Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Area separation walls

Division of an existing structure into separate buildings (if required to comply with the maximum allowable area limitations) may be accomplished by die construction of area separation walls (UBC Section 504.6). (See Fig. 2.)... [Pg.441]

Figure 2. Division of a building into three buildings with the construction of area separation walls as required by UBC 504.6. Also note fire resistive occupancy separation walls. Figure 2. Division of a building into three buildings with the construction of area separation walls as required by UBC 504.6. Also note fire resistive occupancy separation walls.
Smoke dampers, or combination smoke/fire dampers, must be provided at all penetrations of ducts through a smoke partition. Fire dampers shall not be installed in exhaust ducts. Exhaust ducts shall not penetrate area separation walls (UFC 5104.3.2.3). [Pg.450]

Smoke door holders are required on doors through area separation walls (two-hour rating), building separation walls (four-hour rating) and other walls which are required to be smoke partitions. [Pg.460]

Building areas separated by physical walls (e.g., halls, rooms, booths) located on the same level. The wall has either intentional apertures or leaks (Fig. 7.107c2). [Pg.591]

Building areas separated by physical walls located on different levels (floors). Air movement between these zones may occur (e.g., through stairways or ducts) (Fig. 7.107/ ). [Pg.591]

Adequate fire protection must be provided by separation, walls, and/or sprinkler control (NFPA 43B) in order to prevent damage to the surrounding areas in case of a decomposition or fire. [Pg.156]

In the membrane reactor a wall of area separates the phases, and this area is generally fixed by the geometry of the reactor using planar or cylindrical membranes. However, most multiphase reactors do not have fixed boundaries separating phases, but rather allow the boundary between phases to be the interfacial area between insoluble phases. This is commonly a variable-area boundary whose area wiU depend on flow conditions of the phases, as shown in Figure 12-7. [Pg.488]

Fire-explosion risks separated from ignition hazards, other such risk areas-fire walls, curbs, dikes, barriers, etc. [Pg.74]

The Aj is the area of the inner surface of the watt that separates the two fluids, and A is the area of the outer surface of the wall. In other words, A, and A are surface areas of the separating wall wetted by the inner and the outer fluids, respectively. When one fluid flows inside a circular lube and the other outside of it, we have A, - 7rD,L and A = (Fig. 11-8). [Pg.629]

Horizontal exits shall be as specified in UBC 1008. A horizontal exit is an exit from one building into another building or through or aroxmd a wall constructed as required for a two-hour area separation. [Pg.442]

Immediately after the gate area, the wall thickness should not increase rapidly because it would lead to the occurrence of flow separations and air inclusions. [Pg.113]

Fig. 4 Flex Ring feed block consisting of 15 separate walls at the joining area where the radial flow channel gap can be fine tuned with the help of the adjusting screws which are positioned around the circumference of the feed block. [Pg.838]

The table convincingly demonstrates how the unsuspected presence of micropores can lead to an erroneous value of the specific surface calculated from a Type II isotherm by application of the standard BET procedure. According to the foregoing analysis, the external specific surface of the solid is 114m g" the micropore volume (from the vertical separation of isotherms A and E) is 105 mm g but since the average pore width is not precisely known, the area of the micropore walls cannot be calculated. Thus the BET figure of 360m g calculated from isotherm E represents merely an apparent and not a true surface area. [Pg.214]

Figure 2.1 served as the basis for our initial analysis of viscosity, and we return to this representation now with the stipulation that the volume of fluid sandwiched between the two plates is a unit of volume. This unit is defined by a unit of contact area with the walls and a unit of separation between the two walls. Next we consider a shearing force acting on this cube of fluid to induce a unit velocity gradient. According to Eq. (2.6), the rate of energy dissipation per unit volume from viscous forces dW/dt is proportional to the square of the velocity gradient, with t]q (pure liquid, subscript 0) the factor of proportionality ... [Pg.587]

The areas for the reactors and storage tanks should be separated by fire walls, and must be adequately ventilated. Storage tanks should be blanketed by inert gas. A slight positive pressure of inert gas should be maintained in the reactor or storage tanks during the discharging of the resin or resin solution to prevent air from being sucked into the vessel to form an explosive mixture with the solvent vapor. [Pg.41]


See other pages where Area separation walls is mentioned: [Pg.693]    [Pg.475]    [Pg.554]    [Pg.270]    [Pg.245]    [Pg.399]    [Pg.268]    [Pg.156]    [Pg.296]    [Pg.24]    [Pg.119]    [Pg.203]    [Pg.141]    [Pg.354]    [Pg.25]    [Pg.354]    [Pg.454]    [Pg.58]    [Pg.318]    [Pg.187]    [Pg.24]    [Pg.253]    [Pg.397]    [Pg.305]    [Pg.484]    [Pg.149]    [Pg.154]    [Pg.316]    [Pg.381]    [Pg.72]    [Pg.88]    [Pg.327]    [Pg.49]   
See also in sourсe #XX -- [ Pg.441 ]




SEARCH



Wall area

© 2024 chempedia.info