Sizing, safety relief, 436, 437-441 API liquid valve, 444 Balanced valves, 441 Conventional valves, 438 Critical back pressure, 440 Effects of two-phase flow, 437 Hydraulic expansion, 441 Rupture disks, 434 Sub-critical flow, 449 Slurry flow, process pipe, 142-147 Regimes, 143... [Pg.630]

For conventional valves, pressure drop or variations in back pressure should not exceed 10% of set pressure. Because most process safety valves are sized for critical pressure conditions, the piping must accommodate the capacity required for valve relief and not have the pressure at the end of vent or manifold exceed the critical pressure. Designing for pressure 30% to 40% of critical w ith balanced valves, yields smaller pipes yet allows proper functioning of the valve. The discharge line size must not be smaller than the valve discharge. Check the manufacturer for valve performance under particular conditions, especially with balanced valves w hich can handle up to 70% to 80% of set pressure as back pressure. [Pg.431]

Where conventional Safety Relief Valves are used, the relief manifold system should be sized to limit the built-up back pressure to approximately 10% of the set pressure... [Pg.285]

Figure 5-5. Constant back pressure sizing factor, for conventional safety relief valves in vapor or gas service. (API Recommended Practice 520, Sizing, Selection and Installation of Pressure Relieving Devices in Refineries, Part 1, 5th ed., 1990. Reprinted courtesy of the American Petroleum Institute.)... Figure 5-5. Constant back pressure sizing factor, for conventional safety relief valves in vapor or gas service. (API Recommended Practice 520, Sizing, Selection and Installation of Pressure Relieving Devices in Refineries, Part 1, 5th ed., 1990. Reprinted courtesy of the American Petroleum Institute.)...
The maximum allowable back pressure (gauge) for a conventional safety relief valve is 10% of the set pressure (gauge). If the maximum allowable back pressure is exceeded during any relief situation, the size of the relief lines or headers should be increased until the back pressures are sufficiently reduced. ... [Pg.355]


See other pages where Sizing, safety relief Conventional valves is mentioned: [Pg.642]    [Pg.94]   
See also in sourсe #XX -- [ Pg.438 ]




SEARCH



Conventional safety relief

Conventional safety relief valve

Conventional safety valve

Relief conventional

Relief sizing

Relief valves

Safety relief valve

Safety relief valve sizing

Safety reliefs

Safety valve sizing

Safety valves

Sizing, safety relief

Valve sizing

© 2024 chempedia.info