Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Transformers control

Potential/control transformers must be provided with current limiting fuses at both ends. [Pg.378]

Specification for control transformers for switchgear and controlgear for voltages not exceeding lOOOV a.c. Specification for high voltage busbars and busbar connections... [Pg.399]

Tappings are generally not necessary, as a transformer is designed for a particular voltage system. If and when such a need arises (as in a control transformer (Section 15.4.5)) they can be provided on the primary side of the transformer. [Pg.458]

To damp the transient voltages on the primary side. For markings refer to Section 15.10.1 and Figure 15.35. 15.4.5 Control transformers... [Pg.466]

Figure 15.9 A typical outdoor type oil-filled 11 kV control transformer... Figure 15.9 A typical outdoor type oil-filled 11 kV control transformer...
Figure 15.8 Typical single-phase and three-phase control transformers... Figure 15.8 Typical single-phase and three-phase control transformers...
For brevity, only the more relevant aspects are discussed here. For more details, refer to lEC 60044-2 and lEC 60186. for instrument voltage transformers and lEC 60076-3 for control transformers. [Pg.467]

The following may be ascertained w hen selecting the rating of a control transformer ... [Pg.467]

The control transformer to be selected may have a rating nearest to the maximum hold-on VA burden so calculated and must be suitable to feed the required inrush current at the p.f. so calculated without affecting its regulation.. So long as these two points fall below the inrush curve of the control transformer, its regulation... [Pg.467]

The actual values us worked out above must fall below the inrush curve of the selected control transformer of 500 VA. as illustrated in Figure 15,12,... [Pg.469]

Figure 15.12 Checking the suitability of the 500 VA control transformer for the required duty tor Example 15,1... Figure 15.12 Checking the suitability of the 500 VA control transformer for the required duty tor Example 15,1...
Instrument and control transformers application and selection 15/495 Relevant Standards... [Pg.495]

Figure 16.7 Phasor diagrams for QDC, referred to the secondary side of the control transformer... Figure 16.7 Phasor diagrams for QDC, referred to the secondary side of the control transformer...

See other pages where Transformers control is mentioned: [Pg.391]    [Pg.425]    [Pg.455]    [Pg.455]    [Pg.455]    [Pg.457]    [Pg.457]    [Pg.459]    [Pg.461]    [Pg.463]    [Pg.465]    [Pg.467]    [Pg.467]    [Pg.467]    [Pg.467]    [Pg.467]    [Pg.468]    [Pg.469]    [Pg.469]    [Pg.470]    [Pg.471]    [Pg.473]    [Pg.475]    [Pg.477]    [Pg.479]    [Pg.481]    [Pg.483]    [Pg.485]    [Pg.487]    [Pg.489]    [Pg.491]    [Pg.491]    [Pg.493]    [Pg.503]    [Pg.997]    [Pg.230]   
See also in sourсe #XX -- [ Pg.455 ]




SEARCH



CONTROLLED TRANSFORMATION RATE THERMAL ANALYSIS (CRTA)

Catalyst-controlled transformation

Control flow transformation

Controlled Transformations of Carbohydrates into Hydrocarbon Fuels

Controlled Transformations of Carbohydrates into Novel Biofuels

Controlled Transformations of Lignin into Potential Fuel Compounds

Controlled transformation rate

Controlled transformation rate thermal analysis

Controlled transformation rate thermal analysis CRTA) method

Controlled-transformation-rate thermal

Equipment and Control of Transformer-Rectifiers

Fourier transform coherent control

Fourier transform control

Laplace transform, process transfer control

Phase transformation and control

Rectifier/transformer control

Testing control transformers

Transformation diffusion-controlled

© 2024 chempedia.info