Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Airborne Activity Confinement System

The ventilation system section is comprised of seven subsystems airborne activity confinement system (AACS), central control room habitability (CCRH), Assembly Area ventilation (AAV) system, Disassc ty Area ventilation (DAV) stem. Purification Area ventilation (PAV) system. Building 108-K ventilation (V108) system, and nuscellaneous ventilation tystem. [Pg.56]

Airborne Activity Confinement System, (4) Cooling Water System, and (5) Process Water System. Safety Significant discrepancies identified by the waikdowns are to be evaluated by the RIMP Committee and resolved prior to restart. [Pg.121]

Airborne Activity Confinement System Monitoring and Actuation System Moderator Recovery System 120 VAC Power... [Pg.147]

The Savannah River Site (SRS) reactors are designed with an airborne activity confinement system (AACS) rather than a containment system. The AACS is an active ventilation system that continuously exhausts air from prescribed zones in the reactor building through a set of filters in order to prevent unattenuated release of contaminated air to the environment under accident conditions. The system is designed such that air flows from areas of least expected radioactive contamination to areas of higher potential for radioactive contamination. This is achieved by maintaining the process areas at negative pressures by the operation of fans and dampers. [Pg.268]

WSRC, "Airborne Activity Confinement System," Restart Test Identification Report No. 10, Revision 0, March 15, 1990. [Pg.273]

The purpose of the contaminated water removal and disposal system (CWRDS), i.e., the sump water removal system, is to remove and retain the emergency coolant or cooling water following a design basis loss of coolant accident (LOCA) or seismic event. This system operates in conjunction with the Airborne Activity Confinement System (AACS) to control the release of liquid and airborne contaminants. [Pg.278]

Historically, for the SRS reactors, a DBA core damage fraction of 1 percent has been associated with the LBLOCA, which is consistent with the capability of the airborne activity confinement system. [Pg.567]

Air supply and filter breakthrough alarms for Airborne activity Confinement System... [Pg.574]


See other pages where Airborne Activity Confinement System is mentioned: [Pg.24]    [Pg.56]    [Pg.252]    [Pg.268]    [Pg.550]    [Pg.24]    [Pg.56]    [Pg.252]    [Pg.268]    [Pg.550]    [Pg.571]    [Pg.278]    [Pg.221]    [Pg.556]   