Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Local cathodic protection

The danger of corrosion is in general greater for pipelines in industrial installations than in long-distance pipelines because in most cases cell formation occurs with steel-reinforced concrete foundations (see Section 4.3). This danger of corrosion can be overcome by local cathodic protection in areas of distinct industrial installations. The method resembles that of local cathodic protection [1], The protected area is not limited, i.e., the pipelines are not electrically isolated from continuing and branching pipelines. [Pg.309]


Deep anodes are installed where the resistivity is high in the upper layers of soil and decreases with increasing depth. This type of installation is recommended for densely populated areas and for local cathodic protection (see Chapter 12) on account of the small space needed and the smaller voltage cone, which avoids interference with foreign structures. [Pg.250]

Protection currents of a few amperes are needed for the cathodic protection of assemblies of storage tanks or refuelling stations. In this case, electrical contact with grounded installations is the main problem. For cathodic protection, these contacts must be located and electrically separated. If this is not possible, then local cathodic protection should be installed (see Chapter 12). [Pg.294]

Only local cathodic protection can be used for large installations and old installations with electrical contact to components with low grounding resistances that cannot be isolated (see Section 12.6). The measures necessary for tank installations are described in Ref. 10. [Pg.300]

Fig. 11-4 Local cathodic protection of a tank farm with impressed current. Fig. 11-4 Local cathodic protection of a tank farm with impressed current.
With local cathodic protection, the off potential measurement cannot be used directly to check the protective action because, due to the mixed type of installation of the protected object and foreign cathodic structures in the soil, there is a considerable flow of cell currents and equalizing currents. The notes to Eq. (3-28) in Section 3.3 are relevant here, where the // -free potentials must be substantially more negative than the off potential of the protected object. If t/ ff is found to be more positive than U, this does not confirm or conclusively indicate insufficient... [Pg.311]

Figure 12-2 shows as an example the arrangement of the anode installation for the local cathodic protection of pipelines in a power station. The cooling water pipelines have a nominal diameter of DN 2000 and 2500 and a covering of earth up to 6 m. The fire-fighting pipelines have a nominal diameter of DN 100 and a covering of 1 m. All the pipelines have a bitumen coating. [Pg.312]

Fig. 12-2 Local cathodic protection in a power station. deep anodes O horizontal anodes Potential readings Ccu-cuso4 volts (A) free corrosion potential before commissioning the cathodic protection (B) 4 months after switching on... Fig. 12-2 Local cathodic protection in a power station. deep anodes O horizontal anodes Potential readings Ccu-cuso4 volts (A) free corrosion potential before commissioning the cathodic protection (B) 4 months after switching on...
Pumping or compressor stations are necessary for the transport of material in pipelines. These stations are usually electrically separated from the cathodically protected long-distance pipeline. The concrete foundations are much smaller than in power stations and refineries. Since the station piping is endangered by cell formation with the steel-reinforced concrete foundations, local cathodic protection is recommended. [Pg.317]

Structures or pits for water lines are mostly of steel-reinforced concrete. At the wall entrance, contact can easily arise between the pipeline and the reinforcement. In the immediate vicinity of the pit, insufficient lowering of the potential occurs despite the cathodic protection of the pipeline. Figure 12-7 shows that voltage cones caused by equalizing currents are present up to a few meters from the shaft. With protection current densities of 5 mA mr for the concrete surfaces, even for a small pit of 150 m surface area, 0.75 A is necessary. A larger distribution pit of 500 m requires 2.5 A. Such large protection currents can only be obtained with additional impressed current anodes which are installed in the immediate vicinity of the pipe entry into the concrete. The local cathodic protection is a necessary completion of the conventional protection of the pipeline, which would otherwise be lacking in the pit. [Pg.317]

Fig. 12-6 Local cathodic protection of a tank farm in high-resistance soil using the anodic voltage cones of distributed anodes the lines indicate soil potential values for an increase of 0.5 V relative to a remote ground numerical pairs volts. Fig. 12-6 Local cathodic protection of a tank farm in high-resistance soil using the anodic voltage cones of distributed anodes the lines indicate soil potential values for an increase of 0.5 V relative to a remote ground numerical pairs volts.
In the local cathodic protection of the bottoms of flat-bottomed tanks, cell formation with steel-concrete foundations is of little importance since the surfaces are relatively small, in contrast to the installations in Sections 12.2 to 12.5. On the other hand, connected components of the installation, such as cables and grounds, take up considerable protection current. On account of the large foundations of flat-bottomed tanks, which are often bare or only poorly coated, polarization to the protection potential is only possible with very negative on potentials. In tank foundations with the... [Pg.319]

Table 12-2 Parameters of storage tanks with local cathodic protection... Table 12-2 Parameters of storage tanks with local cathodic protection...
Determination of tank/soil potentials is only possible at the outer edge of the tank. For monitoring the local cathodic protection, the distance between test points should not exceed 2 m [3]. The measurement of the tank/soil potential by the current... [Pg.321]

Cathodic protection with impressed current anodes is used predominantly with cables or steel casing in which the cable is inserted, outside built-up areas where it is possible to build large anode installations without damaging interference with other lines. In densely populated areas, protection with impressed current anodes is often only possible with deep anodes, with surface anodes or locally at individual problem points (local cathodic protection, see Chapter 12). [Pg.329]

After a sufficient polarization period, which for the well casing is about a year, for flow lines with a high protection current requirement about half a year, and for flow lines with good coating about a month, the cathodic protection for the flow lines can be verified as in Section 10.4. If the cathodic protection is set up as local cathodic protection, checking is only necessary after a year. [Pg.425]

If AU and AU have the same sign, is more positive than U. This arises when the measuring point has a more positive potential than the surroundings. This means that regions with a relatively positive pipe/soil potential have a still more positive potential than the measured U ff value If AUob and have different signs, then U,g.f is more negative than U. This occurs, for example, with local cathodic protection when there are foreign cathodic structures (see Chapter 12). [Pg.96]


See other pages where Local cathodic protection is mentioned: [Pg.19]    [Pg.96]    [Pg.150]    [Pg.273]    [Pg.273]    [Pg.309]    [Pg.310]    [Pg.310]    [Pg.311]    [Pg.312]    [Pg.313]    [Pg.317]    [Pg.317]    [Pg.319]    [Pg.320]    [Pg.321]    [Pg.336]    [Pg.422]    [Pg.572]    [Pg.572]    [Pg.19]    [Pg.150]    [Pg.273]    [Pg.273]   


SEARCH



Cathodic protection

Cathodically protective

Deep anodes local cathodic protection

Local cathodic corrosion protection

Local cathodic protection power stations

Local cathodic protection tank farms

Local cathodic protection well casings

Special Features of the Local Cathodic Protection

© 2024 chempedia.info