Zero-sequence current cross-bonded cable

Setup for measuring sequence currents for a cross-bonded cable (a) zero-sequence current and (b) positive-sequence current. [Pg.297]

Figure 3.8a shows the setup for measuring the zero-sequence current for a cross-bonded cable. [Pg.298]

The phase angle of the zero-sequence current mentioned in Table 3.1 demonstrates that grounding resistance at substations in both cross-bonded and solidly bonded cables significandy affects the zero-sequence current. As a result, there is litde difference in the zero-sequence impedance of the cross-bonded cable and the solidly bonded cable. The results indicate the importance of obtaining an accurate grounding resistance at the substations to derive accurate zero-sequence impedances of cable systems. [Pg.304]


See also in sourсe #XX -- [ Pg.250 , Pg.251 ]