The American standard ASTM D-2307 [12] provides a test method for measuring Relative thermal endurance properties of film insulated magnet wire . The ageing philosophy is similar to that required by IEC 60216 [9] and is based on the Arrhenius ageing model. Oven ageing is carried out at three specific temperatures. The samples are twisted wire... [Pg.156]

Curves for insulation, which have been oven aged at temperatures that might be expected in normal hght service and under conditions of overheating, are shown in Figure 5.2. [Pg.167]

IEC 60216-4, Sections 1-3, Guide for the determination of thermal endurance properties of electrical insulating materials. Part 4 Ageing ovens, 1990-2000. [Pg.80]

A test commonly used for estimating the lifetime of wire insulation is ANSI/AMTM procedure D-2307. Twisted pairs of insulated wire are aged in an oven for various time intervals (up to 50 days) at elevated temperatures (up to 240 °C) until voltage breakdown occurs. A series of such tests, performed at different oven temperatures, create a semi-logarithmic plot of lifetime versus the reciprocal of failure temperature. This procedure is useful but it is time consuming. For example, it takes many months for the... [Pg.129]


See other pages where Oven ageing insulation is mentioned: [Pg.387]    [Pg.172]    [Pg.175]    [Pg.205]    [Pg.168]    [Pg.430]    [Pg.81]    [Pg.262]    [Pg.123]    [Pg.315]   