Typical flowsheet for a cooling tower system

All materials shall be of first-class quality and free from all defects that would cause unworkmanlike appearance. All materials used shall be suitable for the service under which they will operate. [Pg.171]

The cooling tower manufacturer shall conduct the acceptance performance test and shall supply the necessary instruments to conduct the test in accordance with the requirements of the CTI Test Procedure ATP-105, latest revision. [Pg.171]

The manufacturer s proposal shall include performance curves of the tower, based on design fan horsepower, showing cold water temperature versus air wet-bulb temperature for 90%, 100% and 110% of design water flow. The curves shall cover cooling ranges of 15°F, 20°F, 25°F, 30°F and design range. [Pg.171]

The cooling tower shall meet the following requirements.  [Pg.171]

The supporting structure will be an independent structure in reinforced concrete and so calculated to be able to carry the static loads as well as the mechanical equipment. The construction will be properly reinforced and braced to transfer directly to the foundations all loads and tresses. [Pg.172]


Figure 7.4 Typical flowsheet for a cooling tower system. Figure 7.4 Typical flowsheet for a cooling tower system.