Short-circuit protection

High-voltage contactor-type motor controls depend on power fuses for short-circuit protection. The fuses are coordinated with the overload relays to protect the motor circuit over the full range of fault conditions from overload conditions to solid maximum-current short circmts. [Pg.2490]

The starting of an induction motor does not relate to simple switching alone. It also involves its switchgears to control its starting inrush current, starting torque, or both, and its overload and short-circuit protection. [Pg.71]

The selection should be such as to provide proper discrimination at the various levels of a multi-distribution network. Our discussions generally take account of the recommendations in lEC 60947-4-1 regarding coordination between the short-circuit protection and the main components such as switching devices [switch, breaker. [Pg.288]

Short-circuit protection. To provide an instantaneous tripping on a short-circuit delay of, say, one or two cycles may be introduced into the tripping circuit to bypass any transient currents and avoid an unwanted trip. [Pg.298]

Thermal capacity to perform the required switching duties and sustain the fault conditions, at least up to the cut-off time of the short-circuit protective device, say, the HRC fuses. [Pg.312]

Role of an OCR this is only an overcurrent protection device and does not provide short-circuit protection. [Pg.365]

Testing of the main circuits (with short-circuit protective devices)... [Pg.432]

The current element of a relay is wound for a wide range of current settings in terms of the rated secondary current of the CT, such as 10-80% for a ground fault protection, 50-200% for an overcurrent and 300-800% for a short-circuit protection. At lower current settings, while the VA requirement for the operation of the relay will remain the same, the VA capacity of the CT will decrease in a square proportion of the current. A CT of a correspondingly higher VA level would therefore be necessary to obtain the reduced VA level. [Pg.473]

Nevertheless, unbalance is a major occurrence in either case and an unbalanced protection, in addition to short-circuit protection is imperative in all types of capacitor units. Hence it is also possible to design series protected capacitor units in larger sizes and for higher voltages, which are more economical, compared to smaller units. [Pg.814]

Underwriters Laboratories (UL) requires that consumer batteries pass a number of safety tests [3]. UL requires that a battery withstand a short circuit without fire or explosion. A positive temperature coefficient (PTC) device [4] is used for external short-circuit protection. The resistance of a PTC placed in series with the cell increases by orders of magnitude at high currents and resulting high temperatures. However, in the case of an internal short, e.g., if the positive tab comes lose and contacts the interior of the negative metal can, the separator could act as a fuse. That is, the impedance of the separator increases by two to three orders of magnitude due to an increase in cell temperature. [Pg.554]

Due to the high breaking capacity of the contactor (20 kA rms), fuses for short-circuit protection are unnecessary. [Pg.270]

As applicable, short-circuit protection of the power supply is in accordance with the documentation X ... [Pg.476]

Electrochemical machining (ECM) is a method of metal machining that aims at producing parts of specified shape, dimensions, and surface finish. The process is based on the removal of metal by electrochemical dissolution ([1-15] and references cited therein). Special machines have been developed to realize this aim. A complete ECM installation (Fig. 1) consists of the machine, the power supply, the electrolyte circulation system (tank, pump, heat exchanger, and sludge removal unit), and the control system (control of current, voltage, feed rate, gap width, and electrolyte temperature, pH value, pressure, and concentration short-circuit protection). [Pg.811]

For high voltage cables, and low voltage feeder cables between switchboards, the disconnection time can be reduced from 5 seconds to not less than 0.2 seconds. The time of 0.2 seconds is determined from the total clearance time of a circuit breaker protected by a fast acting overcurrent relay. For high voltage motor circuits in which the short-circuit protection is provided... [Pg.225]

Electrical earth connections, short-circuit protections, etc. [Pg.342]

In your own words, state the meaning of circuit overload and short-circuit protection. What will provide this type of protection ... [Pg.274]


See other pages where Short-circuit protection is mentioned: [Pg.2490]    [Pg.2490]    [Pg.124]    [Pg.299]    [Pg.312]    [Pg.478]    [Pg.507]    [Pg.507]    [Pg.679]    [Pg.829]    [Pg.830]    [Pg.837]    [Pg.837]    [Pg.179]    [Pg.184]    [Pg.113]    [Pg.2245]    [Pg.2245]    [Pg.169]    [Pg.841]    [Pg.169]    [Pg.139]    [Pg.2494]    [Pg.2494]    [Pg.11]    [Pg.333]    [Pg.452]    [Pg.355]    [Pg.127]    [Pg.190]    [Pg.270]    [Pg.271]    [Pg.149]   
See also in sourсe #XX -- [ Pg.240 ]

See also in sourсe #XX -- [ Pg.41 , Pg.49 , Pg.77 , Pg.139 , Pg.156 , Pg.185 , Pg.340 ]

See also in sourсe #XX -- [ Pg.45 ]

See also in sourсe #XX -- [ Pg.3 , Pg.4 , Pg.4 , Pg.5 ]