Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

A p controller

This again is an inherently linear process for small deviations. A P + I controller will obey the [Pg.302]

Taking the Laplace transform gives the transfer function of the controller as  [Pg.302]

4 The response of steam throttle travel to demanded throttle travel, x/x  [Pg.303]

A valve may usually be modelled as an exponential lag, subject to rate limits. For small-signal, linear analysis, the rate limits will not be breached, so the model is simply  [Pg.303]

5 Steam throttle opening to steam throttle travel, dyt/dx [Pg.303]


Usually the proportional gain. Limited to second order systems. No unique answer other than a P-controller. Theoretically can use other transient response criteria. 1/4 decay ratio provides a 50% overshoot. [Pg.257]

Tomlinson, E., and Rolland, A.P., Controllable gene therapy pharmaceutics of nonviral gene delivery systems, Journal of Controlled Release, 1995, 39, 357-372. [Pg.14]

There is a steadystatc error in the controlled variable when a P controller is used. This offset results because there is no integral term to drive the error to zero. [Pg.236]

J0i Use Laplace transforms to prove mathematically that a P controller produces steadystate ofiMt and that a PI controller does not. The disturbance is a step change in the load variable. The process openloop transfer functions, Gm and G[, are both liist-order lags with dUTerent gains but identical time constants. [Pg.335]

The liquid level in a tank is controlled by manipulating the flow out of the tank, using a P controller. The outflow rate is a function of only the valve position. The valve has linear installed eharacleristies and passes 20 ftVmin wide open. [Pg.373]

Figure 13.6 Responses of a P controller, a PI controller, and a PID controller for the step change of set-points. Figure 13.6 Responses of a P controller, a PI controller, and a PID controller for the step change of set-points.
Figure 7.5b gives Nyquist plots for the process with the furnace (FS2). First, note that the system is now openloop-sfaWe for values of reactor gain KR = 2, 3, which was not the case for the FS 1 flowsheet. Second, observe that even for reactor gains up to about KR = 8 it is possible to use a P controller to stabilize the system. Remember that we are talking about the GYi(s) controller, with the G<2ls) controller on automatic (Kcl = 2.13 and rn = 1-94). [Pg.375]

This improvement is true for both flowsheets, as a comparison of Figures 7.5 and 7.6 reveals. For example, in the process without the furnace, a P controller could not stabilize the system for KR = 5. However, the PI controller can stabilize the system. [Pg.376]

Loop 1 is cascaded with loop 2 to improve the response to disturbances in the cooling water temperature Tc w- The cooling water temperature is measured (TT2) and the signal sent to a second feedback controller TC2 which is normally a P-controller (see Figure 14). [Pg.269]

The SMBR plant is equipped with several sensors the temperature of the columns and the incoming streams are kept at around 60 °C by a closed heating water circuit that is controlled by a thermostat. Concentrations in the product line and in the recycling loop are measured online using a combination of a density measurement unit and a polarimeter (Jupke et ah, 2002). The pressure in the recycling loop (i.e. at the inlet of the recycling pump) is maintained constant using a P-controller that varies the extract flow rate. [Pg.412]

The above steps calculate the openloop response of the system with the input fixed. To calculate the closedloop response with a P controller manipulating Qi to control T3, we substitute for Q in Eq. (2.124) ... [Pg.55]

The proportional controller reacts immediately to an x-w jump with a proportional change in y. The ratio Aiv/Ay is known as the proportionality range Xp. The process leads to a value of x that generally deviates from the setpoint, that is, it is not possible to use a P controller to exacdy control x to the setpoint (permanent control deviation). [Pg.213]

Gas and liquid outlet flows were obtained by simulating a P-controller (equation 3) for which the liquid volume was evaluated from a step response experiment. [Pg.314]

Initial response Figure 1(a) shows the SDG for the DAE system. Initial response can be predicted by propagation through the shortest paths in this SDG. The controller effectively behaves as a P controller. Thus equation 4 and CSj can be eliminated from analysis. The remaining equations constitute model of a P controller. For non-zero disturbances or bias, the error, e / 0 (corresponds to imperfect control). Information flow is as expected. The SDG also shows the interaction between the control loop and the external system. [Pg.475]

Imperfect control is exhibited due to large external faults or control loop failure. The error signal is non-zero (Figure 1(a)). CS builds up till the controller saturates. Two scenarios are (i) large external disturbance, set point change or sensor bias in which the controller behaves as a P controller and, (ii) failure inside the control loop in which the control loop is open. Three types of failure are ... [Pg.476]

The PD controller obeys Eq. (88). It kicks in first very strongly the output then reverts back to a value that corresponds to the output of a P controller. [Pg.642]


See other pages where A p controller is mentioned: [Pg.261]    [Pg.478]    [Pg.375]    [Pg.59]    [Pg.124]    [Pg.396]   


SEARCH



P controller

© 2024 chempedia.info