Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Neutral earthing resistance

Neutral earthing arrangements, e.g. solid, with a neutral earthing resistance (NER), with a common busbar, switches or circuit breakers for isolation. [Pg.17]

The high impedance is usually a resistance chosen to limit the earth current to about 20 mA. A current detector is used in conjunction with the resistance to raise an alarm if a line-to-earth fault occurs. A zig-zag transformer, or reactor, is sometimes used with three-wire supplies such as used in drilling rigs and emergency systems. It is specially designed and internally connected to create a very low zero sequence impedance to earth currents. Therefore, the current is limited only by the resistance of the neutral earthing resistor. Some special purpose earth current alarm systems are available that inject a small DC current into the three-phase system, which is used to identify the actual location of the fault. [Pg.358]

L1, L2, L3 phase conductors 1/1, 1/2, 1/3 voltages phase to neutral C1, C2, C3 capacitances phase to earth PE protective earthed conductor RF earth fault resistance UN, PE voltage between neutral N and PE in case of an earth fault... [Pg.494]

In order to minimise the risk of shock and fire, any metalwork other than the current-carrying conductor must be connected to earth. The neutral of the electrical supply is earthed at the source of distribution, i.e. the supply transformer, so that, if all appliances are also connected to earth, a return path for the current will be available through earth when a fault occurs (see Fig. 1.9). To be effective, this earth path must he of sufficiently low resistance to pass a relatively high current when a fault occurs. This higher current will in turn operate the safety device in the circuit, Le. the fuse will blow. [Pg.20]

Insulation resistance tests apply a substantial test voltage, typically 500 V, between the live and neutral bonded together and the earth. The PAT Tester then calculates the insulation resistance and either gives an actual reading... [Pg.40]

There are two tests to be carried out using an insulation resistance tester which must have a test voltage of 500V d.c. for 230V and 400V installations. These are line and neutral conductors to earth and between line conductors. The procedures are ... [Pg.308]

Where the circuit inciudes electronic equipment which might be damaged by the insulation resistance test, a measurement between all live conductors (i.e. live and neutral conductors connected together) and the earthing arrangements may be made. The insulation resistance of these tests should be not less than 1. OMH (lET Regulation 612.3.3). [Pg.309]


See other pages where Neutral earthing resistance is mentioned: [Pg.324]    [Pg.324]    [Pg.164]    [Pg.357]    [Pg.370]    [Pg.227]    [Pg.574]    [Pg.12]    [Pg.365]    [Pg.494]    [Pg.112]    [Pg.350]    [Pg.22]    [Pg.505]    [Pg.260]    [Pg.85]    [Pg.225]    [Pg.216]    [Pg.115]    [Pg.298]    [Pg.300]    [Pg.319]    [Pg.150]    [Pg.421]    [Pg.275]    [Pg.157]   
See also in sourсe #XX -- [ Pg.80 , Pg.355 , Pg.357 , Pg.585 , Pg.596 ]




SEARCH



Earth resistivity

Neutral earthing

© 2024 chempedia.info