Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Air changes per hour

Ventilation Rate The rate at which indoor air enters and leaves a building. Expressed in one of two ways the number of changes of outdoor air per unit of time (air changes per hour, or "ACH") or the rate at which a volume of outdoor air enters per unit of time (cubic feet per minute, or "cfm"). [Pg.552]

Depending on the application, the air-change rate may range from 0.5 to 100 air changes per hour. It must be remembered, however, that adequate provision must be made for the makeup air to enter the space without creating discomfort or other problems. [Pg.737]

A workshop is30mxl5mx4m and has to be maintained at 20 C with six air changes per hour with a supply air temperature of 14 C. Determine the maximum cooling load that can be met. [Pg.739]

Determine the air temperature that is necessary to maintain a volume of 1200 m- with six air changes per hour at 20 "C, if the total heat loss is 45 kW. [Pg.741]

For these rooms, the air should flow horizontally from one end to the other with a velocity greater than 1.3 m s"T The necessary airflow rate is of course calculated as the volume times the number of air changes per hour. [Pg.1000]

A dilution ventilation rate of at least 6 air changes per hour (ach) is recommended, with 12 or more ach recommended for new construction or renovation. This may not provide sufficient dilution to allow workers to enter without respiratory protection, but it is considered a feasible dilution rate that will reduce the risk of infection for those workers who must enter the room with respiratory protection. Dilution also reduces the contaminant concentration and therefore the risk when temporary leakage from the room occurs such as when doors are opened or closed. [Pg.1003]

Air change rate The ratio of the volume of ait supplied or extracted to the volume of the space usually measured in air changes per hour (ach) and normally related to the fresh air change rate. [Pg.1407]

Infiltration rate The rate at which outdoor air enters into a room through the imperfections in the building structure, expressed in air changes per hour or L s. ... [Pg.1451]

Ventilation rate The actual mechanical or natural air change rate within a space, expressed in L/s or air changes per hour. The supply air may be all fresh air, or a mixture of fresh and recirculated air. [Pg.1486]

Place the patient in a private room with negative air pressure that has a minimum of six air changes per hour and appropriate filtration before the air is discharged from the room. [Pg.495]

Consolidate patients in the same area of the hospital to minimize exposures to other patients and healthcare workers. Place the patient in a private room with negative air pressure that has a minimum of six air changes per hour and appropriate filtration before the air is discharged from the room. Restricted access of nonessential staff and visitors to patient s room. [Pg.530]

The enclosed area is provided with six air changes per hour by artificial (mechanical) means. [Pg.149]

If natural ventilation is used, 12 air changes per hour are obtained throughout the enclosed area. [Pg.149]

A minimum of six air changes per hour are provided to enclosed areas. [Pg.162]

All hydrocarbon process areas containing materials with gaseous materials that are not adequately ventilated (i.e., would not achieve a minimum of six air changes per hour or would allow the build up of flammable gas due to noncirculating air space). Typically applications include compressor enclosures, process modules in offshore platforms and enclosed arctic facilities. [Pg.187]

All enclosed spaces with the potential for flammable or toxic atmospheres should be ventilated, preferably at a rate of not less than six air changes per hour. Low level exhaust ventilation is important to minimize the potential accumulation of vapors. A rule of thumb for design is 1 cfm/ft of floor area with exhaust points no higher than 12 in (30 cm) off the floor. The ventilation system should be designed in accordance with Chapter 5 of NFPA 30. [Pg.163]

Where ventilation is installed to effect a reduction in the area electrical classification, the rate should be no less than 12 air changes per hour for an adequately ventilated area in accordance with API RP 500. Areas containing ignition sources, such as control and switchgear buildings, gas turbine acoustical enclosures, and power generators, should be pressurized in accordance with NFPA 496, if located in an electrically classified area. [Pg.163]

Determine the number of air changes per hour in the clean area by calculation from the inlet air flow and the area volume. [Pg.160]


See other pages where Air changes per hour is mentioned: [Pg.382]    [Pg.99]    [Pg.204]    [Pg.325]    [Pg.288]    [Pg.633]    [Pg.709]    [Pg.737]    [Pg.739]    [Pg.739]    [Pg.740]    [Pg.1000]    [Pg.510]    [Pg.512]    [Pg.55]    [Pg.462]    [Pg.433]    [Pg.1297]    [Pg.352]    [Pg.602]    [Pg.617]    [Pg.290]    [Pg.83]    [Pg.97]    [Pg.114]    [Pg.127]    [Pg.141]   
See also in sourсe #XX -- [ Pg.1297 ]




SEARCH



Air changes

HOUR

Per hour

© 2024 chempedia.info