Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Fault current Instantaneous

A CT is provided in series with the spark gap to sense its operation during a line fault. As soon as there is arcing, it provides an instantaneous command to a short-circuit relay. The relay, in turn, closes the bypass breaker, within 3 to 5 cycles, leaving only the natural line impedance in the faulty eircuit. Now = 0, which limits the fault current to the natural level of the system, as if the capacitors were not connected. The shorting device is restored to its original status as soon as the fault condition is cleared. The device must be capable of interrupting the line fault... [Pg.836]

It is a particular characteristic in the solution of differential equations involving resistances and inductances that a DC component accompanies the symmetrical AC component. The magnitude of the DC component can equal that of the peak AC component since both are determined by X J. The decay of the DC component can be reasonably slow and is determined by which is a function of X J and the armature winding resistance Ra With machines that have significant values of X J and particularly low values of R, the value of Ta can become relatively high. When Ta is high in relation to Tj and rj it is possible that the initial AC decay is faster than the DC decay. When this happens the AC instantaneous current does not reach zero until several cycles have passed. This puts an extra strain on the circuit breaker and can cause problems at the point when it starts to open to clear the fault current. [Pg.150]

Short circuits that do not involve earth, and which are within the length of the cable, can be detected by setting the instantaneous elements of the overcnrrent relays to a value of current calculated at the receiving end of the cable that flows into a zero-impedance fault. Customarily this fault is a three-phase fault for which the calculations are straightforward. If the fault is beyond the cable for example in a consumer then the fault current will be less and shonld be cleared by the consnmer protective device. The feeder cable relays will then act as a back np to the consumer relays. [Pg.333]

It is therefore necessary to provide a sensitive method for detecting earth fault currents. The most common method is to provide a core balance current transformer at the circuit breaker or contactor. This current transformer has a current or turns ratio, which is independent of the ratios used by the transformers connected in the three-phase conductors. This is because a particular level of current is to be detected rather than a fraction or multiple of the stator load current. The switchgear manufactnrer will normally recommend the ratio of the core balance transformer and the matching relay. The relay will be either instantaneous 50 N or an inverse time 51 N type depending upon whether the motor is controlled by a circuit breaker or a contactor. [Pg.340]

Overload devices in current use are typically thermal overload relays to BS 4941, motor starters for voltages up to and including 1000 V A.C. and 1200 V D.C. or BS 142 electrical protection relays. Relays to BS 4941 generally provide overload and single-phasing protection. Those complying with BS 142 are also frequently fitted with instantaneous earth fault and over-current trips. [Pg.224]

If one of the structures to be bonded is the sheath or metallic armouring of an electric supply cable, special precautions will be necessary to ensure that the voltage rise at the bond in the event of an instantaneous earth fault on the power-supply system does not endanger personnel or equipment associated with other buried structures. The bond and any associated current-limiting device should be suitably insulated and of adequate current-carrying capacity. [Pg.240]

When high voltage motors are being considered, it is usually found that the minimum conductor size of the cable is determined by the let-through fault withstand capability rather than the full-load or starting current. Cable manufacturers provide graphical data for fault withstand capabilities of their cables, which are based on practical tests. These aspects are also associated with the protection system used for the motor, e.g. a contactor-fuse combination, a circuit breaker, the protective relay characteristics (thermal, inverse time with or without instantaneous or earth fault elements). [Pg.124]

In order to restrict the detection of earth faults to those within the stator winding, and those from the stator terminals to the switchgear current transformers, a sensitive relay (64) is used. Three current transformers are used in the stator live lines and one in the star to NER connection. All four current transformers are connected in parallel such that any unbalance in the currents due to an internal fault is detected by the restricted earth fault relay (64). A sensitive high impedance relay is used to achieve an instantaneous response. However, if a high impedance is connected across a current transformer it is possible that very high voltages will appear across the impedance. This is due to the action of... [Pg.323]

In order to protect against prolonged winding or terminal box faults it is the usual practice to include an instantaneous tripping function. The range of the setting is typically 3 to 10 times the relay nominal current. [Pg.339]

MCBs to BS EN 60898. These are miniature circuit-breakers (MCBs) which may be used as an alternative to fuses for some installations. The British Standard includes ratings up to 100 A and maximum fault capacities of 9 kA. They are graded according to their instantaneous tripping currents - that is, the current at which they will trip within 100 ms. This is less than the time taken to blink an eye. [Pg.186]

Over-current protective devices (OCPDs) such as fuses, circuit breakers and protective relays, if properly adjusted and maintained, can detect an arcing condition almost instantaneously and clear the fault quickly. Old components that have not been well-maintained result in a slower reaction and elevated safety hazard. A requirement to maintain electrical distribution equipment was added to NFPA 70E in 2009. [Pg.50]

The recloser is another overcurrent device that automatically trips and recloses a preset number of times to clear or isolate faults. The concept of reclosing is derived from the fact that most faults are of the temporary type and can be cleared by de-energizing the circuit for a short period. Reclosers can be set for a number of operation sequences depending on the action desired. These typically include instantaneous trip and reclose operation followed by a sequence of time-delayed trip operations prior to lockout of the recloser. The minimum pick-up for most reclosers is typically set to trip instantaneously at two times the current rating. [Pg.1108]


See other pages where Fault current Instantaneous is mentioned: [Pg.288]    [Pg.836]    [Pg.421]    [Pg.164]    [Pg.164]    [Pg.332]    [Pg.529]    [Pg.2480]    [Pg.945]    [Pg.420]    [Pg.425]    [Pg.425]    [Pg.2490]    [Pg.287]    [Pg.507]    [Pg.834]    [Pg.2245]    [Pg.122]    [Pg.2494]    [Pg.329]    [Pg.483]    [Pg.537]    [Pg.149]    [Pg.947]    [Pg.939]    [Pg.127]   
See also in sourсe #XX -- [ Pg.274 ]




SEARCH



Current Instantaneous

Fault currents

Instantaneous

© 2024 chempedia.info