In general, it is fair to state that one of the major difficulties in interpreting, and consequently in establishing definitive tests of, corrosion phenomena in fused metal or salt environments is the large influence of very small, and therefore not easily controlled, variations in solubility, impurity concentration, temperature gradient, etc. . For example, the solubility of iron in liquid mercury is of the order of 5 x 10 at 649°C, and static tests show iron and steel to be practically unaltered by exposure to mercury. Nevertheless, in mercury boiler service, severe operating difficulties were encountered owing to the mass transfer of iron from the hot to the cold portions of the unit. Another minute variation was found substantially to alleviate the problem the presence of 10 ppm of titanium in the mercury reduced the rate of attack to an inappreciable value at 650°C as little as 1 ppm of titanium was similarly effective at 454°C . [Pg.1059]