Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Real factor values

After selection of the experimental design, the experiments can be defined. For this purpose, the level symbols, —1 and +1, as given in Tables 6 and 7, are replaced by the real factor values, as for instance shown in Tables 2 and 3, respectively, yielding the factor level combinations to be performed. Dummy factors in PB designs can be neglected during the execution of the experimental work. [Pg.199]

X is the coded value of the i-th factor (nondimensional magnitude) x , xi0 are natural or the real factor values, their current and null values, respectively Ax(e) is the natural value of the factor-variation interval. In a design matrix when we vary factors on two levels (+1 -1) only signs (+ -) exist. [Pg.268]

Design matrices of central composite rotatable designs (CCRD) for k=2, k=3 and k=5 are shown in Tables 2.138 - 2.140. By using relation (2.59), which connects coded and real factor values, we switch from design matrix to operational matrix, Table 2.138. [Pg.325]

After choosing the simplex matrix of design of experiments with coded factors, we should switch to an operational matrix with real factor values, taking into account factor-variation intervals and coordinates of the center of the experiment. The general formula for transfer from coded to real values (2.59) is also valid in this case ... [Pg.418]

Assume we have to do optimization of a phenomenon that is defined by four factors (k=4). We use Table 2.209 to apply simplex optimization and define the initial simplex. To determine the operational matrix, we should know factor values in the center of experiment and their variation intervals. These data are to be found in Table 2.210. Real factor values are obtained from relation (2.59) ... [Pg.419]

The radiation dose should not be over the value of 3.5+4 Mrd. The simplex optimization method was selected since response and single factor limitations do not interfere with this method. Simplex design matrix is obtained from Table 2.208 for k=2. Matrix elements are divided by the highest value of 0.578 so as to get initial simplex matrix, Table 2.218. Formulas for transformation from coded to real factor values have these forms ... [Pg.429]

After the choice of design of experiments matrix with coded factor values, one should switch to an operational matrix or to a matrix with real factor values. This shift from coded to real factor values is done by the known formula (2.59). Accord-... [Pg.431]

Coded and real factor values are connected by these relations, Table 2.227 ... [Pg.437]

Real world values do not allow a capacitor of this large a value. The largest value capacitor that will pass the ac leakage current test is 0.05 pF. This is 50 percent of the calculated capacitor value, so the inductor must be increased 200 percent in order to maintain the same corner frequency. The inductance then becomes 900 pH and the resultant damping factor is 2.5 which is acceptable. The resulting schematic is shown in Figure 3-77. [Pg.133]

When the (effective or real) g-values can be read from the spectrum (with Equation 2.6) then the factor I is known, and the EPR equivalent of Beer s law at fixed micro-wave frequency, v, has no unknowns except for the concentration c... [Pg.96]

It should be emphasized, however, that awareness in industry is not only an issue for individuals. Awareness of individuals is heavily influenced by social factors such as communication and cooperation with other key-actors and by (formal or informal) corporate incentives. Ultimately, awareness in industry is mainly a collective awareness. The collective awareness in a company is greatly dependent on (but also reflected by) the existing corporate culture. The corporate culture is known to reflect the real core values of a company (which is not by definition the same as the official core values such as presented in senior management statements ) on what is being rewarded or not in everyday practice, on subjects and issues that can be addressed or instead are offlimits, and on missing elements in the awareness of managers and employees. [Pg.494]

Fig.4. Trajectory for the real and imaginary parts of the resonant orbital energy E denoted by dots ( ) as a function of the rotation angle a with the starting value a = 0.0 at top right and the increment Aa = 0.02. The real factor is here fixed at the optimal value p = 0.775 as determined from Fig.2. Note that the distances between consecutive points ( ) are monotonically increasing in the beginning, but noticeably slowing down at the end which resembles a cusp. This phenomenon is associated with a resonance for further details see reference 10. Fig.4. Trajectory for the real and imaginary parts of the resonant orbital energy E denoted by dots ( ) as a function of the rotation angle a with the starting value a = 0.0 at top right and the increment Aa = 0.02. The real factor is here fixed at the optimal value p = 0.775 as determined from Fig.2. Note that the distances between consecutive points ( ) are monotonically increasing in the beginning, but noticeably slowing down at the end which resembles a cusp. This phenomenon is associated with a resonance for further details see reference 10.
The bioconcentration factor can be estimated by exposing fish or other aquatic organisms, for an appropriate time period, to a constant chemical concentration in water by using a flow-through system until a steady-state concentration in the organism is reached. However, for many chemicals - especially very hydrophobic chemicals - a steady-state cannot be reached in an appropriate time. Therefore, the kinetic approach is the only method which can be used for the determination of a real BCF value. [Pg.7]

Another interesting phenomenon can emerge under non-isothermal conditions for strongly exothermic reactions there will be multiple solutions to the coupled system of energy and mass balances even for the simplest first-order reaction. Such steady-state multiplicity results in the existance of several possible solutions for the steady state overall effectiveness factor, usually up to three with the middle point usually unstable. One should, however, note that the phenomenon is, in practice, rather rarely encountered, as can be understood from a comparison of real parameter values (Table 9.2). [Pg.384]

Firstly the unused columns Xg, X[o and of table 2.6 are "dummy variables" that do not correspond to any real factor. However, we may estimate the corresponding coefficients bg, b,o and in exactly the same way as we did for the effects of the real factors. The coefficients are independent of all the others, and, except for experimental error, they should be equal to zero. Their values should be thus indicate random fluctuations. It can be shown that the square of each of these coefficients is an independent estimate of the variance of the coefficients provided the additive model is correct. The mean of the 3 squares is an estimate of a/ with 3 degrees of freedom. [Pg.62]

In Equation 2.2, e"xp is the experimental loss factor value is direct current conductivity d and S are thickness and area of sample, respectively = 2nf(f is frequency) and is the permittivity of vacuum. As a general rule for polymers, is determined from fitting of the real component of the complex conductivity (a j. = where CTq and n are fitting parameters) measured in the low frequency range where a plateau is expected to appear. [Pg.18]

Since the signs of columns 12-15 in the table do not correspond to any real factors, we can use the values of their calculated contrasts as estimates of standard errors of the effects (assuming, of course, that all interactions are negligible). We can obtain a pooled estimate of the... [Pg.188]

Finally, we have noted that division of the ideal heating value per volume (which is the commonly tabulated value) by compressibility factor does not produce the real heating value per volume. It only permits use of the real gas flowrate in calculating q. ... [Pg.11]

The numerator of the transfer function tells us that the output is delayed by a factor which is a function of the length of the tube. All these zeros lie at 0, and can be ignored for purposes of determining the frequency response of the transfer function. The poles are evenly spaced on the unit circle at intervals of n/5. The first is at 7i/10 = 0.314, which when converted to a real frequency value with Equation 10.29, gives 500Hz. Subsequent resonances occur every lOOOHz after that, i.e. 1500Hz, 2500Hz and so on. [Pg.334]


See other pages where Real factor values is mentioned: [Pg.95]    [Pg.312]    [Pg.323]    [Pg.95]    [Pg.312]    [Pg.323]    [Pg.365]    [Pg.71]    [Pg.70]    [Pg.92]    [Pg.253]    [Pg.31]    [Pg.92]    [Pg.93]    [Pg.296]    [Pg.69]    [Pg.224]    [Pg.280]    [Pg.50]    [Pg.16]    [Pg.108]    [Pg.111]    [Pg.45]    [Pg.25]    [Pg.25]    [Pg.403]    [Pg.11]    [Pg.25]    [Pg.535]   
See also in sourсe #XX -- [ Pg.268 ]

See also in sourсe #XX -- [ Pg.268 ]




SEARCH



Value factor

© 2024 chempedia.info