Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Secondary control loop

The dynamics of the secondary control loop should be approximately two to four times as fast as the dynamics of the primary control loop in order to achieve stable control. The secondary controller is actually part of the primary controller s process system. Hence, changes in the secondary controller tuning constants change the process system of the primary controller. Therefore, cascade control loops should always be tuned by first tuning the secondary controller and then the primary controller. If the secondary controller tuning is changed for any reason, the primary controller may need to be retuned also. [Pg.70]

There is no crossover frequency for the secondary control loop. Therefore, we can use large values for the gain KCiU, which produce a very fast closed-loop response, to compensate for any changes in the disturbance dii arising within the secondary process. [Pg.211]

The two feedback controllers are nested with the secondary control loop located inside the primary control loop. [Pg.663]

It is obvious from the preceding discussion that for a cascade control system to function effectively, the secondary control loop must be selected and tuned so as to have a faster response than the primary controller. According to Ref 7, the secondary controller is normally a P or PI controller with derivative action hardly used. The primary controller is typically a PI or PID controller. [Pg.663]

To eliminate reset windup, we break the master controller internal feedback as before, but now we use the secondary measurement for feedback as shown by Figure 9.7. If, for example, we have temperature cascaded to flow, we feed the output from the flow transmitter back into the master controller reset circuit. This means that during normal control the lags in the secondary control loop appear in the reset feedback circuit of the primary controller. If, as usual, Ak slave loop is much faster than the master loop, this technique will not r . >preciably increase the master controller reset time. [Pg.202]

The block diagram for a general cascade control system is shown in Fig. 16.4. Subscript 1 refers to the primary control loop, whereas subscript 2 refers to the secondary control loop. Thus, for the furnace temperature control example,... [Pg.291]

All of these variables represent deviations from the nominal steady state. Because disturbances can affect both the primary and secondary control loops, two... [Pg.291]

Many misconceptions exist about cascade control loops and their purpose. For example, many engineers specify a level-flow cascade for every level control situation. However, if the level controller is tightly tuned, the out-flow bounces around as does the level, regardless of whether the level controller output goes direcdy to a valve or to the setpoint of a flow controller. The secondary controller does not, in itself, smooth the outflow. In fact, the flow controller may actually cause control difficulties because it adds another time constant to the primary control loop, makes the proper functioning of the primary control loop dependent on two process variables rather than one, and requites two properly tuned controllers rather than one to function properly. However, as pointed out previously, the flow controller compensates for the effect of the upstream and downstream pressure variations and, in that respect, improves the performance of the primary control loop. Therefore, such a level-flow cascade may often be justified, but not for the smoothing of out-flow. [Pg.70]

In control situations with more then one measured variable but only one manipulated variable, it is advantageous to use control loops for each measured variable in a master-slave relationship. In this, the output of the primary controller is usually used as a set point for the slave or secondary loop. [Pg.105]

A cascade control system can be designed to handle fuel gas disturbance more effectively (Fig. 10.1). In this case, a secondary loop (also called the slave loop) is used to adjust the regulating valve and thus manipulate the fuel gas flow rate. The temperature controller (the master or primary controller) sends its signal, in terms of the desired flow rate, to the secondary flow control loop—in essence, the signal is the set point of the secondary flow controller (FC). [Pg.189]

Figure 10.1. Cascade control of the temperature of a furnace, which is taken to be the same as that of the outlet process stream. The temperature controller does not actuate the regulating valve directly it sends its signal to a secondary flow rate control loop which in turn ensures that the desired fuel gas... Figure 10.1. Cascade control of the temperature of a furnace, which is taken to be the same as that of the outlet process stream. The temperature controller does not actuate the regulating valve directly it sends its signal to a secondary flow rate control loop which in turn ensures that the desired fuel gas...
We can use a block diagram to describe Fig. 10.1. Cascade control adds an inner control loop with secondary controller function Gc2 (Fig. 10.2a). This implementation of cascade control requires two controllers and two measured variables (fuel... [Pg.190]

Disturbance, such as upstream pressure, which specifically leads to changes in the fuel gas flow rate is now drawn to be part of the secondary flow control loop. (A disturbance such as change in the process stream inlet temperature, which is not part of the secondary loop, would still be drawn in its usual location as in Section 5.2 on page 5-7.)... [Pg.190]

So far, we know that the secondary loop helps to reduce disturbance in the manipulated variable. If we design the control loop properly, we should also accomplish a faster response in the actuating element the regulating valve. To go one step further, cascade control can even help to make the entire system more stable. These points may not be intuitive. We ll use a simple example to illustrate these features. [Pg.191]

The slave loop will have a 10% offset with respect to desired set point changes in the secondary controller. [Pg.192]

With the choice of x = 0.5 s, but without the inner loop nor the secondary controller, the closed-loop equation is... [Pg.193]

A more sophisticated implementation is full metering control (Fig. 10.6). In this case, we send the signals from the fuel gas controller (FC in the fuel gas loop) and the air flow transmitter (FT) to the ratio controller (RC), which takes the desired flow ratio (R) as the set point. This controller calculates the proper air flow rate, which in turn becomes the set point to the air flow controller (FC in the air flow loop). If we take away the secondary flow control loops on both the fuel gas and air flow rates, what we have is called parallel positioning control. In this simpler case, of course, the performance of the furnace is subject to fluctuations in fuel and air supply lines. [Pg.199]

It is useful to compare these values with those found for conventional control = 19.8 and oi. = 1.61. We can see that cascade control results in higher controller gain and smaller dosedloop time constant (the reciprocal of the frequency). Figure 11.26 gives a root locus plot for the primary controller with the secondary controller gain set at Two of the loci start at the complex poles s = rj which Come from the dosedloop secondary loop. The other curve... [Pg.380]

The reactor temperature controller (loop 2) is the primary controller, whereas the jacket temperature controller (loop 3) is the secondary controller. The advantage of the cascade control is that the reactor temperature control quickly reacts by the cascade system to disturbances in cooling fluid inlet conditions. The d3mamics of the transfer function G32 is faster than that of G 22-In the CSTR cascade control there are two control loops using two different measurements temperatures T and Tj, but only one manipulated variable Fj. The transfer function of the primary controller is the following ... [Pg.21]

Secondary Circulation Loop Temperature Control Systems... [Pg.211]

This is the simplest system for temperature control of a reactor only the jacket temperature is controlled and maintained constant, leaving the reaction medium following its temperature course as a result of the heat balance between the heat flow across the wall and the heat release rate due to the reaction (Figure 9.9). This simplicity has a price in terms of reaction control, as analysed in Sections 6.7 and 7.6. Isoperibolic temperature control can be achieved with a single heat carrier circuit, as well as with the more sophisticated secondary circulation loop. [Pg.212]

Figure 9.9 Isoperibolic temperature control with a secondary circulation loop. Figure 9.9 Isoperibolic temperature control with a secondary circulation loop.
An addition to the noted advantages is that the set point of the secondary controller can be limited. In addition, by speeding up the overall cascade loop response, the sensitivity of the primary process variable to process upsets is also reduced, whereas the secondary loop can reduce the effect of control valve sticking or actuator nonlinearity. The primary or outer control loop of a cascade system is usually a PI or PID controller. A properly selected secondary will reduce the proportional band of the primary controller. [Pg.196]

Adding a cascade slave to a fast loop can destabilize the primary if most of the process dynamics (time lags) are within the secondary loop. The most common example of this is using a valve positioner in a flow-control loop. The... [Pg.196]

In reactor temperature control applications, a slave controlling the jacket outlet temperature is recommended so that the dynamics of the jacket is transferred from the primary to the secondary loop. In temperature-on-temperature cascade systems, such as shown in Figure 2.45, the secondary controller should have little or no integral. [Pg.197]

If the ratio calculation is made outside the secondary flow control loop, its setting does not change the dynamics or response of the loop. [Pg.200]

In cascade control, we therefore have two control loops using two different measurements but sharing a common manipulated variable. The loop that measures the controlled variable (in the example, the reacting mixture temperature) is the dominant, or primary control loop (also referred to as the master loop) and uses a set point supplied by the operator, while the loop that measures the second variable (in the example, the cooling water temperature) is called the secondary (or slave) loop and uses the output from the primary controller as its set point. Cascade control is very common in chemical processes and the major benefit to be gained is that disturbances arising within the secondary loop are corrected by the secondary controller before they can affect the value of the primary controlled output. [Pg.266]


See other pages where Secondary control loop is mentioned: [Pg.69]    [Pg.645]    [Pg.386]    [Pg.3624]    [Pg.3626]    [Pg.513]    [Pg.69]    [Pg.645]    [Pg.386]    [Pg.3624]    [Pg.3626]    [Pg.513]    [Pg.733]    [Pg.194]    [Pg.237]    [Pg.279]    [Pg.495]    [Pg.495]    [Pg.465]    [Pg.645]    [Pg.273]    [Pg.24]    [Pg.24]    [Pg.44]    [Pg.199]    [Pg.357]   


SEARCH



Control loop

Secondary Circulation Loop Temperature Control Systems

Secondary loop

© 2024 chempedia.info