Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Condenser mean temperature difference

Countercurrent or Cocurrent Flow If the flow of the streams is either completely countercurrent or completely cocurrent or if one or both streams are isothermal (condensing or vaporizing a pure component with negligible pressure change), the correct MTD is the logarithmic-mean temperature difference (LMTD), defined as... [Pg.1034]

AP,rav = Tray pressure drop, inches of liquid ATi = Condensing side temperature difference, °F ATn, = Log mean temperature difference, °F Pf = Foam density, Ibs/ft ... [Pg.307]

For condensing problems, determine whether apparent weighted mean temperature difference is used, and which is applicable. [Pg.263]

The pressure drop of condensing steam is therefore a function of steam flow rate, pressure and temperature difference. Since the steam pressure drop affects the saturation temperature of the steam, the mean temperature difference, in turn, becomes a function of steam pressure drop. This is particularly important when vacuum steam is being used, since small changes in steam pressure can give significant alterations in the temperature at which the steam condenses. [Pg.398]

A pure, saturated, vapour will condense at a fixed temperature, at constant pressure. For an isothermal process such as this, the simple logarithmic mean temperature difference can be used in the equation 12.1 no correction factor for multiple passes is needed. The logarithmic mean temperature difference will be given by ... [Pg.717]

If the degree of superheat is large, it will be necessary to divide the temperature profile into sections and determine the mean temperature difference and heat-transfer coefficient separately for each section. If the tube wall temperature is below the dew point of the vapour, liquid will condense directly from the vapour on to the tubes. In these circumstances it has been found that the heat-transfer coefficient in the superheating section is close to the value for condensation and can be taken as the same. So, where the amount of superheating is not too excessive, say less than 25 per cent of the latent heat load, and the outlet coolant temperature is well below the vapour dew point, the sensible heat load for desuperheating can be lumped with the latent heat load. The total heat-transfer area required can then be calculated using a mean temperature difference based on the saturation temperature (not the superheat temperature) and the estimated condensate film heat-transfer coefficient. [Pg.718]

It is normal practice to assume that integral condensation occurs. The conditions for integral condensation will be approached if condensation is carried out in one pass, so that the liquid and vapour follow the same path as in a vertical condenser with condensation inside or outside the tubes. In a horizontal shell-side condenser the condensate will tend to separate from the vapour. The mean temperature difference will be lower for differential condensation, and arrangements where liquid separation is likely to occur should generally be avoided for the condensation of mixed vapours. [Pg.721]

Where integral condensation can be considered to occur, the use of a corrected logarithmic mean temperature difference based on the terminal temperatures will generally give a conservative (safe) estimate of the mean temperature difference, and can be used in preliminary design calculations. [Pg.721]

Mean temperature difference the condensation range is small and the change in saturation temperature will be linear, so the corrected logarithmic mean temperature... [Pg.724]

When the fluid being vaporised is a single component and the heating medium is steam (or another condensing vapour), both shell and tubes side processes will be isothermal and the mean temperature difference will be simply the difference between the saturation temperatures. If one side is not isothermal the logarithmic mean temperature difference should be used. If the temperature varies on both sides, the logarithmic temperature difference must be corrected for departures from true cross- or counter-current flow (see Section 12.6). [Pg.752]

Mean temperature difference in the main heat exchangers, melter and condenser 5° F. [Pg.17]

Where Q = Heat-Transfer Rate Fs = Steam Mass Flow AHs = Latent Heat of Vaporization F = Feed Rate Cp = Heat Capacity of Feed T0 = Steam Supply Temperature Pt = Steam Supply Pressure P2 = Steam Valve Outlet Pressure Ps = Condensing Pressure Tj = Inlet Temperature T2 = Outlet Temperature A Tm = Log Mean Temperature Difference Ts = Condensing Steam Temperature... [Pg.280]

In a condenser, the rate of heat flow (Q) is proportional to the condenser area (A), the mean temperature difference (A7"m) between the coolant and vapour streams and the overall coefficient of heat transfer ( ) ... [Pg.187]

In practice, condenser temperatures are as shown in Figure 6.1(b) (both vapour and coolant temperatures change) and in the equation for (0, the log mean temperature difference should be used for A Tm. [Pg.188]

At, = log-mean temperature-difference driving force over condenser, °F Hy = hours the condenser is operated per year, h/year Cw = cooling-water cost assumed as directly proportional to amount of water supplied, /lb... [Pg.368]

The methods presented above are applicable only for conditions in which the heat transferred is a straight-line function of temperature. For systems that do not meet this condition, the total heat-release curve can be treated in sections, each section of which closely approximates the straight-line requirement. A log mean temperature difference can then be calculated for each section. Common examples in which this approach is encountered include (1) total condensers in which the condensate is subcooled after condensation, and (2) vaporizers in which the fluid enters as a subcooled liquid, the liquid is heated to the saturation temperature, the fluid is vaporized, and the vapor is heated and leaves in a superheated state. [Pg.286]

To calculate the logarithmic-meaii temperature difference, the terminal temperatures of the condenser must be fixed. Because the condensation is essentially isobaric, the inlet and outlet ten eratures of the ammonia stream are 41.4°C (106.5 °F). From Table 4.1, the inlet cooling-water temperature is 30°C (86.0 °F) if cooling-tower water is used. Also, for thermodynamic considerations the exit water temperature must be less than 41.4°C, and it is calculated from Equation 4.7.6. If the lower value of the approach tenqjerature difference of 5 C (9.0 °F) is selected from Table 4.4, a low cooling-water flow rate will be needed. Thus, exit water temperature is 36.4°C. Therefore, from Equation 4.7.5, the logarithmic-mean temperature difference,... [Pg.193]

But, when there is a phase change involved in the process — for example, condensation (Fig. lb), or vaporization (Fig. Ic), or both (Fig. Id), LMTD cannot be used directly. In this case, the designer must break the exchanger into two or more zones, and analyze each section separately. The resultant AT is called the weighted mean-temperature-difference (WMTD), and is expressed as ... [Pg.45]

Weighted mean-temperature-difference for exchangers with phase changes Conserving steam Operating boilers intermittently Find the most compact surface condenser Does your surface condenser have spare capacity ... [Pg.134]

This s a little less than the arithmetic mean temperature difference of j(8 + 16) = 12°C. Then the heat transfer rate in Ihe condenser is determined from... [Pg.643]


See other pages where Condenser mean temperature difference is mentioned: [Pg.244]    [Pg.1041]    [Pg.1115]    [Pg.1414]    [Pg.695]    [Pg.696]    [Pg.481]    [Pg.339]    [Pg.62]    [Pg.196]    [Pg.307]    [Pg.339]    [Pg.864]    [Pg.938]    [Pg.1237]    [Pg.182]    [Pg.44]    [Pg.518]    [Pg.244]   


SEARCH



Condensation mean temperature difference

Condensation mean temperature difference

Mean temperature difference

Mean temperature difference in condensation

Mean temperature difference in condensers

Temperature condensation

Temperature, meaning

© 2024 chempedia.info