Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Flow rate control system

Sample analysis was performed by using an Applied Biosystems (Foster City, CA) API 3000 triple quadrupole mass spectrometer equipped with a TurboIonSpray source and an Agilent 1100 capillary HPLC system (Palo Alto, CA). The capillary HPLC system included a binary capillary pump with an active micro flow rate control system, an online degasser, and a microplate autosampler. The analytical column was a 300 pm I.D.x 150 mm Zorbax C18 Stablebond capillary column (pore size 100 A and particle size 3.5 pm). The injection volume was 5 pL, and a needle ejection rate of 40 pL/min was used. The pLC flow rate was 6 pL/min. In order to minimize dead volume before the column, the autosampler was programmed to bypass the 8 pL sample loop 1.5 min after injection. The mobile phase consisted of (A) 2 mM ammonium acetate (adjusted to pH 3.2 with formic acid) in 10 90 acetonitrile-water, and (B) 2 mM ammonium acetate in 90 10 acetonitrile-water. The percentage of mobile phase B was held at 32 % for the first minute, increased to 80 % over 8 min, and then increased tol00% over the following 1 min. [Pg.85]

Feeding flow rate control system based on glucose concentration measured in real time (adapted from Ozturk et a ., 1997). [Pg.268]

Your coworker who is competing for a forthcoming promotion has proposed to install a conventional flow rate control system consisting of an orifice meter, differential-pressure transducer, controller, and control valve in a line between the compressed-air main and the vessel. Have you a suggestion that is likely to win you the promotion ... [Pg.326]

SCB to Zone 1 flow rate control systems (Controls the flow of SCB exhaust to the Zone 1 exhaust line. Two manually operated dampers control flow rate and residence time through the two SCB charcoal filters for... [Pg.450]

Establish the rado of the naximurn anticipated flow rate for system, Qjj, to the design basis rate, Q,d or Q,m/Q.d-When Qv] is not known, nor can it be anticipated, use Qm/Qd of 1.1 for flow control and 1.25 for level pressure and temperature control valves to anticipate the flow rate transients as the control loop recovers from a disturbance [9]. [Pg.93]

Connell recommends that a control valve be used that lakes a 76 psi pressure drop at design flow rate. The system should be able to increase flow to 120 percent of design. [Pg.252]

Control of the field occurs on two levels. The upper level Is the supervisory control and data acquisition (SCADA) system whose main responsibility is well flow rate control, well testing, production allocation, accounting and general field monitoring. The SCADA system is operated from the Main Operations Center (MOC) which is remote from all three GCs. The second level of control is process control in the individual GCs. Flow to the GCs Is normally controlled by the SCADA system (HOC operator), but the GC operator can override and control well flow rates in case of SCADA system failure or other unusual circumstances. The GC operator and the MOC operator communicate via a dedicated telephone connection. [Pg.56]

Figure 15.23. Hypersorber continuous moving bed gas phase adsorption system (See Mantell, Adsorption, McGraw-Hill, New York, 1951). (a) Schematic pattern of flows of gas and solid adsorbent (Hengstebeck, Petroleum Processing, McGraw-Hill, New York, 1959). (b) Solids flow rate control mechanism, (c) Typical separation performance. Figure 15.23. Hypersorber continuous moving bed gas phase adsorption system (See Mantell, Adsorption, McGraw-Hill, New York, 1951). (a) Schematic pattern of flows of gas and solid adsorbent (Hengstebeck, Petroleum Processing, McGraw-Hill, New York, 1959). (b) Solids flow rate control mechanism, (c) Typical separation performance.
Establishing a constant system pressure in a closed system or in a flow system with substrate materials in the reactor is not as simple and straightforward as it might appear. A gas is generally fed into the system by a constant flow rate controlled by... [Pg.255]

The continuous operation of LCVD could be controlled, in principle, by the strict controls of the flow rate, the system pressure, and the discharge power. The addition of a residual gas analyzer in each pumping system is advantageous in detecting abnormality in gas flow, occurrence of leakage, etc. The addition of more sophisticated diagnostic devices, such as an optical emission spectrometer, in-line XPS, etc., is often counterproductive because the stability of performance and the maintenance requirement cycle of these devices do not match those for the continuous mode operation of LCVD. The information obtainable by these devices... [Pg.258]

Gases are metered Into the system by means of a flow rate controller mechanism which Is able to maintain constant flow rates In the range 0-15 cm3 mln l measured at STP. [Pg.199]

Figure 10. Hamster breathing loop for analysis of exhaled Ng The system consists of (a) compressed gas (80/20 He/Oi) and appropriate flow regulators (b) fine flow rate control value (c) rotometer (d) T-joint with gas tight fitting for attaching hamster endotracheal tube (e) heating pallet for hamster (f) chromatograph sampling valve (g) water ana CO absorbent bed (h) chromatograph column (i) thermal conductivity detector. Figure 10. Hamster breathing loop for analysis of exhaled Ng The system consists of (a) compressed gas (80/20 He/Oi) and appropriate flow regulators (b) fine flow rate control value (c) rotometer (d) T-joint with gas tight fitting for attaching hamster endotracheal tube (e) heating pallet for hamster (f) chromatograph sampling valve (g) water ana CO absorbent bed (h) chromatograph column (i) thermal conductivity detector.
For the selection of the appropriate control system a dynamic analysis is needed that can inform the designer about the type of controllers really needed. Some general recommendations follow. In cases when the expected disturbances are strong and the control time permitted is long enough, proportional (P) controller can be used. PI controllers can be applied with > 6. PID controllers are recommended in the range of 4 t, < t < 6. For flow rate control and for level control P and PI controllers are used for tanpera-ture control, P, PI, and PID controllers are mostly applied. [Pg.341]

This structure was tested and gave unexpected results. Figure 8.53a shows what happens when all controllers are on automatic and no disturbance is introduced. Everything runs along for about 20 h, but then a small decrease in Stage 3 temperature occurs. This increases the reboiler heat input, which increases the reflux-drum level. This increases the reflux and distillate flow rates. The temperature then undergoes a large increase, which produces an extreme drop in reboiler heat input and cuts reflux and distillate flow rates. The system shuts down after about 30 h. [Pg.251]

The injection process introduces the prepared sample or reagent into the flowing carrier stream within the manifold. Ideally, the injector system should be designed so as to provide a high sample flow rate. Injection systems typically employ electrokinetic mobility or hydrodynamic pressure techniques. In the former systems, the sample flow into the microchannel is controlled by the application of an external electric field to the reservoir, while in the latter systems, a pressure difference is created in the reservoir using either a positive pressure (pistmi-type) technique or a suction pressure (vacuum) technique. [Pg.2016]

To exclude effect of the changing properties of the columns and also to rule out the inadequacies in the pump operation, the SEC systems are to be frequently recalibrated and the eluent flow rate controlled after each restarting the pump. The latter requirement may be imperative with the low-cost pumping systems, which often exhibit hmited resetabilify. It is generally appropriate to perform the... [Pg.299]

Ageing effects may be detected by a change in measurable parameters. For example, increase in temperature or pressure may be an indication of die accumulation of corrosion products in the tube of a heat-exchanger and instrument drift may be an indication of electronic component degradation. Parameters should be measured periodically in a consistent manner and the readings should be compared and assessed. Physical parameters, such as temperature, pressure, flow rate, control rod drop times, radiation level (e.g. neutron and gamma), water quality, are indicators of the state of a system, structure or component. [Pg.21]


See other pages where Flow rate control system is mentioned: [Pg.391]    [Pg.618]    [Pg.545]    [Pg.546]    [Pg.391]    [Pg.618]    [Pg.545]    [Pg.546]    [Pg.84]    [Pg.85]    [Pg.797]    [Pg.113]    [Pg.85]    [Pg.441]    [Pg.243]    [Pg.436]    [Pg.432]    [Pg.369]    [Pg.64]    [Pg.17]    [Pg.171]    [Pg.186]    [Pg.1158]    [Pg.694]    [Pg.130]    [Pg.2978]    [Pg.1885]    [Pg.240]    [Pg.1108]   
See also in sourсe #XX -- [ Pg.389 ]




SEARCH



Flow control

Flow controllers

Flow rate system

Flow system

Flowing systems 83

Rate control

Rate controlling

Rating System

© 2024 chempedia.info