Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Cables volt drop

LV cable volt-drop when running at full-load 2.5% to 5.0%. [Pg.124]

Appendix G gives detailed calculations of cable volt-drops for the starting and full-load running conditions of a 500 kW induction motor that is to be started direct-on-line in a power system that is fed by three 3125 kVA generators. This appendix demonstrates the following aspects of starting large motors -... [Pg.124]

Note See Chapter 9 for a similar expression used with cable volt-drop). [Pg.135]

The nsual limit to volt-drop in three-phase cables feeding static loads is 2.5% at full load. [Pg.171]

Volt-drop developed across the cable under steady state and transient conditions. [Pg.198]

The secondary cable runs on its own cable rack to a switchboard. Both cable routes are short enough to neglect volt-drop considerations. Find suitable Cu/XLPE/PVC/SWA/PVC cable conductor sizes. [Pg.207]

The volt-drop in the left-hand side of the cable is Vsc,... [Pg.215]

When calculating the volt-drop in low voltage motor feeder cables it is necessary to consider three factors in particular -... [Pg.220]

Typical limiting values for the steady state volt-drop at the receiving end of LV and HV cables are -... [Pg.220]

Find the smallest cable size and its maximum route length to satisfy a running volt-drop of 5% and a starting volt-drop of 15%. Choose an XLPE insulated 600/1000 V 3-core cable to be routed in air. The ambient air temperature is 25°C. [Pg.221]

Since the cable volt-drop is significant it is necessary to revise the starting time duration and current from the data given by the manufacturer of the motor. [Pg.230]

Table 9.33 shows the volt-drop resnlts for all the available cables,... [Pg.239]

Table 9.33. Volt-drop in worked example the motor feeder cable for the ... Table 9.33. Volt-drop in worked example the motor feeder cable for the ...
Cable cross-sectional area should be at least 50 mm, to comply with volt-drop. [Pg.240]

For cables having long route lengths the associated volt-drop may cause the margin in cnrrent capacity to be reasonably high, especially with low voltage feeders. [Pg.333]

These harmonics will cause two secondary problems. Firstly, the harmonic currents will flow in cables, transformers and generator windings and in so doing will immediately produce harmonic volt-drops in these series circuits. This in turn will cause the voltages at various points in the system to contain harmonic components, e.g. either side of a transformer, at motor control centres and... [Pg.386]

The near-rectangular line currents will produce volt-drops in the series resistance-reactance cables, overhead lines and transformers. These volt-drops will be non-sinusoidal and will distort the waveform at their intermediate points of connection. At snch points there may be a switchboard or distribntion board and the loads connected to them will experience the distorted voltage waveform. [Pg.406]

Now test for volt drop from Table 3.5 the volt drop per ampere per metre for a 10mm cable is 4.4mV. So the volt drop for this cable length and load is equal to ... [Pg.206]

Regulation 525 states that the drop in voltage from the supply terminals to the fixed current-using equipment must not exceed 3% for lighting circuits and 5% for other uses of the mains voltage. That is a maximum of 6.9V for lighting and 11.5V for other uses on a 230V installation. The volt drop for a particular cable may be found from ... [Pg.309]


See other pages where Cables volt drop is mentioned: [Pg.7]    [Pg.9]    [Pg.106]    [Pg.123]    [Pg.124]    [Pg.124]    [Pg.159]    [Pg.167]    [Pg.171]    [Pg.171]    [Pg.209]    [Pg.209]    [Pg.210]    [Pg.210]    [Pg.211]    [Pg.213]    [Pg.221]    [Pg.230]    [Pg.236]    [Pg.399]    [Pg.442]    [Pg.452]    [Pg.203]    [Pg.206]    [Pg.313]    [Pg.164]    [Pg.326]   
See also in sourсe #XX -- [ Pg.220 , Pg.223 ]




SEARCH



Cables

Volts

© 2024 chempedia.info