adequate with set points and instrument characteristics fine-tuned in the field. As an example, two modes of control of a heat exchange process are shown in Figure 3.8 where the objective is to maintain constant outlet temperature by exchanging process heat with a heat transfer medium. Part (a) has a feedback controller which goes into action when a deviation from the preset temperature occurs and attempts to restore the set point. Inevitably some oscillation of the outlet temperature will be generated that will persist for some time and may never die down if perturbations of the inlet condition occur often enough. In the operation of the feedforward control of part (b), the flow rate and temperature of the process input are continually signalled to a computer which then finds the flow rate of heat transfer medium required to maintain constant process outlet temperature and adjusts the flow control valve appropriately. Temperature oscillation amplitude and duration will be much less in this mode. [Pg.39]

Control valves have orifices that can be adjusted to regulate the flow of fluids through them. Four features important to their use are capacity, characteristic, rangeability and recoveiy. [Pg.129]

Figure 7.17. Operating points of centrifugal pumps under a variety of conditions, (a) Operating points with a particular pump characteristic and system curves corresponding to various amounts of flow throttling with a control valve, (b) Operating point with two identical pumps in parallel each pump delivers one-half the flow and each has the same head, (c) Operating point with two identical pumps in series each pump delivers one-half the head and each has the same flow. Figure 7.17. Operating points of centrifugal pumps under a variety of conditions, (a) Operating points with a particular pump characteristic and system curves corresponding to various amounts of flow throttling with a control valve, (b) Operating point with two identical pumps in parallel each pump delivers one-half the flow and each has the same head, (c) Operating point with two identical pumps in series each pump delivers one-half the head and each has the same flow.
Flow as a secondary cannot only overcome the effects of valve hysteresis, but also insures that line pressure variations or badly selected valve characteristics will not affect the primary loop. For these reasons, in composition control systems, flow is usually set in cascade. Cascade flow loops are also useful in feedforward systems. Flow controllers invariably have both proportional and integral modes. If their proportional band exceeds 100%, they must have an integral mode. [Pg.197]

Figure 2.63 illustrates the effect of the distortion coefficient (Dc) on the characteristics of a linear and an equal-percentage valve. As the ratio of the minimum to maximum pressure drop increases, the Dc drops and the equal-percentage characteristics of the valve shift toward linear and the linear characteristics shift toward QO. In addition, as the Dc drops, the controllable minimum flow increases, and therefore, the rangeability (the flow range within which the valve characteristic remains as specified) of the valve also drops. [Pg.215]

FIGURE 19.12 Flow-lift characteristics for control valves. (TaylorInstrument Process Control Division ofSybron Corporation.)... [Pg.628]


See other pages where Valve, control flow characteristics is mentioned: [Pg.81]    [Pg.81]    [Pg.790]    [Pg.83]    [Pg.83]    [Pg.614]    [Pg.958]    [Pg.963]    [Pg.794]    [Pg.153]    [Pg.67]    [Pg.67]    [Pg.2531]    [Pg.176]    [Pg.300]    [Pg.201]    [Pg.312]    [Pg.314]    [Pg.317]    [Pg.317]    [Pg.322]    [Pg.338]    [Pg.221]    [Pg.575]    [Pg.41]    [Pg.725]    [Pg.273]    [Pg.212]    [Pg.215]    [Pg.217]   


SEARCH



Control characteristic

Control valve

Control valve characteristic

Flow characteristics

Flow control

Flow controllers

Valve characteristic

Valves, control inherent flow characteristic

Valves, control installed flow characteristic

© 2024 chempedia.info