Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Flooded condenser control

When the condenser contains excess heat transfer area, the fraction of condenser area that is flooded can be manipulated to vary the rate of condensation. This principle is used in "flooded condenser control schemes (Sec. 17.2.2). [Pg.471]

Flooded reflux drums. These are used as part of flooded condenser control schemes (Sec. 17.2.2). A flooded drum is only suitable when substantial fluctuations in product rate can be tolerated (e.g., product goes to storage). A flooded drum provides no surge for controlling and smoothing out product fluctuations, but it maintains surge for the reflux pump and reflux circuit. [Pg.484]

Flooded condenser control A method of pressure control in a distillation tower. [Pg.712]

Pressure can also be controlled by variable heat transfer coefficient in the condenser. In this type of control, the condenser must have excess surface. This excess surface becomes part of the control system. One example of this is a total condenser with the accumulator running full and the level up in the condenser. If the pressure is too high, the level is lowered to provide additional cooling, and vice versa. This works on the principle of a slow moving liquid film having poorer heat transfer than a condensing vapor film. Sometimes it is necessary to put a partially flooded condenser at a steep angle rather than horizontal for proper control response. [Pg.66]

Flooded condensers and flooded reboilers are sometimes used on distillation columns. In the sketch below, a hquid level is held in the condenser, covering some of the tubes. Thus a variable amount of heat transfer area is available to condense the vapor. Column pressure can be controlled by changing the distillate (or reflux) drawoff rate. [Pg.81]

Derive a dynamic mathematical model of the flooded-condenser system. Calculate the transfer function relating steam flow rate to condensate flow rate. Using a PI controller with tj = 0.1 minute, calculate the closedloop time constant of the steam flow control loop when a closedloop damping coefTident of 0.3 is used. Compare this with the result found in (u). [Pg.371]

I well remember one pentane-hexane splitter in Toronto. The tower simply could not make a decent split, regardless of the feed or reflux rate selected. The tower-top pressure was swinging between 12 and 20 psig. The flooded condenser pressure control valve, shown in Fig. 3.1, was operating between 5 and 15 percent open, and hence it was responding in a nonlinear fashion (most control valves work properly only at 20 to 75 percent open). The problem may be explained as follows. [Pg.25]

Figure 13.8 Flooded condenser pressure control the preferred method. Figure 13.8 Flooded condenser pressure control the preferred method.
In general, flooded condenser pressure control is the preferred method to control a tower s pressure. This is so because it is simpler and cheaper than hot-vapor bypass pressure control. Also, the potential problem of a leaking hot-vapor bypass control valve cannot occur. Many thousands of hot-vapor bypass designs have eventually been converted—at no cost—to flooded condenser pressure control. [Pg.160]

Sometimes we see tower pressure control based on feeding a small amount of inert or natural gas into the reflux drum. This is bad. The natural gas dissolves in the overhead liquid product and typically flashes out of the product storage tanks. The correct way to control tower pressure in the absence of noncondensable vapors is to employ flooded condenser pressure control. If, for some external reason, a variable level in the reflux drum is required, then the correct design for tower pressure control is a hot-vapor bypass. [Pg.161]

Figure 3.10. Condensers, (a) Condenser on temperature control of the PF condensate. Throttling of the flow of the HTM may make it too hot. (b) Condenser on pressure control of the HTM flow. Throttling of the flow of the HTM may make it too hot. (c) Flow rate of condensate controlled by pressure of PF vapor. If the pressure rises, the condensate flow rate increases and the amount of unflooded surface increases, thereby increasing the rate of condensation and lowering the pressure to the correct value, (d) Condenser with vapor bypass to the accumulator drum. The condenser and drum become partially flooded with subcooled condensate. When the pressure falls, the vapor valve opens, and the vapor flows directly to the drum and heats up the liquid there. The resulting increase in vapor pressure forces some of the liquid back into the condenser so that the rate of condensation is decreased and the pressure consequently is restored to the preset value. With sufficient subcooling, a difference of 10-15 ft in levels of drum and condenser is sufficient for good control by this method. Figure 3.10. Condensers, (a) Condenser on temperature control of the PF condensate. Throttling of the flow of the HTM may make it too hot. (b) Condenser on pressure control of the HTM flow. Throttling of the flow of the HTM may make it too hot. (c) Flow rate of condensate controlled by pressure of PF vapor. If the pressure rises, the condensate flow rate increases and the amount of unflooded surface increases, thereby increasing the rate of condensation and lowering the pressure to the correct value, (d) Condenser with vapor bypass to the accumulator drum. The condenser and drum become partially flooded with subcooled condensate. When the pressure falls, the vapor valve opens, and the vapor flows directly to the drum and heats up the liquid there. The resulting increase in vapor pressure forces some of the liquid back into the condenser so that the rate of condensation is decreased and the pressure consequently is restored to the preset value. With sufficient subcooling, a difference of 10-15 ft in levels of drum and condenser is sufficient for good control by this method.
Figure 5.5 Heat transfer control by variable heat transfer area in flooded condenser. Figure 5.5 Heat transfer control by variable heat transfer area in flooded condenser.
A fourth degree of freedom is consumed to control column pressure. The valves available are condenser cooling (by far the most commonly7 used), reboiler heat input, and feed (if the feed is partially vapor). If a flooded condenser is used, the cooling water valve is wide open and an additional valve, typically located between the condenser and the reflux drum, is used to cover or expose heat-transfer area in the condenser. [Pg.196]

Step 2. This process has 14 control degrees of freedom. They include fresh feed valve DIB column steam, cooling water, reflux, distillate, and bottoms valves purge column steam, cooling water, reflux, distillate, and bottoms valves furnace fuel valve flooded condenser cooling water valve and DIB column feed valve. [Pg.276]

To avoid the high-pressure safety constraint, we must control reactor pressure. We can use the distillate valve from the purge column, the flooded condenser cooling water valve, or the DIB column feed valve. The most logical variable to use for control of the flooded condenser (.reactor) pressure is the DIB column feed valve (as shown in Fig. 5.5). Based upon the discussion in Step 3, we would then use the flooded condenser cooling water valve to keep the liquid level in a good control range. [Pg.281]

In the HYSYS simulation, the flooded condenser is simulated as a cooler with a temperature control loop manipulating cooling water rate. The reactor inlet pressure is set by the exit of the liquid recycle pump on the purge column distillate stream. [Pg.283]

For column pressure control there are Ihrea genaial approaches vent bleed (to arraosphere or to vacuum system), hot vapor bypass, and flooded condenser. These approaches are illustrated in Fig. 5.11-2.3 For an atmospheric column, the vent approach is quite simple. The vapor bypass represents a temperature bleading method. Partial flooding of the condenser suiface adjusts the bent transfer capability or the condenser. The schemes are generally self-explanatory. [Pg.330]

Control techniques. Pressure and condensation control techniques are classified into four categories vapor flow variations, flooded condensers, coolant flow variations, and miscellaneous methods. These techniques are described below. [Pg.528]

Figure 17.5a illustrates a flooded condenser with the control valve located at the condenser outlet. The control valve required is small... [Pg.528]

Figure 17.5 Pressure control by condenser flooding, (a) Control valve in condenser outlet ib) flooded reflux drum (c) flooded reflux drum with automatic noncondensables venting [d) hot vapor bypass (c) a poorly pip hot vapor bypass if) control valve in condenser inlet. (Part c from "Unusual Operating Histories of Gas Processing and Olefins Plant Columns, H. Z. Kister and T. C. Hower, Jr., Plant/Operations Progi a, vol. 6. no. 3, p. 153 (July 1987). Reproduced by permis-... Figure 17.5 Pressure control by condenser flooding, (a) Control valve in condenser outlet ib) flooded reflux drum (c) flooded reflux drum with automatic noncondensables venting [d) hot vapor bypass (c) a poorly pip hot vapor bypass if) control valve in condenser inlet. (Part c from "Unusual Operating Histories of Gas Processing and Olefins Plant Columns, H. Z. Kister and T. C. Hower, Jr., Plant/Operations Progi a, vol. 6. no. 3, p. 153 (July 1987). Reproduced by permis-...
Figure 17.5/ shows a flooded condenser scheme similar to that of Fig. 17.5a, but with the control valve located at the condenser inlet. This method is inferior compared to Fig. 17.5a (77). It requires a larger control valve, is more difficult to understand, and it affects condensation at a lower temperature. The condenser outlet line must enter the reflux drum well below the liquid level. A pressure-equalizing line as in the method shown in Fig. 17.5a is also required. Figure 17.5/ shows a flooded condenser scheme similar to that of Fig. 17.5a, but with the control valve located at the condenser inlet. This method is inferior compared to Fig. 17.5a (77). It requires a larger control valve, is more difficult to understand, and it affects condensation at a lower temperature. The condenser outlet line must enter the reflux drum well below the liquid level. A pressure-equalizing line as in the method shown in Fig. 17.5a is also required.
Column pressure was controlled using a hot vapor bypass scheme (partially flooded condenser). Severe pressure and reflux drum level upsets occurred whenever the reflux drum surface was inadvertently agitated. [Pg.673]

Condenser controlled using a hot vsqwr bypass (partially flooded condenser). bcooM liquid entered the reflux drum vsqwr qiace (presumably due to unflooding the liquid inlet), and contacted drum vapor that was 100°F hotter. The rapid condensation sucked the liquid leg between the condenser and drum in seconds. [Pg.758]

FIGURE S.11 2 Sdiemes for control of column pressure (a) pressure control for an atmospheric column (vent bleed to atmosphere) (b) split range valves in a block and bleed anangement (vent Weed to vacuum) . (c) hot vapor bypass pressure control and (flooded condenser pressure control. [Pg.331]


See other pages where Flooded condenser control is mentioned: [Pg.147]    [Pg.159]    [Pg.408]    [Pg.209]    [Pg.221]    [Pg.177]    [Pg.550]    [Pg.147]    [Pg.159]    [Pg.408]    [Pg.209]    [Pg.221]    [Pg.177]    [Pg.550]    [Pg.159]    [Pg.44]    [Pg.279]    [Pg.44]    [Pg.919]    [Pg.924]    [Pg.539]   
See also in sourсe #XX -- [ Pg.209 , Pg.221 ]




SEARCH



Condensate control

Condensers control

Flooded condenser, pressure control

Flooding condensation

Flooding control

Pressure Control Via Flooded Condenser

Tower pressure controls) flooded condenser

© 2024 chempedia.info