Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Steam pressure drop

These systems, commercially known as Tberminol VP or Dowtherm A, differ from steam in some key areas which can result in operating problems unless handled properly in design (14). The low pressure—high temperature operation means that the AT/AP ratio at saturation is quite high for example, at 315°C the ratio is 25 times that of steam. This means that a pressure drop that would be nominal in a steam system (10 kPa (0.1 atm)), can not be tolerated if precise temperature control is needed. [Pg.229]

Table 6 shows the effect of varying coil oudet pressure and steam-to-oil ratio for a typical naphtha feed on the product distribution. Although in these tables, the severity is defined as maximum, in a reaUstic sense they are not maximum. It is theoretically possible that one can further increase the severity and thus increase the ethylene yield. Based on experience, however, increasing the severity above these practical values produces significantly more fuel oil and methane with a severe reduction in propylene yield. The mn length of the heater is also significantly reduced. Therefore, this is an arbitrary maximum, and if economic conditions justify, one can operate the commercial coils above the so-called maximum severity. However, after a certain severity level, the ethylene yield drops further, and it is not advisable to operate near or beyond this point because of extremely severe coking. [Pg.437]

Cavitation Loosely regarded as related to water hammer and hydrauhc transients because it may cause similar vibration and equipment damage, cavitation is the phenomenon of collapse of vapor bubbles in flowing liquid. These bubbles may be formed anywhere the local liquid pressure drops below the vapor pressure, or they may be injected into the hquid, as when steam is sparged into water. Local low-pressure zones may be produced by local velocity increases (in accordance with the Bernouhi equation see the preceding Conservation Equations subsection) as in eddies or vortices, or near bound-aiy contours by rapid vibration of a boundaiy by separation of liquid during water hammer or by an overaU reduction in static pressure, as due to pressure drop in the suction line of a pump. [Pg.670]

An equation for use with venturi meters was given by Chisholm [Br Chem. Eng., 12, 454—457 (1967)]. A procedure for determining steam quahty via pressure-drop measurement with upflow through either venturi meters or sharp-edged orifice plates was given By Colhus and Gacesa [J. Basic Eng., 93, 11-21 (1971)]. [Pg.898]

Steam pressure. The main boosters can operate on steam pressures from as low as 0,15 bar up to 7 bar gauge. The quantity of steam required increases rapidly as the steam pressure drops (Fig, 11-106), The best steam rates are obtained with about 7 bar. Above this pressure the change in quantity of steam required is prac tically negligible. Ejectors must be designed for the highest available steam pressure, to take advantage of the lower steam consumption for various steam-inlet pressures. [Pg.1122]

The two principal elements of evaporator control are evaporation rate a.ndproduct concentration. Evaporation rate in single- and multiple-effect evaporators is usually achieved by steam-flow control. Conventional-control instrumentation is used (see Sec. 22), with the added precaution that pressure drop across meter and control valve, which reduces temperature difference available for heat transfer, not be excessive when maximum capacity is desired. Capacity control of thermocompression evaporators depends on the type of compressor positive-displacement compressors can utilize speed control or variations in operating pressure level. Centrifugal machines normally utihze adjustable inlet-guide vanes. Steam jets may have an adjustable spindle in the high-pressure orifice or be arranged as multiple jets that can individually be cut out of the system. [Pg.1148]

Sizing Steam Piping in New Plants Maximum Allowable Flow and Pressure Drop... [Pg.5]

G = Gas specific gravity = mol. wt./29 Pi = Valve inlet pressure, psia AP = Pressure drop across valve, psi Q = Gas flow rate, SCFH Qs = Steam or vapor flow rate, Ib/hr T = Absolute temperature of gas at inlet, °R T5I1 = Degrees of superheat, °F... [Pg.15]

The theoretical steam rate (sometimes referred to as the water rate) for stream turbines can be determined from Keenan and Keyes or Mollier charts following a constant entropy path. The theoretical steam rate is given as Ib/hr/kw which is easily converted to Ib/hr/hp. One word of caution—in using Keenan and Keyes, steam pressures are given in PSIG. Sea level is the basis. For low steam pressures at high altitudes appropriate coirections must be made. See the section on Pressure Drop Air-Cooled Air Side Heat Exchangers, in this handbook, for the equation to correct atmospheric pressure for altitude. [Pg.126]

In biphase systems velocity of the steam is often 10 times the velocity of the liquid. If condensate waves rise and fill a pipe, a seal is formed with the pressure of the steam behind it (Fig. 2). Since the steam cannot flow through the condensate seal, pressure drops on the downstream side. The condensate seal now becomes a piston accelerated downstream by this pressure differential. As it is driven downstream it picks up more liquid, which adds to the existing mass of the slug, and the velocity increases. [Pg.314]

It is also important to note that the lowest design pressure of any section of the casing must be specified to be no lower than the pressure which it may be subjected to under the PR valve relieving conditions. This is necessary to recognize pressure drop within the casing. The PR valve should be sized to pass the normal steam flow to the turbine, but credit may be taken for steam flow which is withdrawn from an intermediate turbine stage if it would not be blocked by the same contingency as closure of the exhaust. [Pg.142]

Flare stack sizing and pressure drop is included with considerations of pressure drop through the safety valve headers, blowdown drums, flare headers, seal drum, etc. Elevated flare tips incorporating various steam injection nozzle configurations are normally sized for a velocity of 120 m/s at maximum flow, as limited by excessive noise and the ability of manufacturers to design tips which will insure flame stability. This velocity is based on the inclusion of steam flow if injected internally, but the steam is not included if added through jets external to the main tip. [Pg.250]

Metering flare gas is important for loss accounting and for control of steam injection. A special requirement for flare gas meters is low pressure drop and the ability to continue functioning in fouling conditions. The flare gas metering methods listed below have been used with varying degrees of success. [Pg.280]


See other pages where Steam pressure drop is mentioned: [Pg.207]    [Pg.326]    [Pg.207]    [Pg.326]    [Pg.352]    [Pg.8]    [Pg.94]    [Pg.94]    [Pg.482]    [Pg.189]    [Pg.306]    [Pg.479]    [Pg.418]    [Pg.236]    [Pg.175]    [Pg.223]    [Pg.227]    [Pg.230]    [Pg.477]    [Pg.478]    [Pg.653]    [Pg.1054]    [Pg.1097]    [Pg.2501]    [Pg.2502]    [Pg.64]    [Pg.553]    [Pg.227]    [Pg.291]    [Pg.42]    [Pg.96]    [Pg.283]    [Pg.213]    [Pg.424]    [Pg.709]    [Pg.9]    [Pg.1085]    [Pg.1183]    [Pg.119]    [Pg.135]   
See also in sourсe #XX -- [ Pg.103 ]




SEARCH



Pressurized steam

Steam Reformers Pressure Drop

Steam pressure drop Chart

© 2024 chempedia.info