Ejector systems Chilled water refrigeration

Dusts, particle sizes, 225 Dusts, hazard class, 521-523 Explosion characteristics, 524 Efficiency, centrifugal pumps, 200 Ejector control, 380 Ejector systems, 343, 344, 351 Air inleakage, table, 366, 367 Applications, 345 Calculations, 359-366 Chilled water refrigeration, 350 Comparison guide, 357, 375 Evacuation lime, 380, 381 Charts, 382 Example, 381 Features, 345... [Pg.626]

Ejector (steam-jet) refrigeration systems are used for similar apph-cations, when chilled water-outlet temperature is relatively high, when relatively cool condensing water and cheap steam at 7 bar are available, and for similar high duties (0.3-5 MW). Even though these systems usually have low first and maintenance costs, there are not many steam-jet systems running. [Pg.1117]

Capacity Control The simplest way to regulate the capacity of most steam vacuum refrigeration systems is to furnish several primary boosters in parallel and operate only those required to handle the heat load. It is not uncommon to have as many as four main boosters on larger units for capacity variation. A simple automatic on-off type of control may be used for this purpose. By sensing the chilled-water temperature leaving the flash tank, a controller can turn steam on and off to each ejector as required. [Pg.1123]


See other pages where Ejector systems Chilled water refrigeration is mentioned: [Pg.334]   
See also in sourсe #XX -- [ Pg.350 ]




SEARCH



Chill

Chill chilled))

Chilling systems

Ejector systems

Ejectors Water

Refrigerated water

Refrigeration systems

© 2024 chempedia.info