Refrigerated inlet cooling is much more effective in humid areas and can add about 12.8% to the power output of the simple cycle gas turbine. The... [Pg.105]

FIG. 24-65 Mechanical refrigeration TIC systems utilizing chilled water for cooling turbine inlet air, and cooling towers to reject the waste heat into the environment, account for the majority of refrigeration TIC systems sold. [Pg.57]

An ideal Brayton refrigeration system uses air as a refrigerant. The pressure and temperature of air at compressor inlet are 14.7 psia and 100°F. The pressure and temperature of air at the turbine inlet are 60 psia and 260°F. The mass rate of air flow is 0.031bm/sec. Determine (a) the cooling load, (b) the compressor power required, (c) the turbine power produced, and (d) the cycle COP. [Pg.328]

Determine the COP, horsepower required, and cooling load of a Carnot vapor refrigeration cycle using R-12 as the working fluid and in which the condenser temperature is 100°F and the evaporation temperature is 20°F. The circulation rate of fluid is O.llbm/sec. Determine the compressor power required, turbine power produced, net power required, cooling load, quality at the inlet of the evaporator, quality at the inlet of the compressor, and COP of the refrigerator. [Pg.289]