Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Subcooling of condensate

Loss of volatile vapor out vent, apparent undersized area for condensation of immiscible liquids lack of subcooling of condensate/condenser installed horizontally instead of vertically. [Pg.76]

Countercurrent flow is accomplished resulting in maximum possible subcooling of condensate. Noncondensable gases, which always exist in a condenser, are contacted with the lowest available temperature before removal. Vent losses are therefore at a minimum. [Pg.215]

Thermostatic traps are temperature-sensitive traps there are several basic types. They respond to either a temperature difference between the steam and the condensate or directly to a temperature of either steam or condensate. All thermostatic traps are operated and controlled by the temperature in the line upstream of the trap time Is necessary for the operating elements to either absorb heat to cause the valve to close or dissipate heat to cause the valve to open. They usually discharge condensate below the steam temperature and require a collecting leg before the trap to permit some subcooling of condensate. Therefore, sufficient piping length should be provided at the trap inlet to prevent the condensate backup from interfering with the heat transfer surface. [Pg.263]

Single-pass air-cooled condensers must usually be somewhat oversized resulting in subcooling of condensate. This results because the air temperature at each row of tubes is different consequently, each row condenses a different amount of vapor. In order to insure that all vapor entering the top row (highest air temperature) is condensed, it may be necessary to provide more area than required for all other rows. Multipass condensers avoid this problem, but pressure drop considerations do not always permit multipass designs. [Pg.310]

The overhead condenser on a distillation column is to subcool the condensed vapors from the condensation temperature of 46.4°F down to 35°F. The specific heat of the liquid is 0.3 Btu/lb (°F), and the latent heat of vaporization at 46.4°F is 265 Btu/lb. The vapor rate to the condenser is 740.3 Ib/hr. What is the total heat load on the condenser ... [Pg.74]

The total unit size is the sum of the area requirements for condensation plus subcooling of the liquid to the desired oudet temperature. For the subcooling portion ... [Pg.130]

The mean temperature of condensate film before subcooling ... [Pg.131]

A condenser is required to condense a flowrate of 7 kg-s-1 of isopropanol. The condensation takes place isothermally at 83°C without subcooling of the condensate. The cooling is provided by cooling water between 25 and 35°C. The condenser can be assumed to be steel with 20 mm tubes... [Pg.355]

Calculation of the power requirements for the three refrigerants requires the flowrate to be calculated for a duty of 3 MW. This can be calculated from the enthalpy difference across the evaporator (H2 — H1). The enthalpy difference across the evaporator is assumed to be the difference between the saturated vapor enthalpy at the evaporator pressure and the saturated liquid enthalpy at the condenser pressure. This assumes no subcooling of the refrigerant. [Pg.538]

The temperature driving force will be taken as the difference between the temperature of the condensing steam and that of the evaporating water as the preheating of the solution and subcooling of the condensate represent but a small proportion of the total heat load, that is AT = (394 - 325) = 69 degK. [Pg.194]

The vapor is drawn into a steam jet (discussed in Chap. 16). The steam condensate flows into the boot or hot well. The water in the boot is slightly subcooled. This is accomplished by a pair of baffles that create a small zone of condensate backup. The subcooled condensate, cooled to perhaps 10°F below its boiling or bubbling point, is easier to pump. As the pressure in the hot well is subatmospheric, the hot-well pump typically develops a AP of at least 30 to 50 psi. [Pg.103]

Effect of subcooling. When steam condenses at atmospheric pressure, it gives off 1000 Btu per pound of condensing steam. This is called the latent heat of condensation of steam. [Pg.148]

Effect of condensate backup. When the condensate level in an exchanger increases, the area of the condenser devoted to subcooling the condensate increases. But the area of the exchanger available for condensing decreases. That is bad ... [Pg.152]

As the hot-vapor bypass valve opens, the condensate level in the shell side of the condenser increases to produce cooler, subcooled liquid. This reduces the surface area of the condenser exposed to the saturated vapor. To condense this vapor, with a smaller heat-transfer area, the pressure of condensation must increase. This, in turn, raises the tower pressure. This then is how opening the hot bypass pressure-control valve increases the tower pressure. [Pg.158]

The increase in the vapor outlet temperature from a condenser, as compared to a decrease in the temperature of the condensate from the same condenser, is a sure sign of condensate backup. The condensate is covering some of the tubes in the surface condenser. This subcools the condensate and does no harm. [Pg.223]

Figure 3.10. Condensers, (a) Condenser on temperature control of the PF condensate. Throttling of the flow of the HTM may make it too hot. (b) Condenser on pressure control of the HTM flow. Throttling of the flow of the HTM may make it too hot. (c) Flow rate of condensate controlled by pressure of PF vapor. If the pressure rises, the condensate flow rate increases and the amount of unflooded surface increases, thereby increasing the rate of condensation and lowering the pressure to the correct value, (d) Condenser with vapor bypass to the accumulator drum. The condenser and drum become partially flooded with subcooled condensate. When the pressure falls, the vapor valve opens, and the vapor flows directly to the drum and heats up the liquid there. The resulting increase in vapor pressure forces some of the liquid back into the condenser so that the rate of condensation is decreased and the pressure consequently is restored to the preset value. With sufficient subcooling, a difference of 10-15 ft in levels of drum and condenser is sufficient for good control by this method. Figure 3.10. Condensers, (a) Condenser on temperature control of the PF condensate. Throttling of the flow of the HTM may make it too hot. (b) Condenser on pressure control of the HTM flow. Throttling of the flow of the HTM may make it too hot. (c) Flow rate of condensate controlled by pressure of PF vapor. If the pressure rises, the condensate flow rate increases and the amount of unflooded surface increases, thereby increasing the rate of condensation and lowering the pressure to the correct value, (d) Condenser with vapor bypass to the accumulator drum. The condenser and drum become partially flooded with subcooled condensate. When the pressure falls, the vapor valve opens, and the vapor flows directly to the drum and heats up the liquid there. The resulting increase in vapor pressure forces some of the liquid back into the condenser so that the rate of condensation is decreased and the pressure consequently is restored to the preset value. With sufficient subcooling, a difference of 10-15 ft in levels of drum and condenser is sufficient for good control by this method.
Condensation Outside Horizontal Tubes. Figure 8.14(d) shows a condenser with two tube passes and a shell side provided with vertically cut baffles that promote side to side flow of vapor. The tubes may be controlled partially flooded to ensure desired subcooling of the condensate or for control of upstream pressure by regulating the rate of condensation. Low-fin tubes often are advantageous, except when the surface tension of the condensates... [Pg.205]

Barolo et al. (1998) developed a mathematical model of a pilot-plant MVC column. The model was validated using experimental data on a highly non-ideal mixture (ethanol-water). The pilot plant and some of the operating constraints are described in Table 4.13. The column is equipped with a steam-heated thermosiphon reboiler, and a water-cooled total condenser (with subcooling of the condensate). Electropneumatic valves are installed in the process and steam lines. All flows are measured on a volumetric basis the steam flow measurement is pressure- and temperature-compensated, so that a mass flow measurement is available indirectly. Temperature measurements from several trays along the column are also available. The plant is interfaced to a personal computer, which performs data acquisition and logging, control routine calculation, and direct valve manipulation. [Pg.99]

The Jakob number is basically a measure of the importance of subcooling expressing, as it does, the change in the sensible heat per unit mass of condensed liquid in the film relative to the enthalpy associated with the phase change. The Jakob number is small for many problems, i.e the sensible heat change across the liquid film is small compared to the latent heat release. For example, for cases involving the condensation of steam, Ja, is typically of the order of 0.01. [Pg.565]

Vapor can condense on a cooled surface in two ways. Attention has mainly been given in this chapter to one of these modes of condensation, i.e.. to him condensation. The classical Nusselt-type analysis for film condensation with laminar film flow has been presented hnd the extension of this analysis to account for effects such as subcooling in the film and vapor shear stress at the outer edge of the film has been discussed. The conditions under which the flow in the film becomes turbulent have also been discussed. More advanced analysis of laminar film condensation based on the use of the boundary layer-type equations have been reviewed. [Pg.600]

A 30-cm high by 150-cm wide plate is maintained at 5°C and is inclined at 45° from the vertical. Calculate the rate of condensation, the heat transfer rate, and the maximum film thickness when the plate is exposed to stagnant saturated water vapor at 20°C. Do die calculation both with and without the effect of film subcooling. What is the value of the Jakob number for this problem ... [Pg.601]

The conditions of steam generation in the boiler are the same as in Example 8.1 8,600 kPa and 500°C. The exhaust pressure of the turbine, lOkPa, is also the same. The saturation temperature of the exhaust steam is therefore 45.83°C. Allowing for slight subcooling of the condensate, we fix the temperature of the liquid water from the condenser at 45°C. The feedwater pump, which operates under exactly the conditions of the pump in Example 7.10, causes a temperature rise of about 1°C, making the temperature of the feedwater entering the series of heaters equal to 46°C. [Pg.138]

The methods presented above are applicable only for conditions in which the heat transferred is a straight-line function of temperature. For systems that do not meet this condition, the total heat-release curve can be treated in sections, each section of which closely approximates the straight-line requirement. A log mean temperature difference can then be calculated for each section. Common examples in which this approach is encountered include (1) total condensers in which the condensate is subcooled after condensation, and (2) vaporizers in which the fluid enters as a subcooled liquid, the liquid is heated to the saturation temperature, the fluid is vaporized, and the vapor is heated and leaves in a superheated state. [Pg.286]

No good methods are available for calculating heat-transfer coefficients when appreciable subcooling of the condensate is required. A conservative approach is to calculate a superficial mass velocity assuming the condensate fills the entire tube and use the equations presented above for single-phase heat transfer inside tubes. This method is less conservative for higher condensate loads. [Pg.300]


See other pages where Subcooling of condensate is mentioned: [Pg.161]    [Pg.879]    [Pg.487]    [Pg.223]    [Pg.190]    [Pg.161]    [Pg.879]    [Pg.487]    [Pg.223]    [Pg.190]    [Pg.39]    [Pg.56]    [Pg.122]    [Pg.339]    [Pg.340]    [Pg.489]    [Pg.335]    [Pg.292]    [Pg.196]    [Pg.292]    [Pg.51]    [Pg.44]    [Pg.39]    [Pg.137]    [Pg.614]    [Pg.304]   
See also in sourсe #XX -- [ Pg.414 ]

See also in sourсe #XX -- [ Pg.24 ]




SEARCH



Condensate subcooling

Condensation subcooling

Condenser subcooling

Subcooled

Subcooling

© 2024 chempedia.info