Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Vapor flow calculation

The multicomponent form of the Underwood equation can be used to calculate the vapor flow at minimum reflux in each column of the sequence. The minimum vapor rate in a single column is obtained by alternate use of two equations ... [Pg.135]

Often in plant operations condensate at high pressures are let down to lower pressures. In such situations some low-pressure flash steam is produced, and the low-pressure condensate is either sent to a power plant or is cascaded to a lower pressure level. The following analysis solves the mass and heat balances that describe such a system, and can be used as an approximate calculation procedure. Refer to Figure 2 for a simplified view of the system and the basis for developing the mass and energy balances. We consider the condensate to be at pressure Pj and temperature tj, from whence it is let down to pressure 2. The saturation temperature at pressure Pj is tj. The vapor flow is defined as V Ibs/hr, and the condensate quality is defined as L Ibs/hr. The mass balance derived from Figure 2 is ... [Pg.494]

Another important consideration in tower design is tray downcomers size. At high ratios of liquid flow to vapor flow a proportionally greater area on the tray must be allotted to the downcomer channel opening. Downcomers are designed from basic hydraulic calculations. If the downcomer is inadequately sized and becomes filled with liquid, liquid level will build on the tray above. This unstable situation will propagate its way up to the tower and result in a flooded tower condition. Excessive entrainment can also lead to this same condition and, in fact, is usually the cause of flooding. [Pg.87]

Calculate individually the orifice area required to pass the unflashed hquid component, using Equation (8). The pressure drop term Pj should be made equal to the set pressure minus the total back pressure developed by the vapor portion at critical flow pressure, except when the critical flow pressure is less than the calculated total back pressure (superimposed plus built-up), considering the combined liquid and vapor flow. In the latter case, P should be made equal to set pressure minus the calculated total back pressure. [Pg.194]

When the maximum vapor-relieving requirement of the flare system has been established and the maximum allowable back pressure (as just described) has been defined, line sizing reduces to standard flow calculations. [Pg.324]

Thus the total mass flows tn= m, + m,) differ in different cases. Water vapor flow th, is obtained by multiplying the dry air mass flow by the corresponding humidity x (Eq. 4.93). As a basic quantity in humid air mass and energy balance calculations, we use dry air mass flow m and the effect of humidity on the energy balance is noted in the enthalpy h, (Eq. 4.87). [Pg.73]

The balance equations for water vapor flows are similar to balance equations for contaminant flows, but in addition possible condensation and evaporation must be calculated. Also they must be considered in heat flow equations. [Pg.623]

I Calculate free water and water vapor flow rates. [Pg.87]

Calculate total entrainment as pounds of liquid per hour, based on total vapor flow in tower. [Pg.169]

Whether for a distillation, absorption, or stripping system the material balance should be established around the top, bottom, and feed sections of the column. Then, using these liquid and vapor rates at actual flowing conditions, determine the flooding and maximum operating points or conditions. Then, using Figures 9-21B, -21E, or -21F, establish pressure drop, or assume a pressure drop and back-calculate a vapor flow rate, and from this a column diam-... [Pg.300]

This is still not enough change in from 24,000 to justify a calculation of a new h. Use of the water vapor flow leaving the assumed interval means the actual G through that interval will he equal to or greater than the value for conditions at 115°F. This value is on the safe side for h. ... [Pg.152]

Pressure drops from Dowtherm A heat transfer media flowing in pipes may be calculated from Figure 10-137. The effective lengths of fittings, etc., are shown in Chapter 2 of Volume 1. The vapor flow can be determined from the latent heat data and the condensate flow. With a liquid system, the liquid flow can be determined using the specific heat data. [Pg.160]

Design of vessel and vent line pipe supports is very important because very large forces can be encountered as soon as venting begins. Figure 4 shows the equations and nomenclature to calculate forces on pipe bends. The authors have heard of situations where vent line bends have been straightened, lines broken off, or vent catch tanks knocked off their foundations by excessive forces. For bends, the transient effects of the initial shock wave, the transition from vapor flow to two-phase flow, and steady state conditions should be considered. Transient conditions, however, are likely to be so rapid as to not have enough dura-... [Pg.335]

For preliminary design, liquid entrainment is usually used as a reference. To prevent entrainment, the vapor velocity for tray columns is usually in the range 1.5 to 3.5 ms-1. However, the entrainment of liquid droplets can be predicted using Equation 8.3 to calculate the settling velocity. To apply Equation 8.3 requires the parameter KT to be specified. For distillation using tray columns, KT is correlated in terms of a liquid-vapor flow parameter FLV, defined by ... [Pg.172]

Pressure drop during condensation results essentially from the vapor flow. As condensation proceeds, the vapor flowrate decreases. The equations described previously for pressure drop in shell-and-tube heat exchangers are only applicable under constant flow conditions. Again the exchanger can be divided into zones. However, in preliminary design, a reasonable estimate of the pressure drop can usually be obtained by basing the calculation on the mean of the inlet and outlet vapor flowrates. [Pg.340]

The column vapor loads (i.e. vapor flow rates up the columns) are calculated to determine the approximate equipment sizes. An approximate method for calculating the vapor flow V in a column is (Hurme, 1996). [Pg.112]

Therefore the total fluid inventory of the process is considered to be directly proportional to the total vapor flow of the columns. This is calculated by Equation 11 for each column. [Pg.115]

Additional equations include physical property relationships to get densities and enthalpies, a vapor hydraulic equation to calculate vapor flow rates from known tray pressure drops, and a liquid hydraulic relationship to get liquid flow... [Pg.71]

Calculate vapor flow rates on all trays, starting in the column base, using the algebraic form of the energy equations. [Pg.140]

Finally we can now calculate the vapor flow rate through the tray from the pressure drop through the tray (P i - P ) and the liquid height on the tray, which we can get from the weir height fi and the height of liquid over the weir... [Pg.142]

FLLO = old value of assumed total vapor flow in iterative flash calculation... [Pg.312]


See other pages where Vapor flow calculation is mentioned: [Pg.41]    [Pg.169]    [Pg.477]    [Pg.1042]    [Pg.1287]    [Pg.1288]    [Pg.2292]    [Pg.2298]    [Pg.2298]    [Pg.133]    [Pg.324]    [Pg.188]    [Pg.265]    [Pg.367]    [Pg.165]    [Pg.213]    [Pg.217]    [Pg.133]    [Pg.2]    [Pg.6]    [Pg.50]    [Pg.147]    [Pg.259]    [Pg.263]    [Pg.343]    [Pg.140]    [Pg.125]    [Pg.298]    [Pg.311]   
See also in sourсe #XX -- [ Pg.54 ]




SEARCH



Flow calculation

© 2024 chempedia.info