Normal water level in the basin must be at least 6 inches above the top of the pump casing. [Pg.165]

Water velocity in the pump suction line should not exceed 8.5 ft/sec. In the discharge line, the water velocity should not be greater than 12 ft/sec to avoid excessive erosion of piping (especially where water containing grit is used). [Pg.165]

Each pump should be isolated with suction and discharge valves. [Pg.165]

Pumps should be provided with strainers at their suction inlet, normally with 3/8-inch screen openings to avoid leaves, pieces of wood and other foreign material from getting into the pump impeller. [Pg.165]

The design capacity of the pumps should be 110-115% of normal capacity. Pumps should have suitable spares, depending on the number of pumps provided for example, two 100% capacity or three 50% capacity pumps. For a large installation, where more than two pumps are required to operate simultaneously, one spare machine every two pumps should be provided. [Pg.165]


Figure 7.2 Various methods to prevent vortex formation. Figure 7.2 Various methods to prevent vortex formation.