Thermocouples range

Type J thermocouples (Table 11.58) are one of the most common types of industrial thermocouples because of the relatively high Seebeck coefficient and low cost. They are recommended for use in the temperature range from 0 to 760°C (but never above 760°C due to an abrupt magnetic transformation that can cause decalibration even when returned to lower temperatures). Use is permitted in vacuum and in oxidizing, reducing, or inert atmospheres, with the exception of sulfurous atmospheres above 500°C. For extended use above 500°C, heavy-gauge wires are recommended. They are not recommended for subzero temperatures. These thermocouples are subject to poor conformance characteristics because of impurities in the iron. [Pg.1216]

The Type K thermocouple (Table 11.59) is more resistant to oxidation at elevated temperatures than the Type E, J, or T thermocouple, and consequently finds wide application at temperatures above 500°C. It is recommended for continuous use at temperatures within the range — 250 to 1260°C in inert or oxidizing atmospheres. It should not be used in sulfurous or reducing atmospheres, or in vacuum at high temperatures for extended times. [Pg.1216]

Temperature measurements ranging from 760 to 1760°C are made usiag iron—constantan or chromel—alumel thermocouples and optical or surface pyrometers. Temperature measuriag devices are placed ia multiple locations and protected to allow replacement without iaciaerator shutdown (see... [Pg.55]

The Ferranti-Shidey viscometer was the first commercial general-purpose cone—plate viscometer many of the instmments stiU remain in use in the 1990s. Viscosities of 20 to 3 x 10 mPa-s can be measured over a shear rate range of 1.8-18, 000 and at up to 200°C with special ceramic cones. Its features include accurate temperature measurement and good temperature control (thermocouples are embedded in the water-jacketed plate), electrical sensing of cone—plate contact, and a means of adjusting and locking the position of the cone and the plate in such a way that these two just touch. Many of the instmments have been interfaced with computers or microprocessors. [Pg.188]

The ITS-90 has its lowest point at 0.65 K and extends upward without specified limit. A number of values assigned to fixed points differ from those of the immediately previous scale, IPTS-68. In addition, the standard platinum resistance thermometer (SPRC) is specified as the interpolation standard from 13.8033 K to 961.78°C, and the interpolation standard above 961.78°C is a radiation thermometer based on Planck s radiation law. Between 0.65 and 13.8033 K interpolation of the scale rehes upon vapor pressure and constant-volume gas thermometry. The standard thermocouple, which in previous scales had a range between the upper end of the SPRT range and the lower end of the radiation thermometer range, has been deleted. [Pg.399]

Called the Seebeck coefficient. It is given here at the high-temperature end of the range many thermocouples are nonlinear. [Pg.402]

TABLE 8-7 Recommended Temperature Measurement Ranges for RTDs and Thermocouples... [Pg.759]

Total Radiation Pyrometers In total radiation pyrometers, the thermal radiation is detec ted over a large range of wavelengths from the objec t at high temperature. The detector is normally a thermopile, which is built by connec ting several thermocouples in series to increase the temperature measurement range. The pyrometer is calibrated for black bodies, so the indicated temperature Tp should be converted for non-black body temperature. [Pg.761]

Thermocouples are unsurpassed for making temperature-difference measurements. The thermoelectric power of thermocouple materials makes them adequate for use at hquid-air temperatures and above. At 20 K and below, the thermoelectric power drops to a few lV/K, and their use in this range is as much art as science. [Pg.1136]

Verifying temperature is the second most important aspect of any compressor operation. As with pressure, the basic form of measurement is a simple temperature gauge. The construction of the gauges is quite varied, ranging from a bimetallic device to the filled systems. When transmis sion is involved, the sensor becomes quite simple, taking the form v)l a thermocouple or a resistance temperature detector (RTD). The monitor does the translation from the native signal to a temperature readout ()r signal proportional to temperature. [Pg.343]

Figure 25.9. Typical exotherm curves for polyester resin cured with 1% benzoyl peroxide over a range of bath temperatures. (Test tubes of 19 mm dia are filled to height of 8 cm with a mixture of resin plus peroxide. The tubes are immersed in a glycerin bath to the level of the resin surface. Temperature is measured with a thermocouple needle whose point is half-way down the resin... Figure 25.9. Typical exotherm curves for polyester resin cured with 1% benzoyl peroxide over a range of bath temperatures. (Test tubes of 19 mm dia are filled to height of 8 cm with a mixture of resin plus peroxide. The tubes are immersed in a glycerin bath to the level of the resin surface. Temperature is measured with a thermocouple needle whose point is half-way down the resin...
The measurement ranges for the base-metal thermocouples are 0 to +750 °C (type J), -200 to +1200 °C (type K), and -200 to +350 °C (type T). The noble-metal thermocouples can be used at higher temperatures up to 1700 °C. The dynamic response of sheathed thermocouples is not very fast however, a probe made from bare, thin wires can have very fast dynamic properties. One of the best features of thermocouples is the simplicity of making new probes by soldering or welding the ends of two wires together. [Pg.1138]

The commercial units have a very low thermal capacity and very high response speeds. Some are available with several independent channels and a common cold junction. Each channel is scanned in turn by the instrument, and the readings either displayed or stored for future recovery. Accuracies of better than 0.2 per cent are possible. Thermocouples are available to cover a very wide range of temperatures, their cost is low and they have a small mass, so minimizing the intrusive effect on the surface at the point where the temperature is being measured. The output characteristics (output voltage versus temperature) are reasonably linear but the measurement accuracy is not particularly high. [Pg.243]

Kinetic measurements were made with a glass tubular one-pass fixed bed reactor. The internal diameter of the reactor was 9-12 mm, and the thermocouple well of external diameter 5-6 mm reached into the catalyst bed. The amount of the catalyst varied within the range of 0.01 to 1 g for pseudodifferential measurements (depending upon the activity of the catalyst... [Pg.25]

The ITS-90 scale is designed to give temperatures T90 that do not differ from the Kelvin Thermodynamic Scale by more than the uncertainties associated with the measurement of the fixed points on the date of adoption of ITS-90 (January 1, 1990), to extend the low-temperature range previously covered by EPT-76, and to replace the high-temperature thermocouple measurements of IPTS-68 with platinum resistance thermometry. The result is a scale that has better agreement with thermodynamic temperatures, and much better continuity, reproducibility, and accuracy than all previous international scales. [Pg.618]

Finally, the recording of many signals from the output of the analytic and electrochemical instrumentation requires a reliable multi-pen recorder or an equivalent recording system based on a data acquisition card and appropriate software. The recorded signals are normally in the range of a few mV to 10V. The use of reliable temperature controllers and thermocouples is also crucial for the success of the experiments. A lot of suppliers of such equipment can be easily found and will not be reported here. [Pg.550]

The central transport chamber is an 80-cm-diameter stainless steel vessel, and is pumped by a 1000-1/s turbomolecular pump, which is backed by a small (501/s) turbomolecular pump to increase the compression ratio for hydrogen, and by a 16-m /h rotating-vane pump. UHV is obtained after a bake-out at temperatures above 100°C (measured with thermocouples at the outside surface) of the whole system for about a week. A pressure in the low 10 " -mbar range is then obtained. With a residual gas analyzer (quadrupole mass spectrometer, QMS) the partial pressures of various gases can be measured. During use of the system, the pressure in the central chamber is in the low 10 -mbar range due to loading of samples. Water vapor then is the most abundant species in the chamber. [Pg.22]


See other pages where Thermocouples range is mentioned: [Pg.1216]    [Pg.376]    [Pg.384]    [Pg.193]    [Pg.174]    [Pg.174]    [Pg.66]    [Pg.402]    [Pg.759]    [Pg.776]    [Pg.885]    [Pg.886]    [Pg.659]    [Pg.216]    [Pg.1162]    [Pg.162]    [Pg.1039]    [Pg.934]    [Pg.73]    [Pg.238]    [Pg.28]    [Pg.29]    [Pg.155]    [Pg.278]    [Pg.491]    [Pg.802]    [Pg.360]    [Pg.438]    [Pg.278]    [Pg.381]    [Pg.24]    [Pg.312]    [Pg.227]    [Pg.329]   